Semi-Hermetic Compressor(3HP-20HP)

Usability:

•The same serial compressors are available for many kinds of refrigerants such as R134a, R404a, R407C and R22

•The same serial compressors are suitable for different operating temperatures.

Products Description

Message

Excellent functions:

•High efficiency motors.

•Great gap control, high quality and low energy consumption in order to achieve a higher refrigerating capacity.

•Great mass balance of driving parts, less vibration and lower noise.

Special design for the construction:

•BFBV20 56H(Y) applies coil motor with low starting current.

•The materials which can reduce the friction are used.

•The valves are constructed with buffer activation.

Reliability protector:

•Electronic module protector is installed in the motor to control its operating temperature.

•BFBV20 84.5(Y) use oil pump for a good lubrication system.

•BFBV20 56H(Y) is equipped with auto protector of high pressure release valve.

•Crankcase heater is applied for preventing liquid strike.

 

MODEL CONFIGURCTION INSTRUCTION


 

 

BFBZ Suction View

1. Terminal 2. Suction valve 3. Filter 4. Body 5. Main shaft 6. Crankshaft 7.Connective lever 8. Bottomplate 9. Electric heater 10. Rear shaft 11. Cap of rear shaft 12. Tube 13. Piston pin 14. Cylinder cap 15. Piston 16. Piston ring 17. Valve assembly 18. Motor

 

COMPRESSOR REFRIGERATION CAPACITY

R404A  Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

7.5

5

0

-5

5

-10

-20

-25

-30

-35

-40

-45

BFBZ3

12Y

30

Qo

 

 

 

9700

7860

6210

4640

3740

2730

2387

1460

1034

Pe

 

 

 

2.68

2.62

2.52

2.05

1.78

1.44

1.21

1.00

0.80

40

Qo

 

 

 

8200

6510

5150

3890

3060

2210

1600

1090

760

Pe

 

 

 

3.21

3.02

2.84

2.32

1.84

1.53

1.32

1.10

082

50

Qo

 

 

 

6750

5400

4300

3270

2640

1940

1350

840

 

Pe

 

 

 

3.65

3.19

3.14

2.64

2.07

1.71

1.38

0.95

 

BFBZ4

15Y

30

Qo

 

 

 

12150

9720

7820

6040

4520

2965

2210

1570

1110

Pe

 

 

 

3.32

3.03

2.89

2.41

1.94

1.47

1.26

1.03

0.82

40

Qo

 

 

 

10190

8650

6470

4900

3910

2540

1780

1380

950

Pe

 

 

 

3.68

3.43

3.22

2.56

2.05

1.76

1.45

1.12

0.86

50

Qo

 

 

 

8450

6710

5330

3980

3460

2160

1770

1110

 

Pe

 

 

 

4.27

3.54

3.23

2.82

2.37

1.96

1.53

1.09

 

BFBZ4

15HY

30

Qo

17910

16370

14110

12150

9720

7820

6040

4520

2965

2210

1570

1110

Pe

3.63

3.49

3.38

3.32

3.03

2.89

2.41

1.94

1.47

1.26

1.03

0.82

40

Qo

15790

14460

11890

10190

8650

6470

4900

3910

2540

1780

1380

950

Pe

3.88

3.74

3.69

3.68

3.43

3.22

2.56

2.05

1.76

1.45

1.12

0.86

50

Qo

13200

12140

10260

8450

6710

5330

3980

3460

2160

1770

1110

 

Pe

4.79

4.72

4.38

4.27

3.87

3.53

2.82

2.37

1.96

1.53

1.09

 

BFBZ5

18Y

30

Qo

 

 

 

15070

12410

10100

7800

6300

4550

3990

2420

1720

Pe

 

 

 

4.13

3.88

3.73

3.08

2.66

2.47

2.12

1.74

1.39

40

Qo

 

 

 

13020

10730

8650

6970

5350

3860

2800

1910

1320

Pe

 

 

 

4.89

4.53

4.29

3.60

2.85

1.98

1.62

1.25

0.96

50

Qo

 

 

 

11090

9120

7350

5830

4740

3480

2420

1510

 

Pe

 

 

 

5.60

5.26

4.86

4.13

3.24

2.68

2.09

1.48

 

BFBZ5

18HY

30

Qo

23480

21460

18240

15070

12410

10100

7800

6300

4550

2990

2420

 

Pe

4.56

4.36

4.22

4.13

3.88

3.73

3.08

2.66

2.47

2.12

1.74

 

40

Qo

20790

19040

16240

13020

10730

8650

6970

5350

3860

2800

1910

 

Pe

5.24

5.10

5.03

4.89

4.53

4.29

3.60

2.90

1.98

1.62

1.25

 

50

Qo

18030

16590

14230

11090

9120

7350

5830

4740

3480

2420

1510

 

Pe

6.57

6.21

5.99

5.60

5.26

4.86

4.13

3.24

2.68

2.09

1.48

 

BFBZ8

27HY

30

Qo

 

32100

26700

22860

17960

14270

11250

8550

6340

4720

3370

2390

Pe

 

6.36

6.03

5.83

5.38

4.92

4.37

3.67

3.08

2.64

2.17

1.73

40

Qo

 

27910

23000

18800

15070

11920

9500

7340

5660

4100

2800

1940

Pe

 

7.16

6.59

6.28

5.93

5.59

4.90

4.58

3.93

3.24

2.51

1.92

50

Qo

 

 

18900

15640

12800

10150

7810

6490

4780

3310

2070

 

Pe

 

 

7.89

7.70

7.38

6.71

5.84

4.78

3.95

3.09

2.19

 

BFBZ10

36Y

30

Qo

 

 

 

30400

24920

20200

15990

12580

9650

7190

5130

3640

Pe

 

 

 

7.88

7.74

7.47

6.51

5.41

4.66

3.99

3.28

2.62

40

Qo

 

 

 

26290

21710

17420

13930

10800

8320

6030

4100

2840

Pe

 

 

 

9.54

9.09

8.43

7.20

6.23

5.35

4.40

3.42

2.61

50

Qo

 

 

 

22470

18620

15090

12260

9550

7370

4880

3050

 

Pe

 

 

 

11.10

10.44

9.27

8.56

6.53

5.39

4.22

2.99

 

BFBZ10

36HY

30

Qo

45950

42000

35680

30400

24920

20200

15990

12580

9650

7190

5130

 

Pe

8.81

8.53

8.09

7.88

7.74

7.47

6.51

5.41

4.66

3.99

3.28

 

40

Qo

40660

37240

31770

26290

21710

17420

13830

10800

8230

6030

4110

 

Pe

9.95

9.80

9.70

9.54

9.09

8.43

7.20

6.23

5.35

4.40

3.42

 

50

Qo

34920

32110

27140

22470

18620

15090

12260

9550

7030

4880

3050

 

Pe

11.92

11.70

11.37

11.10

10.44

9.72

8.56

6.53

5.39

4.22

2.99

 

BFBZ15

54Y

30

Qo

 

 

 

42450

34370

27930

22340

17700

13720

10350

7510

5150

Pe

 

 

 

11.85

11.16

10.11

9.32

8.31

7.38

6.21

5.12

4.14

40

Qo

 

 

 

35420

29010

23320

18630

14590

11130

8220

5760

3730

Pe

 

 

 

13.41

12.23

11.17

10.09

8.74

7.39

6.12

4.92

3.83

50

Qo

 

 

 

 

23130

18620

14880

11390

8520

6130

4070

 

Pe

 

 

 

 

13.39

11.87

10.58

9.08

7.54

6.09

4.68

 

BFBZ15

54HY

30

Qo

67550

61850

52040

42850

35270

28110

22730

17920

13810

10080

7110

 

Pe

12.32

12.19

12.08

11.53

10.83

10.13

9.11

8.09

7.23

6.05

4.88

 

40

Qo

57190

52540

43800

36200

28790

23220

18600

14290

10760

7890

5290

 

Pe

14.83

14.53

13.74

12.86

11.82

10.74

9.74

8.43

7.11

5.88

4.71

 

50

Qo

46520

42690

34740

28610

23270

18660

14630

11200

8260

5880

3710

 

Pe

17.05

16.39

15.27

14.03

12.71

11.27

10.07

8.54

7.24

5.71

4.49

 

 

Note:

1Cooting capactity at 30℃sudion superheat over cold 5℃suction temperature 15℃ of medium-high temperature compressor.

2Add cooling fan in working condition,a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

 

COMPRESSOR REFRIGERATION CAPACITY

R404A  Watt(50Hz380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

7.5

5

0

-5

5

-10

-20

-25

-30

-35

-40

-45

BFBV3 18.1Y

30

Qo

 

 

 

13650

11270

9210

7430

5910

4610

3490

2570

1790

Pe

 

 

 

3.89

3.71

3.48

3.21

2.93

2.61

2.26

1.91

1.51

40

Qo

 

 

 

11500

9470

7700

6170

4860

3730

2770

1970

1300

Pe

 

 

 

4.47

4.15

3.81

3.44

3.06

2.65

2.26

1.83

1.41

50

Qo

 

 

 

9400

7710

6230

4940

3840

2890

2100

1420

 

Pe

 

 

 

4.97

4.53

4.09

3.63

3.16

2.71

2.24

1.79

 

BFBV5

18.1HY

30

Qo

21440

19690

16510

13740

11340

9270

7480

5940

4630

3510

2570

 

Pe

3.82

3.84

3.81

3.71

3.56

3.35

3.11

2.82

2.51

2.17

1.82

 

40

Qo

18150

16650

13950

11590

9530

7750

6210

4870

3740

2780

1960

 

Pe

4.71

4.65

4.51

4.31

4.03

3.73

3.39

3.01

2.61

2.22

1.77

 

50

Qo

14900

13660

11410

9450

7740

6250

4950

3840

2890

2080

1400

 

Pe

5.51

5.39

5.13

4.82

4.44

4.03

3.59

3.13

2.65

2.16

1.66

 

BFBV4 22.7Y

30

Qo

 

 

 

17240

14220

11600

9350

7410

5770

4370

3190

2210

Pe

 

 

 

4.66

4.44

4.17

3.85

3.49

3.09

2.67

2.25

1.81

40

Qo

 

 

 

14370

11810

9600

7680

6040

4630

3430

2420

1580

Pe

 

 

 

5.35

4.99

4.58

4.15

3.68

3.19

2.67

2.17

1.65

50

Qo

 

 

 

11590

9500

7680

6100

4730

3570

2570

1740

 

Pe

 

 

 

5.94

5.46

4.93

4.38

3.82

3.22

2.63

2.05

 

BFBV6

22.7HY

30

Qo

27360

25070

21000

17490

14430

11770

9480

7510

5830

4400

3200

 

Pe

4.79

4.81

4.79

4.67

4.49

4.22

3.89

3.52

3.12

2.67

2.23

 

40

Qo

23030

21140

17690

14670

12060

9790

7820

6130

4670

3450

2410

 

Pe

5.94

5.88

5.69

5.43

5.07

4.67

4.23

3.73

3.21

2.68

2.14

 

50

Qo

18840

17270

14420

11920

9740

7850

6210

4790

3580

2550

1700

 

Pe

6.95

6.82

6.46

6.03

5.55

5.02

4.43

3.83

3.23

2.62

1.99

 

BFBV5 26.8 Y

30

Qo

 

 

 

21000

17330

14150

11410

9050

7040

5340

3910

2720

Pe

 

 

 

5.59

5.36

5.05

4.68

4.24

3.75

3.23

2.69

2.14

40

Qo

 

 

 

17560

14450

11750

9410

7400

5690

4230

3000

1970

Pe

 

 

 

6.43

6.03

5.58

5.06

4.49

3.88

3.26

2.63

2.01

50

Qo

 

 

 

14260

11670

9440

7510

5850

4420

3200

2180

 

Pe

 

 

 

7.17

6.62

6.01

5.36

4.68

3.97

3.26

2.55

 

BFBV7

26.8HY

30

Qo

32440

29750

24870

20700

17030

13880

11150

8810

6820

5130

3710

 

Pe

5.57

5.59

5.58

5.47

5.25

4.95

4.58

4.16

3.68

3.16

2.62

 

40

Qo

27360

25070

20990

17400

14280

11570

9220

7210

5480

4020

2790

 

Pe

6.91

6.85

6.64

6.35

5.96

5.51

4.98

4.41

3.79

3.15

2.51

 

50

Qo

22390

20500

17120

14160

11560

9300

7340

5660

4220

2990

1970

 

Pe

8.08

7.94

7.57

7.11

6.55

5.94

5.27

4.56

3.83

3.07

2.31

 

BFBV6 32.5Y

30

Qo

 

 

 

24820

20550

16820

13600

10850

8500

6490

4820

3410

Pe

 

 

 

6.74

6.45

6.06

5.61

5.08

4.51

3.91

3.29

2.66

40

Qo

 

 

 

21000

17330

14130

11360

8980

6940

5210

3750

2530

Pe

 

 

 

7.75

7.27

6.72

6.12

5.45

4.74

3.99

3.25

2.51

50

Qo

 

 

 

17230

14150

11460

9140

7140

5430

3980

2760

 

Pe

 

 

 

8.73

8.08

7.38

6.61

5.78

4.94

4.06

3.17

 

BFBV9

32.5HY

30

Qo

38610

35420

29750

24780

20490

16790

13590

10840

8480

6500

4820

 

Pe

6.95

6.97

6.92

6.73

6.45

6.06

5.61

5.08

4.51

3.91

3.29

 

40

Qo

32690

30000

25170

20990

17320

14120

11370

8990

6960

5220

3750

 

Pe

8.47

8.39

8.13

7.75

7.28

6.72

6.11

5.44

4.72

3.99

3.24

 

50

Qo

26910

24720

20790

17290

14240

11560

9230

7200

5450

3940

2650

 

Pe

9.94

9.76

9.29

8.73

8.08

7.38

6.62

5.78

4.94

4.06

3.17

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited

 

 

COMPRESSOR REFRIGERATION CAPACITY

R404A  Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

7.5

5

0

-5

5

-10

-20

-25

-30

-35

-40

-45

BFBV8

41.3Y

30

Qo

 

 

 

32880

27110

22090

17800

14100

10940

8260

6010

4130

Pe

 

 

 

8.86

8.28

7.65

6.96

6.24

5.48

4.69

3.91

3.11

40

Qo

 

 

 

27610

22680

18380

14690

11500

8780

6490

4560

2940

Pe

 

 

 

9.99

9.17

8.31

7.44

6.54

5.64

4.71

3.78

2.84

50

Qo

 

 

 

 

18260

14720

11650

9020

6770

4850

3240

 

Pe

 

 

 

 

9.87

8.83

7.78

6.73

5.68

4.94

3.51

 

BFBV12

41.3HY

30

Qo

51240

46960

39250

32590

26760

21790

17460

13760

10600

7920

5670

 

Pe

8.74

8.75

8.61

8.33

7.91

7.38

6.77

6.08

5.32

4.53

3.72

 

40

Qo

43280

39650

33130

27410

22490

18170

14460

11260

8550

6240

4300

 

Pe

10.81

10.61

10.12

9.53

8.84

8.06

7.24

6.37

5.48

4.56

3.66

 

50

Qo

35220

32240

26910

22240

18140

14580

11490

8840

6560

4630

3010

 

Pe

12.45

12.11

11.32

10.47

9.55

8.56

7.55

6.51

5.46

4.41

3.41

 

BFBV10

48.5Y

30

Qo

 

 

 

38110

31440

25620

20600

16310

12630

9500

6880

4670

Pe

 

 

 

10.21

9.51

8.75

7.97

7.15

6.31

5.41

4.48

3.52

40

Qo

 

 

 

32140

26370

21390

17040

13330

10170

7480

5210

3330

Pe

 

 

 

11.55

10.59

9.59

8.56

7.51

6.43

5.36

4.31

3.25

50

Qo

 

 

 

 

21390

17200

13590

10500

7850

5610

3740

 

Pe

 

 

 

 

11.41

10.18

8.92

7.63

6.36

5.12

3.92

 

BFBV15

48.5HY

30

Qo

61190

56120

46860

38850

31940

25870

20700

16240

12430

9190

6470

 

Pe

10.37

10.33

10.09

9.71

9.18

8.54

7.81

6.99

6.12

5.21

4.28

 

40

Qo

51940

47610

39750

32880

26910

21740

17270

13420

10140

7350

4990

 

Pe

12.58

12.31

11.67

10.94

10.12

9.23

8.29

7.28

6.25

5.19

4.12

 

50

Qo

42390

38810

32340

26620

21690

17340

13610

10410

7670

5350

3400

 

Pe

14.47

13.96

12.95

11.89

10.79

9.68

8.54

7.35

6.21

5.01

3.81

 

BFBV12

56Y

30

Qo

 

 

 

43870

36180

29400

23520

18630

14440

10890

7900

5420

Pe

 

 

 

11.97

11.27

10.21

9.41

8.39

7.45

6.27

5.17

4.18

40

Qo

 

 

 

37280

30540

24550

19610

15360

11720

8650

6060

3930

Pe

 

 

 

13.47

12.36

11.23

10.19

8.83

7.46

6.18

4.97

3.87

50

Qo

 

 

 

 

24350

19600

15660

11990

8970

6450

4280

 

Pe

 

 

 

 

13.46

11.93

10.63

9.17

7.61

6.13

4.73

 

BFBV20

56HY

30

Qo

71100

65100

54780

45110

37130

29590

23930

18860

14540

10610

7480

 

Pe

12.38

12.26

12.14

11.59

10.94

10.23

9.21

8.18

7.31

6.11

4.93

 

40

Qo

60200

55300

46100

38100

30310

24440

19580

15040

11330

8300

5570

 

Pe

14.98

14.68

13.88

12.99

11.94

10.85

9.84

8.52

7.18

5.94

4.76

 

50

Qo

48970

44940

36570

30120

24490

19640

15400

11790

8700

6190

3910

 

Pe

17.14

16.48

15.35

14.11

12.84

11.38

10.12

8.63

7.31

5.77

4.51

 

 

Note: The refrigeration capacity is based on suction temperature 20℃, no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

 

COMPRESSOR REFRIGERATION CAPACITY

R404A Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

7.5

5

0

-5

5

-10

-20

-25

-30

-35

-40

-45

BFBV15

73.7Y

30

Qo

 

 

 

56750

46950

38510

31230

24980

19640

15090

 

8100

Pe

 

 

 

15.83

14.88

13.83

12.67

11.43

10.13

8.80

 

6.12

40

Qo

 

 

 

48350

39920

32590

26290

20860

16230

12280

 

6190

Pe

 

 

 

18.21

16.85

15.39

13.86

12.29

10.68

9.08

 

5.95

50

Qo

 

 

 

 

32930

26770

21390

16810

12870

9530

 

 

Pe

 

 

 

 

18.56

16.72

14.84

12.95

11.06

9.20

 

 

BFBV25

73.7HY

30

Qo

87980

80700

67610

56160

46320

37780

30410

24060

18630

14030

 

 

Pe

16.19

16.12

15.77

15.19

14.40

13.45

12.36

11.14

9.84

8.49

 

 

40

Qo

75080

68870

57720

47920

39430

32010

25660

20180

15450

11450

 

 

Pe

19.62

19.28

18.43

17.37

16.16

14.80

13.35

11.82

10.23

8.63

 

 

50

Qo

62570

57330

48020

39770

32590

26380

20950

16330

12360

 

 

 

Pe

22.85

22.25

20.90

19.39

17.76

16.03

14.22

12.38

10.52

 

 

 

BFBV20

84.5Y

30

Qo

 

 

 

58600

53570

44060

35860

28240

22310

17240

12920

9280

Pe

 

 

 

18.50

17.10

15.80

14.50

13.10

11.60

10.10

8.50

6.80

40

Qo

 

 

 

55970

47330

37970

30400

24220

18950

14430

10600

7370

Pe

 

 

 

20.70

19.00

17.40

15.70

13.90

12.20

10.30

8.50

6.50

50

Qo

 

 

 

 

38500

31390

25640

20240

15640

11690

8340

11280

Pe

 

 

 

 

20.80

18.90

16.90

14.80

12.80

10.60

8.40

7.45

BFBV30

84.5HY

30

Qo

98690

90540

75850

63210

52240

42780

34430

27480

21540

16210

12100

8960

Pe

19.00

18.80

18.20

17.40

16.40

15.30

14.00

12.60

11.00

9.40

7.70

7.49

40

Qo

85740

78660

65790

54830

45200

36820

29180

23160

17980

13860

8010

6710

Pe

22.20

21.80

20.90

19.60

18.20

16.70

15.10

13.40

11.60

9.90

8.20

7.39

50

Qo

71530

65620

54960

45610

37480

30420

24730

19470

14980

11230

7790

10150

Pe

25.80

25.10

23.60

21.90

20.10

18.20

16.30

14.30

12.20

10.30

8.30

7.10

BFBW25

110.5Y

30

Qo

 

 

 

83950

69600

56930

45890

36480

28810

22200

16580

11730

Pe

 

 

 

23.63

22.11

20.54

18.79

16.91

14.92

12.86

10.78

8.76

40

Qo

 

 

 

72090

59450

48440

39190

30950

23960

18220

13300

9040

Pe

 

 

 

27.15

25.13

22.96

20.64

18.25

15.23

13.33

10.91

8.55

50

Qo

 

 

 

 

48990

39920

32010

25170

19420

14460

10290

 

Pe

 

 

 

 

27.72

24.97

22.14

19.27

16.40

13.58

10.84

 

BFBW35

110.5HY

30

Qo

129880

119190

100320

83420

68740

56070

45120

35710

27940

21260

15570

 

Pe

25.06

24.71

23.97

23.01

21.73

20.25

18.60

16.80

14.88

12.86

10.82

 

40

Qo

112230

102870

86180

71500

59070

47960

38420

30180

23200

17320

12360

 

Pe

29.66

29.14

27.65

26.09

24.25

22.24

20.10

17.84

15.23

13.33

10.78

 

50

Qo

93220

85500

71500

59260

48890

39480

31430

24500

18690

13720

9570

 

Pe

34.10

33.07

31.12

28.90

26.51

23.99

21.37

18.67

15.93

13.33

10.82

 

BFBW30

126.8Y

30

Qo

 

 

 

96770

80350

66050

53760

43200

34130

26400

19780

14190

Pe

 

 

 

27.43

25.44

23.46

21.48

19.38

17.23

14.99

12.63

10.15

40

Qo

 

 

 

83580

68260

56300

45320

35870

27760

20900

15060

10160

Pe

 

 

 

30.69

28.22

25.74

23.27

20.69

18.07

15.36

12.58

9.71

50

Qo

 

 

 

 

57790

47090

37870

29900

23090

17270

12320

 

Pe

 

 

 

 

30.99

28.11

25.15

22.08

18.96

15.77

12.49

 

BFBW40

126.8HY

30

Qo

148130

135840

113860

94750

78240

64030

51840

41330

32520

24910

18570

 

Pe

28.22

27.92

27.03

25.84

24.35

22.73

20.79

18.67

16.40

14.01

11.47

 

40

Qo

128640

117980

98690

81980

67580

55100

44300

35140

27260

20640

15080

 

Pe

32.97

32.37

30.89

29.11

27.03

24.75

22.37

19.90

17.26

14.70

12.17

 

50

Qo

107330

98400

82370

68350

56160

45600

36530

28700

22080

16430

11680

 

Pe

38.31

37.22

35.05

32.57

29.90

27.13

24.16

21.19

18.18

15.23

12.37

 

BFBW40

151.6Y

30

Qo

 

 

 

115780

96000

78910

64130

51460

40610

31300

23380

16680

Pe

 

 

 

33.36

30.89

28.41

25.94

23.36

20.69

17.88

15.01

12.02

40

Qo

 

 

 

100420

83040

67970

54910

43680

34080

25820

18860

13000

Pe

 

 

 

36.80

33.86

30.89

27.82

24.65

21.38

18.14

14.80

11.4

50

Qo

 

 

 

 

68830

56060

45020

35470

27260

20300

14350

 

Pe

 

 

 

 

37.22

33.67

30.00

26.24

22.37

18.47

14.55

 

BFBW50

151.6HY

30

Qo

177410

162620

136220

113380

93500

76510

61820

49250

38590

29520

21940

 

Pe

36.13

35.66

34.42

32.81

30.89

28.69

26.26

23.67

20.95

18.15

15.31

 

40

Qo

153890

141120

117980

97920

80640

65370

52800

41760

32350

24380

17560

 

Pe

44.39

40.53

38.55

36.27

33.75

30.99

28.05

24.94

21.71

18.39

15.02

 

50

Qo

128260

117600

98300

81500

66910

54340

43390

34030

26060

19300

13610

 

Pe

47.47

46.12

43.26

40.19

36.94

33.51

29.93

26.23

22.42

18.53

14.57

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited .

 

COMPRESSOR REFRIGERATION CAPACITY

R134a  Watt(50Hz 380v )

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

BFBZ3

12Y

 

30

Qo

10910

9940

8960

8190

6490

5500

4360

3340

2310

1720

1170

Pe

1.66

1.63

1.59

1.55

1.50

1.40

1.35

1.24

1.01

0.85

0.67

40

Qo

9990

9050

8050

7390

6170

4830

3890

2910

1920

1410

930

Pe

2.06

2.02

1.96

1.90

1.87

1.68

1.56

1.39

1.10

0.90

0.68

50

Qo

8710

7940

7230

6520

5510

4180

3250

2530

1620

1350

940

Pe

2.49

2.49

2.42

2.35

2024

1.94

1.77

1.52

1.17

1.05

0.78

BFBZ4

15Y

30

Qo

12990

11830

10720

9700

8190

6890

5370

4200

2930

2070

1270

Pe

1.96

1.92

1.89

1.83

1.78

1.74

1.56

1.41

1.13

0.926

0.67

40

Qo

11920

10860

9850

8920

7180

6010

4650

3560

2410

1700

1170

Pe

2.44

2.39

2.33

2.26

2.08

2.01

1.78

1.56

1.20

1.10

0.77

50

Qo

10550

9620

8750

7960

6560

5240

4050

3090

1980

1580

1090

Pe

2.87

2.80

2.72

2.64

2.48

2.23

1.98

1.69

1.26

1.15

0.89

BFBZ4

15HY

50

Qo

10540

9600

8730

7950

6550

5230

4050

3090

1980

1580

1090

Pe

2.87

2.81

2.73

2.65

2.49

2.23

1.98

1.69

1.26

1.15

0.89

60

Qo

9010

8210

7470

6780

5580

4430

3390

2570

1620

 

 

Pe

3.22

3.21

3.02

2.93

2.72

2.45

2.13

1.82

1.3

 

 

70

Qo

7570

6890

6260

5670

4640

3670

2800

2100

1310

 

 

Pe

3.56

3.43

3.32

3.20

2.95

2.63

2.26

1.91

1.34

 

 

BFBZ5

18Y

30

Qo

17030

15510

13930

12720

10580

8550

6850

5430

3880

2860

1950

Pe

2.57

2.52

2.44

2.40

2.31

2.16

2.00

1.83

1.50

1.28

1.01

40

Qo

15690

14300

12970

11750

9810

7670

6410

4790

3440

2470

1630

Pe

3.22

3.14

3.06

2.96

2.84

2.56

2.35

2.09

1.71

1.40

1.06

50

Qo

14430

13150

11960

10800

9110

6880

5500

4270

2900

2720

1900

Pe

4.45

3.82

3.71

3.61

3.44

2.97

2.70

2.33

1.85

1.80

1.54

 

 

BFBZ5

18HY

 

50

Qo

14410

13130

11950

10880

9110

6880

5500

4270

2900

2700

1900

Pe

4.40

3.81

3.71

3.60

3.44

2.97

2.70

2.33

1.82

1.80

1.54

60

Qo

12310

11230

11210

9270

7740

5810

4610

3550

2370

 

 

Pe

4.53

4.27

4.13

4.00

3.78

3.21

2.89

2.51

1.96

 

 

70

Qo

10340

9420

8550

7750

6450

4820

3810

2900

1920

 

 

Pe

4.86

4.69

4.53

4.37

4.11

3.45

3.07

2.64

1.96

 

 

 

BFBZ8

27HY

50

Qo

19450

17730

16120

14660

12090

9710

7710

5890

3890

2970

 

Pe

6.11

5.15

5.00

4.86

4.57

4.20

3.78

3.22

3.17

2.75

 

60

Qo

16330

15160

13770

12260

10110

8090

6620

4890

3180

 

 

Pe

6.84

6.18

5.49

5.31

4.97

4.54

4.15

3.47

3.47

 

 

70

Qo

13710

12720

11520

10250

8450

6740

5460

4000

2570

 

 

Pe

7.59

6.79

6.02

5.80

5.40

4.88

4.42

3.76

3.70

 

 

BFBZ10

36Y

30

Qo

33190

30220

27490

24890

20710

17260

13770

10860

7750

5780

4140

Pe

5.00

4.91

4.81

4.69

4.51

4.36

4.01

3.66

3.01

2.58

2.14

40

Qo

30700

27980

25370

22990

19200

15490

12460

9650

6870

4990

 

Pe

6.29

6.15

5.99

5.82

5.56

5.17

4.47

4.22

3.43

2.85

 

50

Qo

27940

25470

23160

21050

17360

13950

11230

8770

6110

4370

 

Pe

8.78

7.40

7.19

6.98

6.57

6.03

5.51

4.79

3.88

3.17

 

BFBZ10

36HY

50

Qo

27940

25470

23160

21050

17360

13950

11230

8770

6110

4370

 

Pe

8.78

7.40

7.19

6.98

6.57

6.03

5.51

4.79

3.88

3.17

 

60

Qo

23870

21740

19780

17930

14760

11790

9410

7300

4990

 

 

Pe

8.98

8.25

8.00

7.75

7.21

6.51

5.90

5.16

4.00

 

 

70

Qo

20050

18240

16560

15000

12250

9780

7770

5950

4040

 

 

Pe

9.43

9.33

9.10

8.45

7.79

7.00

6.26

5.41

4.12

 

 

BFBZ15

54Y

30

Qo

46670

42450

38600

35070

28700

23250

18570

14610

11270

8470

6150

Pe

7.41

7.36

7.29

7.18

6.89

6.51

6.06

5.54

4.98

4.39

3.78

40

Qo

41530

37770

34330

31120

25390

20440

16210

12620

9580

7020

4880

Pe

9.12

8.92

8.71

8.45

7.91

7.29

6.62

5.88

5.14

4.37

3.58

50

Qo

36260

32960

29890

27050

21920

17500

13740

10530

7810

5520

3610

Pe

10.72

10.39

10.03

9.65

8.83

7.94

7.01

6.06

5.12

4.21

3.32

BFBZ15

54HY

50

Qo

36260

32960

29890

27050

21920

17500

13740

10530

7810

 

 

Pe

10.36

10.05

9.71

9.36

8.57

7.72

6.81

5.84

4.86

 

 

60

Qo

31080

28100

25360

22780

18200

14240

10850

7970

5520

 

 

Pe

11.59

11.13

10.65

10.16

9.13

8.05

6.94

5.80

4.67

 

 

70

Qo

25210

22780

20490

18340

14530

11220

8390

5980

3940

 

 

Pe

12.51

11.94

11.36

10.75

9.51

8.25

6.98

5.71

4.49

 

 

 

Note: Cooting capactity at 30℃ sudion superheat over cold 5℃ suction temperature 15℃ of medium-high temperature compressor.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end,or the inlet air temperature should be limited

 

COMPRESSOR REFRIGERATION CAPACITY

R134a Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

BFBV3

18.1Y

30

Qo

15640

14230

12930

11720

9570

7710

6130

4800

3670

2750

1960

Pe

2.24

2.22

2.20

2.16

2.08

1.96

1.82

1.66

1.48

1.27

1.04

40

Qo

13790

12530

11380

10300

8370

6720

5310

4110

3100

2240

1560

Pe

2.65

2.61

2.56

2.5

2.37

2.21

2.03

1.82

1.59

1.34

1.06

50

Qo

12010

10910

9890

8940

7250

5780

4540

3470

2580

1850

1210

Pe

3.06

2.98

2.89

2.81

2.62

2.42

2.19

1.95

1.67

1.36

1.02

BFBV5

18.1HY

50

Qo

11960

10870

9860

8910

7220

5770

4530

3470

2580

 

 

Pe

3.21

3.13

3.03

2.95

2.73

2.51

2.25

1.98

1.67

 

 

60

Qo

10280

9340

8460

7640

6180

4910

3830

2910

2150

 

 

Pe

3.61

3.51

3.39

3.27

3.02

2.73

2.43

2.11

1.75

 

 

70

Qo

8630

7830

7090

6400

5160

4080

3150

2400

1710

 

 

Pe

4.01

3.87

3.73

3.58

3.29

2.95

2.59

2.21

1.79

 

 

BFBV4

22.7Y

30

Qo

20290

18470

16780

15200

12410

10020

8010

6280

4860

3680

2750

Pe

2.82

2.86

2.88

2.88

2.83

2.73

2.58

2.39

2.17

1.92

1.64

40

Qo

17850

16220

14720

13330

10840

8720

6910

5380

4110

3040

2160

Pe

3.49

3.48

3.46

3.41

3.26

3.07

2.84

2.56

2.26

1.93

1.59

50

Qo

15430

14020

12700

11490

9310

7450

5850

4500

3360

2410

1630

Pe

4.15

4.08

3.99

3.91

3.66

3.37

3.04

2.68

2.28

1.87

1.43

BFBV6

22.7HY

50

Qo

15400

13980

12680

11480

9300

7450

5850

4500

3360

 

 

Pe

4.18

4.11

4.02

3.91

3.67

3.36

3.03

2.66

2.25

 

 

60

Qo

13080

11880

10750

9710

7830

6210

4820

3640

2640

 

 

Pe

4.84

4.71

4.55

4.39

4.03

3.62

3.18

2.71

2.21

 

 

70

Qo

10810

9820

8850

7980

6390

5010

3830

2820

1980

 

 

Pe

5.47

5.27

5.06

4.84

4.36

3.85

3.29

2.72

2.11

 

 

BFBV5

26.8Y

30

Qo

24110

22010

20020

18140

14840

12020

9590

7550

5820

4350

3150

Pe

3.63

3.57

3.51

3.44

3.28

3.09

2.87

2.63

2.36

2.06

1.73

40

Qo

21270

19360

17580

15950

13010

10480

8310

6480

4930

3640

2580

Pe

4.33

4.24

4.15

4.04

3.81

3.55

3.24

2.93

2.57

2.18

1.76

50

Qo

18520

16830

15270

13830

11230

9010

7090

5480

4110

2960

2040

Pe

4.99

4.87

4.74

4.59

4.29

3.95

3.58

3.17

2.72

2.24

1.73

BFBV7

26.8HY

50

Qo

18520

16810

15210

13770

11200

8990

7090

5470

4110

 

 

Pe

5.02

4.89

4.76

4.61

4.29

3.94

3.56

3.15

2.71

 

 

60

Qo

15840

14390

13040

11790

9560

7610

5970

4560

3370

 

 

Pe

5.65

5.49

5.31

5.13

4.73

4.31

3.84

3.35

2.81

 

 

70

Qo

13310

12080

10950

9880

7980

6330

4930

3720

2710

 

 

Pe

6.31

6.09

5.87

5.64

5.17

4.66

4.11

3.53

2.92

 

 

BFBV6

32.5Y

30

Qo

28960

26360

23960

21760

17810

14430

11530

9080

7030

5300

3870

Pe

4.38

4.31

4.22

4.13

3.82

3.66

3.37

3.06

2.71

2.34

1.95

40

Qo

25480

23180

21070

19100

15590

12570

10010

7820

5980

4430

3150

Pe

5.28

5.16

5.03

4.88

4.57

4.21

3.82

3.39

2.95

2.49

2.01

50

Qo

22100

20090

18270

16540

13470

10820

8560

6630

5000

3640

2510

Pe

6.11

5.93

5.75

5.56

5.14

4.68

4.19

3.68

3.15

2.58

1.99

BFBV9

32.5HY

50

Qo

22100

20100

18280

16550

13480

10820

8560

6630

5000

 

 

Pe

6.09

5.93

5.75

5.56

5.15

4.68

4.21

3.68

3.14

 

 

60

Qo

18870

17150

15550

14070

11420

9130

7170

5510

4100

 

 

Pe

6.89

6.66

6.42

6.17

5.65

5.11

4.52

3.91

3.26

 

 

70

Qo

15650

14230

12910

11660

9430

7510

5860

4470

3280

 

 

Pe

7.61

7.32

7.02

6.72

6.11

5.46

4.78

4.08

3.36

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

 

COMPRESSOR REFRIGERATION CAPACITY

R134a  Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

BFBV8

41.3Y

30

Qo

37630

34300

31160

28320

23130

18740

14970

11790

9090

6840

4980

Pe

5.08

5.15

5.19

5.19

5.08

4.86

4.55

4.17

3.75

3.29

2.85

40

Qo

33270

30280

27490

24890

20290

16340

12960

10080

7650

5620

3910

Pe

6.66

6.55

6.42

6.25

5.89

5.46

4.96

4.42

3.85

3.28

2.71

50

Qo

28760

26170

23720

21460

17380

13890

10890

8350

6190

4380

2910

Pe

7.92

7.68

7.41

7.13

6.55

5.92

5.25

4.56

3.86

3.16

2.45

BFBV12

41.3HY

50

Qo

28520

25870

23420

21120

17040

13530

10540

7980

5820

 

 

Pe

7.55

7.37

7.16

6.91

6.37

5.76

5.09

4.39

3.68

 

 

60

Qo

23960

21710

19590

17640

14130

11110

8540

6330

4520

 

 

Pe

8.53

8.22

7.89

7.54

6.82

6.05

5.24

4.42

3.59

 

 

70

Qo

19450

17590

15850

14230

11310

8790

6620

4780

3220

 

 

Pe

9.19

8.78

8.37

7.95

7.08

6.17

5.27

4.37

3.43

 

 

BFBV10

48.5Y

30

Qo

43950

40040

36410

33030

27000

21850

17430

13680

10520

7860

5640

Pe

5.91

6.04

6.11

6.13

6.02

5.76

5.36

4.86

4.32

3.75

3.19

40

Qo

38810

35280

32050

29060

23670

19020

15050

11680

8820

6410

4390

Pe

7.66

7.59

7.48

7.32

6.92

6.41

5.79

5.13

4.43

3.72

3.02

50

Qo

33520

30480

27640

24940

20190

16120

12610

9620

7080

4950

3210

Pe

9.14

8.89

8.59

8.29

7.61

6.87

6.08

5.27

4.42

3.59

2.77

BFBV15

48.5HY

50

Qo

34010

30820

27880

25140

20240

16020

12430

9370

6790

 

 

Pe

8.82

8.58

8.32

8.04

7.39

6.68

5.91

5.09

4.26

 

 

60

Qo

28670

25970

23420

21070

16830

13180

10060

7400

5160

 

 

Pe

9.84

9.48

9.09

8.71

7.86

6.97

6.04

5.07

4.09

 

 

70

Qo

23370

21120

18990

17030

13490

10440

7800

5560

3710

 

 

Pe

10.62

10.16

9.68

9.19

8.17

7.12

6.03

4.91

3.78

 

 

BFBV12

56Y

30

Qo

49880

45370

41260

37490

30670

24840

19850

15610

12040

9060

6570

Pe

7.48

7.43

7.36

7.25

6.96

6.58

6.12

5.61

5.03

4.43

3.81

40

Qo

44390

40380

36700

33270

26310

21850

17330

13480

10230

7500

5220

Pe

9.21

9.01

8.79

8.53

7.98

7.36

6.68

5.94

5.19

4.41

3.62

50

Qo

38760

35230

31950

28910

23420

18710

14680

11250

8340

5900

3860

Pe

10.83

10.49

10.13

9.75

8.92

8.02

7.08

6.12

5.17

4.24

3.35

BFBV20

56HY

50

Qo

39440

35770

32340

29210

23470

18590

14400

10820

7780

 

 

Pe

10.46

10.15

9.81

9.45

8.66

7.81

6.88

5.91

4.91

 

 

60

Qo

33220

30040

27100

24350

19450

15220

11590

8520

5900

 

 

Pe

11.71

11.24

10.76

10.26

9.22

8.13

7.01

5.86

4.72

 

 

70

Qo

26950

24350

21910

19610

15520

12000

8970

6390

4220

 

 

Pe

12.64

12.06

11.47

10.86

9.61

8.33

7.05

5.77

4.54

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃ no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited

 

COMPRESSOR REFRIGERATION CAPACITY

R134a Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

BFBV15

73.7Y

30

Qo

67030

60920

55290

50050

40690

32690

25900

20220

15440

11480

8250

Pe

10.43

10.10

9.77

9.44

8.77

8.09

7.40

6.69

5.97

5.22

4.43

40

Qo

59460

54030

48890

44230

35890

28710

22650

17560

13290

9760

6870

Pe

12.50

11.97

11.46

10.96

10.00

9.07

8.15

7.25

6.25

5.41

4.45

50

Qo

52480

47580

43070

38900

31430

25030

19640

15100

11310

8180

5630

Pe

14.28

13.58

12.91

12.26

11.02

9.84

8.72

7.61

6.53

5.45

4.35

BFBV25

73.7HY

50

Qo

52480

47580

43070

38900

31430

25030

19640

15100

11310

 

 

Pe

13.81

13.17

12.56

11.96

10.81

9.71

8.65

7.60

6.57

 

 

60

Qo

45690

41420

37440

33760

27160

21530

16800

12790

9470

 

 

Pe

15.09

14.31

13.57

12.85

11.47

10.16

8.92

7.71

6.55

 

 

70

Qo

39040

35360

31910

28710

23040

18180

14070

10610

7740

 

 

Pe

16.14

15.26

14.40

13.57

12.00

10.51

9.10

7.76

6.47

 

 

BFBV20

84.5Y

30

Qo

75360

68550

62210

56260

45800

36820

29240

22850

17460

13020

9380

Pe

12.50

12.20

11.80

11.50

10.80

10.00

9.20

8.30

7.30

6.30

5.30

40

Qo

66910

60770

55110

49830

40420

32400

25580

19870

15070

11110

7860

Pe

15.20

14.10

13.60

13.10

12.00

11.00

9.90

8.70

7.60

6.40

5.30

50

Qo

59040

53570

48480

43830

35480

28330

22280

17160

12900

9380

6510

Pe

16.70

15.90

15.00

14.50

13.10

11.70

10.30

9.00

7.70

6.40

5.10

BFBV30

84.5HY

50

Qo

59040

53570

48480

43830

35480

28330

22280

17160

12900

 

 

Pe

16.10

15.40

14.80

14.10

12.80

11.50

10.20

8.90

7.70

 

 

60

Qo

51550

46770

43340

38110

30720

24430

19090

14600

10820

 

 

Pe

17.70

16.80

16.00

15.10

13.50

12.00

10.50

9.00

7.60

 

 

70

Qo

44060

39930

36090

32490

26110

20690

16050

12170

8950

 

 

Pe

19.20

18.20

17.10

16.20

14.30

12.50

10.80

9.10

7.60

 

 

BFBW25

110.5Y

30

Qo

100170

91000

82600

74690

60800

48830

38700

30210

23070

17160

12320

Pe

15.68

15.18

14.68

14.18

13.17

12.16

11.12

10.06

8.97

7.84

6.67

40

Qo

88780

80680

73050

66100

53560

42900

33870

26200

19830

14570

10260

Pe

18.77

17.99

17.22

16.48

15.03

13.62

12.25

10.89

9.53

8.13

6.69

50

Qo

78260

71020

64270

58100

46900

37450

29340

22580

16900

12350

8620

Pe

21.49

20.38

19.41

18.42

16.56

14.79

13.09

11.45

9.82

8.19

6.54

BFBW35

110.5HY

50

Qo

78260

71020

64270

58100

46900

37450

29340

22580

16900

 

 

Pe

20.78

19.80

18.88

17.97

16.24

14.59

12.99

11.43

9.88

 

 

60

Qo

68230

61860

55870

50380

40580

32230

25090

19120

14140

 

 

Pe

22.69

21.49

20.38

19.32

17.24

15.27

13.39

11.59

9.84

 

 

70

Qo

58290

52790

47670

42900

34400

27170

21000

15850

11560

 

 

Pe

24.31

22.89

21.69

20.38

18.02

15.79

13.67

11.66

9.72

 

 

BFBW30

126.8Y

30

Qo

113180

102820

93310

84480

68740

55300

43870

34220

26210

19540

14070

Pe

18.75

18.31

17.83

17.33

16.24

15.07

13.79

12.45

11.01

9.52

7.96

40

Qo

100420

91200

82660

74780

60670

48670

38400

29810

22610

16670

11790

Pe

22.09

21.28

20.48

19.73

18.12

16.50

14.83

13.15

11.44

9.71

7.95

50

Qo

88610

80450

72870

65760

53180

42480

33410

25730

19340

14060

9750

Pe

25.11

23.99

22.89

21.79

19.68

17.58

15.53

13.51

11.54

9.59

7.68

BFBW40

126.8HY

50

Qo

88610

80450

75040

65760

53180

42480

34450

25730

19340

 

 

Pe

24.19

23.19

22.18

21.28

19.28

17.33

15.39

13.47

11.56

 

 

60

Qo

77280

70080

63360

57220

46130

36670

28660

21890

16280

 

 

Pe

26.61

25.31

24.10

22.79

20.38

18.06

15.80

13.60

11.46

 

 

70

Qo

66140

59900

54140

48770

39220

31010

24100

18260

13420

 

 

Pe

28.91

27.41

25.81

24.29

21.49

18.77

16.19

13.74

11.38

 

 

BFBW40

151.6Y

30

Qo

132860

120770

109630

99260

80830

65180

52840

40510

31100

23280

16870

Pe

22.29

21.69

21.18

20.58

19.35

17.98

16.51

14.93

13.25

11.49

9.63

40

Qo

117980

107230

97250

88030

71520

57500

45500

35420

27020

20020

14300

Pe

25.89

24.97

24.11

23.19

21.28

19.41

17.46

15.48

13.47

11.46

9.42

50

Qo

104350

94750

85920

77660

62980

50400

39890

30820

23280

17090

12020

Pe

29.98

28.61

27.21

25.89

23.19

20.68

18.23

15.85

13.53

11.27

9.07

BFBW50

151.6HY

50

Qo

104350

94750

85920

77660

62980

50400

39890

30820

23280

 

 

Pe

29.42

28.11

26.81

25.51

22.99

20.58

18.21

15.91

13.66

 

 

60

Qo

91200

82850

74980

67780

54820

43730

34320

26400

19820

 

 

Pe

32.73

30.92

29.22

27.61

24.49

21.49

18.74

16.11

13.61

 

 

70

Qo

78240

71040

64220

57980

46800

37200

29090

22270

16560

 

 

Pe

35.34

33.23

31.32

29.42

25.91

22.59

19.47

16.56

13.77

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃, no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

 

COMPRESSOR REFRIGERATION CAPACITY

R22 Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)  Power Consumption Pe(kw)

Evaporating temperature(°C)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

BFBZ3

12

30

Qo

 

 

 

 

 

8460

6820

5360

4080

3180

2300

Pe

 

 

 

 

 

2.30

2.28

2.15

1.85

1.56

1.14

40

Qo

 

 

 

 

 

7400

5830

4540

3380

2600

 

Pe

 

 

 

 

 

2.71

2.56

2.35

1.95

1.62

 

50

Qo

 

 

 

 

 

6320

4950

3850

2820

2180

 

Pe

 

 

 

 

 

3.01

2.78

2.48

2.10

1.75

 

BFBZ4

15

30

Qo

 

 

 

 

 

10590

8430

6750

5180

3480

2500

Pe

 

 

 

 

 

2.83

2.7

2.52

2.32

2.04

1.69

40

Qo

 

 

 

 

 

9200

7270

5700

4250

3320

 

Pe

 

 

 

 

 

3.26

3.03

2.75

2.45

2.15

 

50

Qo

 

 

 

 

 

7910

6160

4760

3430

2840

 

Pe

 

 

 

 

 

3.64

3.28

2.91

2.48

2.26

 

BFBZ4

15H

30

Qo

 

 

15710

14350

12330

10590

8430

6750

5180

3840

2500

Pe

 

 

3.24

3.10

2.96

2.83

2.7

2.52

2.32

2.04

1.69

40

Qo

 

 

14510

13250

10820

9200

7270

5700

4250

3320

 

Pe

 

 

3.95

3.72

3.49

3.26

3.03

2.75

2.45

2.15

 

50

Qo

 

 

12850

11740

9780

7910

6160

4760

3430

2840

 

Pe

 

 

4.66

4.34

4.02

3.64

3.28

2.91

2.48

2.26

 

BFBZ5

18

30

Qo

 

 

 

 

 

13140

10760

8720

6860

5300

3840

Pe

 

 

 

 

 

3.54

3.38

3.18

2.93

2.65

2.32

40

Qo

 

 

 

 

 

11750

9600

7620

6050

4540

 

Pe

 

 

 

 

 

4.12

3.84

3.54

3.18

2.82

 

50

Qo

 

 

 

 

 

10380

8370

6570

5030

3890

 

Pe

 

 

 

 

 

4.61

4.24

3.81

3.35

2.89

 

BFBZ5

18H

30

Qo

24580

22550

20600

18810

15940

13140

10760

8720

6860

5360

3840

Pe

4.64

4.53

4.42

4.11

3.83

3.54

3.38

3.18

2.93

2.65

2.32

40

Qo

22810

20920

19110

17450

14780

11750

9600

7620

6050

4540

 

Pe

5.05

4.96

4.85

4.64

4.38

4.12

3.84

3.54

3.18

2.82

 

50

Qo

 

19230

17560

16040

13570

10380

8370

6570

5030

3890

 

Pe

 

5.54

5.38

5.17

4.93

4.61

4.24

3.81

3.35

2.89

 

BFBZ8

27H

30

Qo

 

 

30810

28140

22790

19930

15580

12320

9650

7270

5350

Pe

 

 

5.25

5.13

5.00

4.88

4.56

4.14

3.79

3.38

2.98

40

Qo

 

 

28010

25580

20930

16970

13480

10500

8250

6230

 

Pe

 

 

6.20

6.31

5.91

5.47

5.02

4.55

4.04

3.53

 

50

Qo

 

 

23670

21620

18020

14650

11740

9070

6740

5330

 

Pe

 

 

7.58

7.10

6.62

6.06

5.46

5.01

4.33

3.85

 

BFBZ10

36

30

Qo

 

 

 

 

 

26510

21620

17450

13720

10700

8140

Pe

 

 

 

 

 

7.22

6.82

6.31

5.81

5.26

4.71

40

Qo

 

 

 

 

 

23730

19420

15350

12100

9160

 

Pe

 

 

 

 

 

8.28

7.68

6.97

6.31

5.65

 

50

Qo

 

 

 

 

 

21040

17090

13490

10580

7840

 

Pe

 

 

 

 

 

9.24

8.38

7.58

6.72

5.86

 

BFBZ10

36H

30

Qo

47890

43930

40310

36810

31190

26510

21620

17450

13720

10700

8140

Pe

8.83

8.62

8.36

8.03

7.62

7.22

6.82

6.31

5.81

5.26

4.71

40

Qo

44620

40930

37380

34140

28910

23730

19420

15350

12100

9160

 

Pe

10.62

10.41

9.98

9.45

8.89

8.28

7.68

6.97

6.31

5.65

 

50

Qo

 

37240

34010

31056

25880

21040

17090

13490

10580

7840

 

Pe

 

11.38

11.16

10.66

10.05

9.24

8.38

7.58

6.72

5.86

 

BFBZ15

54

30

Qo

 

 

 

 

 

38960

31750

25350

20170

15700

11980

Pe

 

 

 

 

 

10.40

9.91

9.21

8.34

7.47

6.67

40

Qo

 

 

 

 

 

34890

28260

22560

17800

13430

 

Pe

 

 

 

 

 

11.92

11.02

9.98

8.94

7.89

 

50

Qo

 

 

 

 

 

30700

24880

19650

15580

11490

 

Pe

 

 

 

 

 

13.30

12.12

10.86

9.61

8.37

 

BFBZ15

54H

30

Qo

73900

67790

62910

56510

47620

39590

32000

25370

19860

 

 

Pe

11.62

11.35

11.15

10.98

10.55

10.20

9.75

9.07

8.16

 

 

40

Qo

65770

61330

55960

49760

42560

35460

28600

22780

17760

 

 

Pe

13.91

13.68

13.38

12.87

12.26

11.65

10.84

10.07

9.12

 

 

50

Qo

 

56040

51180

46740

38600

31140

25160

19860

15740

 

 

Pe

 

14.93

14.78

14.56

13.96

13.10

11.97

10.75

9.42

 

 


Note: Cooting capactity at 30℃ sudion superheat over cold 5℃suction temperature 15℃ of medium-high temperature compressor.

Add cooling fan in working condition,heat fan are veguived the air voeume 15m³/min.

 

COMPRESSOR REFRIGERATION CAPACITY

R22  Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt) Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

-35

-40

BFBV3

18.1

30

Qo

 

 

 

 

 

12500

10170

8140

6930

5440

4210

3160

2280

Pe

 

 

 

 

 

3.26

3.09

2.87

2.69

5440

2.19

1.93

1.71

40

Qo

 

 

 

 

 

11000

8850

7010

5890

4560

3460

2530

1770

Pe

 

 

 

 

 

3.79

3.49

3.18

2.97

2.63

2.29

1.97

1.71

50

Qo

 

 

 

 

 

9460

7520

5830

4860

3690

2740

1940

 

Pe

 

 

 

 

 

4.23

3.83

3.44

3.26

2.89

2.52

2.13

 

BFBV5

18.1H

30

Qo

23670

21680

20090

18160

15230

12520

10180

8150

6420

4980

3700

 

 

Pe

2.85

2.97

3.07

3.14

3.18

3.12

2.99

2.81

2.58

2.33

2.07

 

 

40

Qo

21150

19360

17710

16150

13470

11010

8860

7010

5420

4050

2940

 

 

Pe

4.01

4.03

4.02

3.99

3.87

3.67

3.41

3.12

2.81

2.49

2.21

 

 

50

Qo

18610

17080

15520

14240

11680

9450

7510

5820

4390

3190

 

 

 

Pe

5.01

4.94

4.85

4.73

4.46

4.13

3.77

3.39

3.02

2.68

 

 

 

BFBV4

22.7

30

Qo

 

 

 

 

 

15460

12600

10140

8640

6790

5230

3950

2880

Pe

 

 

 

 

 

3.98

3.79

3.56

3.33

3.07

2.77

2.42

2.09

40

Qo

 

 

 

 

 

13560

10960

8700

7400

5740

4350

3230

2280

Pe

 

 

 

 

 

4.61

4.29

3.93

3.67

3.34

2.94

2.56

2.17

50

Qo

 

 

 

 

 

11620

9260

7210

6040

4600

3410

2420

 

Pe

 

 

 

 

 

5.13

4.69

4.26

4.03

3.59

3.06

2.49

 

BFBV6

22.7H

30

Qo

29350

26950

24700

22590

18780

15480

12610

10140

8040

6220

4730

 

 

Pe

3.45

3.66

3.79

3.91

3.98

3.92

3.74

3.48

3.17

2.86

2.58

 

 

40

Qo

26220

24100

21950

20040

16590

13570

10970

8710

6770

5110

3730

 

 

Pe

4.98

5.05

5.04

5.01

4.82

4.55

4.23

3.85

3.47

3.11

2.83

 

 

50

Qo

23090

21020

19180

17450

14340

11610

9260

7200

5450

4010

 

 

 

Pe

6.33

6.24

6.08

5.95

5.57

5.13

4.64

4.18

3.77

3.42

 

 

 

BFBV5

26.8

30

Qo

 

 

 

 

 

18570

15130

12160

10040

7870

6070

4550

3310

Pe

 

 

 

 

 

4.78

4.51

4.23

3.94

3.63

3.28

2.93

2.55

40

Qo

 

 

 

 

 

16330

13190

10480

8650

6740

5120

3740

2620

Pe

 

 

 

 

 

5.57

5.16

4.71

4.37

3.96

3.51

3.08

2.63

50

Qo

 

 

 

 

 

14050

11200

8840

7130

5460

4040

2890

 

Pe

 

 

 

 

 

6.24

5.67

5.11

4.69

4.24

3.83

3.41

 

BFBV7

26.8H

30

Qo

35310

32400

30100

27160

22550

18580

15140

12160

9920

7520

5650

 

 

Pe

4.25

4.39

4.51

4.59

4.66

4.57

4.42

4.17

3.86

3.52

3.15

 

 

40

Qo

31530

28860

26390

24110

20140

16330

13190

10480

8150

6210

4500

 

 

Pe

5.84

5.87

5.87

5.83

5.68

5.41

5.07

4.68

4.25

3.83

3.36

 

 

50

Qo

27650

25320

23090

21050

17300

14050

11200

8840

6710

4870

 

 

 

Pe

7.29

7.21

7.08

6.95

6.57

6.16

5.67

5.15

4.63

4.08

 

 

 

BFBV6

32.5

30

Qo

 

 

 

 

 

22260

18180

14820

11760

9150

7010

 

 

Pe

 

 

 

 

 

5.77

5.49

5.18

4.81

4.38

3.92

 

 

40

Qo

 

 

 

 

 

19650

16080

12820

10020

7620

5650

 

 

Pe

 

 

 

 

 

6.63

6.18

5.73

5.24

4.67

4.08

 

 

50

Qo

 

 

 

 

 

16980

13730

10770

8220

6090

 

 

 

Pe

 

 

 

 

 

7.52

6.93

6.33

5.67

5.01

 

 

 

BFBV9 32.5H

30

Qo

42430

38560

35360

32350

27020

22260

18190

14820

11760

9140

7010

 

 

Pe

5.53

5.68

5.83

5.91

5.94

5.79

5.54

5.19

4.76

4.33

3.94

 

 

40

Qo

37740

34580

31640

28960

23980

19650

16080

12830

10030

7630

5660

 

 

Pe

7.46

7.42

7.37

7.25

7.01

6.66

6.24

5.73

5.21

4.67

4.14

 

 

50

Qo

33230

30510

27800

25420

21060

16980

13730

10770

8210

6090

 

 

 

Pe

9.28

9.06

8.84

8.56

8.07

7.52

6.93

6.31

5.67

4.98

 

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

Add cooling fan in working condition and change the suction valve location.

 

COMPRESSOR REFRIGERATION CAPACITY

R22  Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(watt)   Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

-35

-40

BFBV8

41.3

30

Qo

 

 

 

 

 

30180

24450

20110

16040

12630

9630

7170

5170

Pe

 

 

 

 

 

7.31

6.93

6.45

5.87

5.28

4.67

4.03

3.37

40

Qo

 

 

 

 

 

26390

21490

17310

13870

10780

8040

5810

4010

Pe

 

 

 

 

 

8.39

7.78

7.13

6.44

5.72

5.07

4.32

3.51

50

Qo

 

 

 

 

 

22750

18480

14950

11640

8870

6510

4520

2910

Pe

 

 

 

 

 

9.41

8.59

7.74

6.91

6.11

5.26

4.38

3.45

BFBV12 41.3H

30

Qo

55390

51350

46660

42680

35600

30120

24310

20040

15610

12160

9230

 

 

Pe

6.93

7.05

7.14

7.19

7.18

7.02

6.72

6.29

5.77

5.15

4.45

 

 

40

Qo

50120

45250

41470

37930

31580

26260

21190

17040

13570

10470

7820

 

 

Pe

9.08

9.05

8.97

8.85

8.53

8.08

7.58

6.97

6.28

5.56

4.79

 

 

50

Qo

43070

40040

36130

33030

27360

22460

18210

14530

11500

8780

 

 

 

Pe

11.08

10.89

10.65

10.39

9.83

9.14

8.39

7.61

6.75

5.87

 

 

 

BFBV10

48.5

30

Qo

 

 

 

 

 

34580

28380

23010

18560

14560

11110

8230

5810

Pe

 

 

 

 

 

8.45

8.06

7.51

6.89

6.16

5.48

4.72

3.96

40

Qo

 

 

 

 

 

30520

24940

20120

16060

12460

9310

6710

4590

Pe

 

 

 

 

 

9.75

9.06

8.27

7.45

6.58

5.69

4.85

4.03

50

Qo

 

 

 

 

 

26480

21490

17170

13520

10300

7550

5230

3320

Pe

 

 

 

 

 

10.93

9.96

8.94

7.97

6.94

5.91

4.95

4.05

BFBV15 48.5H

30

Qo

66350

61540

55870

51120

42490

35070

28620

23040

18430

14300

10780

 

 

Pe

8.35

8.47

8.53

8.56

8.48

8.21

7.83

7.29

6.67

5.95

5.15

 

 

40

Qo

59690

54230

50180

45410

37680

30990

25220

20130

16030

12300

9130

 

 

Pe

10.67

10.59

10.47

10.31

9.89

9.36

8.73

8.02

7.22

6.38

5.49

 

 

50

Qo

51700

47430

43360

40050

32790

26870

21730

17320

13660

10410

 

 

 

Pe

12.87

12.59

12.29

11.95

11.24

10.46

9.62

8.71

7.75

6.74

 

 

 

BFBV12

56

30

Qo

 

 

 

 

 

39920

32740

26580

21250

16700

12610

9320

6630

Pe

 

 

 

 

 

10.10

9.54

8.81

8.05

7.17

6.31

5.43

4.60

40

Qo

 

 

 

 

 

35550

29060

23430

18600

14470

10710

7720

5240

Pe

 

 

 

 

 

11.51

10.67

9.71

8.67

7.65

6.74

5.72

4.83

50

Qo

 

 

 

 

 

31090

25270

20230

15670

11920

8710

6020

3840

Pe

 

 

 

 

 

12.78

11.68

10.54

9.41

8.16

6.97

5.87

4.92

BFBV20

56H

30

Qo

76730

70420

64600

59070

49280

40640

33170

26770

21240

16470

12430

 

 

Pe

11.61

10.62

10.58

10.52

10.29

9.93

9.40

8.77

8.05

7.15

6.28

 

 

40

Qo

68480

62760

57520

52570

43650

35890

29150

24050

18340

14070

10430

 

 

Pe

13.18

13.06

12.85

12.63

12.16

11.34

10.57

9.58

8.59

7.54

6.48

 

 

50

Qo

59950

56500

51600

46930

38820

31590

25220

20030

15570

11760

 

 

 

Pe

15.84

15.42

15.04

14.59

13.65

12.63

11.46

10.28

9.12

7.79

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

Add cooling fan in working condition, cooling fan and cooling spray system should be fixed at the cylinder end.

 

 

COMPRESSOR REFRIGERATION CAPACITY

R22 Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

 Capacity Qo(watt)   Power Consumption Pe(kw)

Evaporating temperature(℃)

12.5

10

7.5

5

0

-5

-10

-15

-20

-25

-30

-35

-40

BFBV15

73.7

30

Qo

 

 

 

 

 

50730

41420

33420

26530

20660

15910

11640

8060

Pe

 

 

 

 

 

12.77

11.97

11.04

10.01

8.85

8.27

7.15

6.00

40

Qo

 

 

 

 

 

45440

34670

29590

23330

17950

13420

9510

6250

Pe

 

 

 

 

 

14.95

13.85

12.60

11.22

9.79

8.70

7.32

5.92

50

Qo

 

 

 

 

 

40450

32690

26000

20270

15330

11160

7680

4820

Pe

 

 

 

 

 

17.16

15.72

14.17

12.51

10.88

9.24

7.55

5.81

BFBV25 73.7H

30

Qo

96320

88470

81090

74210

61790

51020

41660

33610

26680

20760

15770

 

 

Pe

13.93

13.78

13.60

13.38

12.88

12.57

11.51

10.66

9.70

8.62

7.43

 

 

40

Qo

87010

79830

73140

66830

55580

45740

37200

29880

23520

18110

13520

 

 

Pe

16.80

16.52

16.21

15.88

15.10

14.21

13.85

12.11

10.88

9.55

8.10

 

 

50

Qo

78090

71590

65570

59850

49570

40690

32930

26240

20470

15550

 

 

 

Pe

19.62

19.22

18.80

18.32

17.30

16.15

14.87

13.48

11.98

10.36

 

 

 

BFBV20

84.5

30

Qo

 

 

 

 

 

58080

47520

38400

30500

23850

18240

13420

9340

Pe

 

 

 

 

 

14.60

13.60

12.60

11.50

10.30

9.60

8.40

7.10

40

Qo

 

 

 

 

 

52230

40480

34230

27010

20740

15980

11380

7500

Pe

 

 

 

 

 

17.40

16.10

14.60

13.10

11.90

10.30

8.70

7.10

50

Qo

 

 

 

 

 

46570

35960

30250

23420

17780

13420

9280

 

Pe

 

 

 

 

 

20.00

18.40

16.60

14.90

13.10

11.20

9.20

 

BFBV30 84.5H

30

Qo

109540

100620

92270

84400

70730

58080

47520

38400

30500

23850

18270

 

 

Pe

16.50

16.30

16.00

15.70

15.10

14.30

13.50

12.40

11.30

10.20

9.00

 

 

40

Qo

99080

90920

83340

76240

63380

52230

40480

34230

27010

20980

15880

 

 

Pe

19.80

19.40

19.10

18.70

17.80

16.80

15.60

14.30

12.90

11.30

9.70

 

 

50

Qo

89000

81610

74800

68270

56660

46570

35960

30250

23770

18280

 

 

 

Pe

23.30

22.80

22.30

21.70

20.40

19.00

17.60

16.03

14.50

12.90

 

 

 

BFBW25

110.5

30

Qo

 

 

 

 

 

76070

62180

50200

40040

31180

23690

17420

12090

Pe

 

 

 

 

 

18.91

17.71

16.34

14.82

13.10

12.22

10.59

8.91

40

Qo

 

 

 

 

 

68340

55770

44700

35240

26920

20030

14210

9370

Pe

 

 

 

 

 

22.18

20.49

18.65

16.63

14.48

12.88

10.85

8.77

50

Qo

 

 

 

 

 

60910

49600

39270

30410

23040

16800

11590

7290

Pe

 

 

 

 

 

25.35

23.27

20.99

18.50

16.12

13.67

11.16

8.62

BFBW35 110.5H

30

Qo

143180

131600

120500

110400

91970

76550

62570

50490

40230

31430

23500

 

 

Pe

20.85

20.39

20.20

19.83

19.08

18.16

17.07

15.81

14.37

12.78

11.05

 

 

40

Qo

129490

118930

109020

99800

83080

68820

56050

45050

35580

27180

20150

 

 

Pe

25.03

24.45

24.06

23.47

22.38

21.10

19.58

17.94

16.13

14.16

12.08

 

 

50

Qo

116560

106880

97860

89550

74270

61300

49730

39610

30750

23380

 

 

 

Pe

29.25

28.51

28.01

27.13

25.64

23.96

22.11

20.04

17.74

15.42

 

 

 

BFBW30

126.8

30

Qo

 

 

 

 

 

87170

71330

57600

45890

35860

27360

20160

14020

Pe

 

 

 

 

 

21.68

20.30

18.73

17.08

15.29

14.31

12.48

10.56

40

Qo

 

 

 

 

 

78340

63840

51360

40610

31200

23230

16550

10920

Pe

 

 

 

 

 

25.84

23.86

21.78

19.41

17.67

15.36

12.96

10.55

50

Qo

 

 

 

 

 

69890

56740

45360

35230

26740

19540

13510

8500

Pe

 

 

 

 

 

29.80

27.22

24.65

22.08

19.46

16.65

13.68

10.53

BFBW40

126.8H

30

Qo

164350

150910

138340

126620

105500

87170

71330

57600

45890

35860

27410

 

 

Pe

24.55

24.16

23.76

23.36

22.37

21.19

19.30

18.42

16.85

15.17

13.37

 

 

40

Qo

148700

136510

125090

114340

95130

78340

63840

51360

40610

31490

23810

 

 

Pe

29.30

28.91

28.41

27.82

26.43

24.95

23.17

21.19

19.09

16.80

14.37

 

 

50

Qo

133540

122500

112130

102530

85110

69890

56740

45360

35660

27410

 

 

 

Pe

34.65

33.86

33.07

32.18

30.29

28.22

26.04

23.76

21.48

19.15

 

 

 

BFBW40

151.6

30

Qo

 

 

 

 

 

102820

84190

68160

54430

42770

32740

24240

17040

Pe

 

 

 

 

 

27.03

25.15

23.07

20.89

18.48

16.88

14.82

12.87

40

Qo

 

 

 

 

 

92640

75650

61060

48480

37340

28030

20160

13490

Pe

 

 

 

 

 

31.68

29.30

26.83

24.06

21.29

18.43

15.61

12.87

50

Qo

 

 

 

 

 

82850

67490

54240

42340

32350

23810

16680

10690

Pe

 

 

 

 

 

35.94

33.08

30.00

26.83

23.46

20.00

16.47

12.87

BFBW50 151.6H

30

Qo

193060

177310

162720

148990

124220

102820

84190

67160

54430

42770

32880

 

 

Pe

31.68

31.09

30.49

29.80

28.41

26.73

24.95

22.97

20.79

18.55

16.18

 

 

40

Qo

174820

160510

147170

134690

112220

92640

75650

61060

48480

37820

28850

 

 

Pe

37.22

36.43

35.74

34.85

32.07

31.09

28.91

26.43

23.86

21.19

18.22

 

 

50

Qo

157340

144380

132290

120960

100610

82850

67490

54240

42910

33260

 

 

 

Pe

42.47

41.68

40.69

39.70

37.52

35.05

32.37

29.50

26.43

23.27

 

 

 

 

Note: The refrigeration capacity is based on suction temperature 20℃,no degree of supercooling.

Add cooling fan in working condition, a cooling fan should be fixed at the cylinder end, or the inlet air temperature should be limited.

Add cooling fan in working condition, cooling fan and cooling spray system should be fixed at the cylinder end.

 

APPLIANCE SCOPE

 

Compressors

model

High/Medium temperature ,compressor (Take the H model)

Medium temperature compressor

Vapor temperature(R22) 

+ 12.5℃〜-25℃ (-30℃)

-5℃ ~-30℃ (-40℃)

Cooler temperature(R22) 

30℃ ~ 55℃

Suction temperature

Max. 20℃

Max. compression ratio

15

Max. working pressure

High pressure side 2.5MPa

Max. differential pressure

1.8MPa

Max. outlet air temperature

130℃ (the temperature of the exterior of the exhaust pipe 150mm away from the exhaust valve.)

Degree of overheating of inlet air

Least. 10k;Max.Promise not to exceed the highest exhaust temperature

Moter power

380V/3N ~/50Hz; 440V/3N ~/60Hz

Motor insulation level

Grade F

Allowance in voltage

Rated voltage ±10%

Unbalanced two-phase current

10%

Unbalanced two-phase voltage

2%

Max. start-up times per hour

6 times

Max. oil temperature of crankshaft box

80℃

High ambient temperature

43℃

 

Note:

1. For many reasons the running conditions of the compressor should be strictly limited to accord with the above-mentioned specifications.

2.If the vaporization temperature is between -15℃ to -30℃, a cooling fan should be fixed at the cylinder end. Air-cooled condenser flow needs no cooling fan.

3.If the vaporization temperature is between -20℃ to -40℃, cooling fan and cooling spray system should be fixed at the cylinder end.

 

TECHNICAL DATA

 

Compressors

model

Nominal power of motor (HP/KW)

Displacement (m³/h)

Cylinder numbers

Oil

quantity

Connecting

pipe

Power

supply

(V/Φ/Hz)

Electrical

parameters

Startrt

running

power(A)

Weight(kg)

Exhaust pipe (mm) uction pipe (mm) Max working current(A) Max power consumption(KW) 

BFBZ3

12(Y)

3/2.2

12

2

1.25

16.5

19.5

380~420V Y/3/50HZ

440~480V Y/3/60HZ

5.7

2.96

29

62

BFBZ4

15(Y)

3/2.2

15

2

1.85

19.5

25

5.7

2.96

29

86

BFBZ4

15H(Y)

4/3

15

2

1.85

19.5

25

7.6

4.03

42

88

BFBZ5

18(Y)

5/3.7

18

2

1.85

19.5

25

8.6

4.5

49

90

BFBZ5

18H(Y)

5/5.1

18

2

1.85

19.5

25

10.1

6.2

60

91

BFBZ8

27H(Y)

8/5.5

27

2

3.5

25.4

31.8

380 ~420V A

/3/50HZ 440 ~480V A

/3/60HZ

15

7.4

79

131

BFBZ10

36(Y)

10/7.5

36

2

3.5

25.4

31.8

17.6

8.4

112

138

BFBZ10

36H(Y)

10/9.6

36

2

3.5

25.4

31.8

19.4

11.52

126

140

BFBZ15

54(Y)

15/10.5

54

3

4.8

28

38

24.3

12.6

155

181

BFBZ15

54H(Y)

15/12

54

3

4.8

28

38

27.6

14.4

168

183

BFBV3

18.1(Y)

3/2.2

18.1

4

2.0

16

22

(220~240V A)

380~420V Y/3/50HZ

(265 - 290V A) 440~480V

Y/3/60HZ

(15.9)

/9.2

5.4

(76.6)

/44.2

82

BFBV5

18.1H(Y)

5/3.0

18.1

4

2.0

16

22

(18.7)

/10.8

6.2

(107.7)

162.2

86

BFBV4

22.7(Y)

4/3.0

22.7

4

2.0

16

28

(18.5)

/10.7

6.4

(92.7)

/53_2

84

BFBV6

22.7H(Y)

6/3.7

22.7

4

2.0

16

28

(22.9)

/13.2

7.9

(107.7)

162.2

86

BFBV5

26.8(Y)

5/3.7

26.8

4

2.0

22

28

(23.4)

/13.5

8.0

(107.7)

162.2

85.5

BFBV7

26.8(Y)

7/5.1

26.8

4

2.0

22

28

(27.5)

/15.9

9.0

(142.8)

/82.4

88.5

BFBV6

32.5(Y)

6/4.5

32.5

4

2.0

22

28

(27.5)

/15.9

9.0

(142.8)

/82.4

90.5

BFBV9

32.5H(Y)

9/5.5

32.5

4

2.0

22

28

(34.5)

/20.0

11.6

(142.8)

/82.4

90.5

 

TECHNICAL DATA

 

Compressors

model

Nominal power of motor (HP/KW)

Displacement (m3/h)

Cylinder numbers

Oil

quantity

Connecting

pipe

Power

supply

(V/Φ/Hz)

Electrical

parameters

Startrt

running

power(A)

Weight(kg)

Exhaust pipe (mm) Suction pipe (mm) Max working current(A) Max power consumption(KW) 

BFBV8

41.3(Y)

8/5.5

41.3

4

2.6

28

35

 

 

 

 

 

380~420V

YY /3/50HZ

440~480V YY /3/60HZ

 

 

 

 

 

 

 

 

17

9.4

49/81

134

BFBV12

41.3H(Y)

12/8.8

41.3

4

2.6

28

35

24

13.8

69/113

141

BFBV10

48.5(Y)

10/7.4

48.5

4

2.6

28

35

21

11.7

59/99

139

BFBV15

48.5H(Y)

15/11

48.5

4

2.6

28

42

31

16.3

81/132

142

BFBV12

56(Y)

12/9.1

56

4

2.6

28

35

24

14.1

69/113

141

BFBV20

56H(Y)

20/15

56

4

2.6

28

42

37

19.5

97/158

150

BFBV15

73.7(Y)

15/11

73.7

4

4.5

28

54

31

18.1

81/132

184

BFBV25

73.7H(Y)

25/18

73.7

4

4.5

28

54

45

24.9

116/193

203

BFBV20

84.5(Y)

20/15

84.5

4

4.5

28

54

37

21.5

97/158

192

BFBV30

84.5H(Y)

30/22

84.5

4

4.5

28

54

53

30.1

135/220

206

BFBW25

110.5(Y)

25/18

110.5

6

4.75

35

54

45

27.2

116/193

224

BFBW35

110.5H(Y)

35/27

110.5

6

4.75

35

54

61

37.4

147/262

235

BFBW30 126.8(Y)

30/22

126.8

6

4.75

35

54

53

31.9

125/220

217

BFBW40

126.8H(Y)

40/30

126.8

6

4.75

35

54

78

45.1

180/323

235

BFBW40 151.6(Y)

40/30

151.6

6

4.75

42

54

78

38.6

180/323

240

BFBW50

151.6H(Y)

50/37

151.6

6

4.75

42

54

92

53.2

226/404

242

 

Note:1、Nominal power is different with motor power,when you chose the cable relay and fuse,you mustfind out right for maximum working current and maximumpower consumption;

2、Allow the pressure tolerance: ±10%;

3、BFBV8 41.3 ~BFBW50 151.6H line start motor,Y/YY part-winding start motor 50%/50%

 

OVERALL DRAWING

Compressors model

A

B

H

L

W

mm

mm

mm

mm

mm

BFBZ3 12(Y)

310

200

305

518

261

BFBZ4 15(Y)

355

230

380

585

282

BFBZ415H(Y)

355

230

380

585

282

BFBZ5 18(Y) BFBZ5 18H(Y)

355

230

380

585

282

BFBZ8 27H(Y)

380

280

466

624

320

BFBZ10 36(Y) BFBZ10 36H(Y)

380

280

466

624

320

BFBZ15 54(Y) BFBZ15 54H(Y)

480

315

448

748

356

 

1. uction valve 

2. xhaust valve

3.Low-pressure connection ( Φ6 )

4.High-pressure connection ( Φ6 )

5.Plug oil charge ( R1/4")

6.Drain oil plug ( R1/4")

 

OVERALL DRAWING

BFBV3 18.1(Y)~BFBV9 32.5H(Y)

 

 

Compressors model

A

B

C

D

D1

E

F

H

J

mm

mm

mm

mm

mm

mm

mm

mm

mm

BFBV3 18.1(Y), BFBV5 18.1H(Y)

432

304

350

293

75

198

221

314

361

BFBV4 22.7(Y), BFBV 6 22.7H(Y)

432

304

353

293

75

198

221

317

361

BFBV5 26.8(Y)

432

304

353

293

75

198

221

317

361

BFBV7 26.8H(Y), BFBV632.5(Y), BFBV932.5H(Y)

458

304

353

293

101

198

247

317

387

 

BFBV8 41.3(Y)〜BFBV20 56H(Y)

 

 

Compressors model

A

B

C

D

D1

E

F

G

H

J

L

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

BFBV8 41.3(Y),BFBV12 41.3H(Y)

649

306

385

367

187

256

44

63

161

558

340

BFBV 10 48.5 (Y)

649

306

385

367

187

256

44

63

161

558

340

BFBV15 48.5H(Y)

670

306

385

367

210

256

44

111

172

581

340

BFBV12 56(Y)

649

306

385

367

187

256

44

63

161

558

340

BFBV 20 56H(Y)

670

306

385

367

210

256

44

111

172

581

340

 

1.High pressure protect 2. Exhaust temperature protect and CIL sensing unit. 3.LP low pressure protect 4. CIC nozzle 5. Fill oil nozzle 6. Flow out oil nozzle (with magnetic-core) 7. Oil filter 8. Return oil (connection with oil separator) 9.Oil balance connection (plurality running) 10.Air balance connection (plurality running) 11.Heater of crankcase 12. Oil low pressure 13. Oil high pressure

 

OVERALL DRAWING

BFBV15 73.7(Y)~BFBV30 84.5H(Y)

 

 

Position of Connection tube SL(054)suction valve DL(028)exhaust valve

1 .Return oil (connected with oil separator) 2.Fill oil nozzle.  3. Exhaust temperature protect or CIC sensing 4. LP (low pressure protect)  5. LP(CIC nozzle) 6.Oil high pressure  7. HP(high pressure protect) 8.Nozzle for flow out oil(with magnetic-core)  9. Heater of crank shaft case  10. Balance of connection(plurality running)  11. Air balance connection(plurality running) 12.Low pressure of oil pressure

Compressors model

A

B

C

D

E

D1

mm

mm mm mm mm mm

BFBV15 73.7(Y)

707

396

442

381

305

169

BFBV20 84.5(Y)

707

396

442

381

305

169

BFBV25 73.7H(Y)

740

396

442

381

305

199

BFBV30 84.5H(Y)

740

396

442

381

305

199

 

BFBW25 101.5(Y)~BFBW40 126.8H(Y)

 

 

Position of Connection tube

SL(Φ54)suction valve DL(Φ35)exhaust valve

1.High pressure protect  2. Exhaust temperature protect and CIL sensing unit.  3.LP low pressure protect  4.CIC nozzle  5. Fill oil nozzle  6. Flow out oil nozzle (with magnetic-core)  7. Oil filter  8. Return oil (connection with oil separator)  9.Oil balance connection (plurality running) 10. Air balance connection (plurality running)  11.Heater of crankcase  12. Oil low pressure 13.Oil high pressure

 

Compressors model

A

B

C

D

D1

E

F

H

L

mm

mm mm mm mm mm mm mm mm

BFBW25 101.5H(Y)

760

452

445

381

211

305

87

379

271

BFBW35 101.5H(Y)

795

452

445

381

241

305

87

379

271

BFBW30 126.8(Y)

760

452

445

381

211

305

87

379

271

BFBW40 126.8H(Y)

795

452

445

381

241

305

87

379

271

 

OVERALL DRAWING

BFBW40 151.6(Y)~BFBW50 151.6H(Y)

 

 

Positions of connection tube: SL(Φ54) suction valve DL(Φ42) exhaust valve 1 .High pressure protect (HP) 2. Exhaust temperature protect and CIL sensing unit. 3. Low pressure (LP) 4. CIC nozzle (LP) 5. Fill oil nozzle 6. Flow out oil nozzle 7. Oil filter (with magnetic-core) 8. Return oil (connection with oil separator) 9a.Air balance connection (plurality running) 9b.Oil balance connection (plurality running) 10. Heater of crankcase 11. Oil high pressure 12. Oil low pressure

 

Compressors model

A

B

C

D

D1

E

F

H

J

L

mm

mm mm mm mm mm mm mm mm mm

BFBW40 151.6(Y)

795

452

445

381

241

305

87

379

730

381

BFBW50 151.6H(Y)

795

452

445

381

241

305

87

379

730

381

 

MODEL CONFIGURCTION INSTRUCTION

 

 

OVERALL DRAWING

BFBWS20 73.6(Y)~BFBWS30 101.1(Y)

 

 

Compressors model

A

B

C

D

D1

E

G

H

J

L

mm

mm mm mm mm mm mm mm mm mm

BFBWS20 73.6(Y)

790

545

510

381

211

305

112

443

714

324

BFBWS25 84.5(Y)

790

545

510

381

211

305

112

443

714

324

BFBWS 30 101.1(Y)

790

545

510

381

211

305

112

443

714

324

 

Positions of connection tube:

SL( Φ 54) suction valve DL( Φ 35) exhaust valve

1 .(HP)High pressure protect 2. Heater of crankcase shaft case 3. (LP)Low pressure 4. CIC nozzle 5. Fill oil nozzle 6.with magnetic-core 7.Nozzle for flow out oil 8. Return oil (connection with oil) 9.Intermediate pressure Interface 10.Expansion valve air intake inlets 11.Oil high pressure 12. Oil low pressure 3. Liquid cooling refrigerant outlets 14.Liquid cooling refrigerant inlets

 

TWO STAGES COMPRESSOR REFRIGERATION CAPACITY

R22 Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(kw) Power Consumption Pe(kw)
Evaporating temperature(℃)
-20 -25 -30 -35 -40 -45 -50

BFBWS20

73.6

30

Qo

35150

29400

24260

19770

15800

12280

9090

Pe

15.38

14.14

12.89

11.62

10.36

9.11

7.87

35

Qo

34800

29110

24060

19560

15590

12040

8790

Pe

16.45

15.09

13.72

12.36

10.99

9.64

8.31

40

Qo

34400

28810

23810

19360

15400

11820

8500

Pe

17.52

16.04

14.57

13.08

11.61

10.14

8.67

45

Qo

34060

28510

23560

19180

15220

11600

 

Pe

18.59

16.98

15.39

13.81

12.19

10.58

 

50

Qo

33710

28220

23360

19020

15070

 

 

Pe

19.64

17.91

16.21

14.49

12.74

 

 

55

Qo

33360

28020

23170

18880

 

 

 

Pe

20.69

18.83

17.01

15.15

 

 

 

BFBWS25

84.5

30

Qo

40390

33710

27870

22670

18140

14090

10430

Pe

17.66

16.22

14.79

13.34

11.89

10.46

9.03

35

Qo

39950

33410

27620

22470

17910

13820

10100

Pe

18.86

17.32

15.76

14.19

12.62

11.06

9.52

40

Qo

39500

33070

27320

22230

17680

13560

9760

Pe

20.11

18.42

16.73

15.02

13.33

11.64

9.95

45

Qo

39110

32720

27080

22020

17470

13330

 

Pe

21.33

19.50

17.67

15.84

14.00

12.14

 

50

Qo

38710

32420

26830

21830

17300

 

 

Pe

22.55

20.57

18.60

16.64

14.63

 

 

55

30

Qo

Pe

Qo

38310

23.75

48310

32130

21.62

40340

26630

19.52

33360

21680

17.39

27130

21680

16860

12480

BFBWS30

101.1

Pe

21.12

19.42

17.69

15.56

14.23

12.51

10.81

35

Qo

47770

39950

33020

26880

21430

16540

12080

Pe

22.60

20.72

18.85

16.97

15.10

13.24

11.39

40

Qo

47270

39550

32670

26580

21140

16230

11670

Pe

24.06

22.04

20.01

17.98

15.95

13.92

11.88

45

Qo

46780

39150

32370

26330

20890

15940

 

Pe

25.53

23.33

21.14

18.95

16.76

14.53

 

50

Qo

46280

38810

32130

26140

20690

 

 

Pe

26.98

24.61

22.26

19.91

17.50

 

 

55

Qo

45840

38460

31880

25940

 

 

 

Pe

28.41

25.86

23.35

20.81

 

 

 

 

Base on suction temperature 20℃,fixed with inter cooler, rev. 1450 .

Test Data

 

TWO STAGES COMPRESSOR REFRIGERATION CAPACITY

R404A Watt(50Hz 380v)

 

Compressors

model

Condensing

temperature(℃)

Capacity Qo(kw)   Power Consumption Pe(kw)
Evaporating temperature(℃)
-25 -30 -35 -40 -45 -50 -55 -60 -65 -70

BFBWS20

73.6Y

 

30

Qo

31580

27180

23070

19250

15750

12630

9920

7610

5710

4190

Pe

16.35

14.94

13.57

12.24

10.95

9.71

8.53

7.41

6.37

5.37

35

Qo

30990

26680

22620

18840

15400

12360

9100

7480

5610

4100

Pe

17.38

15.87

14.41

12.97

11.61

10.28

9.02

7.82

6.69

5.63

40

Qo

30290

26090

22130

18420

15080

12120

9540

7350

5480

 

Pe

18.44

16.82

15.24

13.72

12.27

10.87

9.52

8.25

7.03

 

45

Qo

29600

25490

21630

18020

14770

11890

9380

7190

 

 

Pe

19.51

17.76

16.09

14.48

12.93

11.44

10.02

8.66

 

 

50

Qo

29060

24950

21140

17630

14480

11680

9190

 

 

 

Pe

20.53

18.69

16.92

15.22

13.58

12.01

10.51

 

 

 

55

Qo

 

24450

20690

17280

14220

11450

 

 

 

 

Pe

 

19.59

17.74

15.95

14.22

12.55

 

 

 

 

BFBWS25

84.5Y

30

Qo

35840

30990

26330

22030

18040

14470

11370

8740

6560

4820

Pe

18.75

17.18

15.63

14.09

12.59

11.13

9.75

8.44

7.25

6.17

35

Qo

35240

30390

25840

21530

17630

14160

11140

8570

6440

4710

Pe

19.92

18.23

16.56

14.93

13.34

11.81

10.36

8.97

7.68

6.48

40

Qo

34550

29800

25250

21090

17250

13860

10930

18420

6290

 

Pe

21.16

19.21

17.51

15.77

14.09

12.49

10.95

9.47

8.09

 

45

Qo

33760

29110

24700

20590

16890

13600

10730

8230

 

 

Pe

22.41

20.40

18.46

16.62

14.84

13.13

11.50

9.95

 

 

50

Qo

33120

28460

24110

20150

16550

13360

10510

 

 

 

Pe

23.59

21.47

19.25

17.47

15.59

13.78

12.04

 

 

 

55

Qo

32570

27870

23560

19720

16250

13100

 

 

 

 

Pe

24.66

22.49

20.38

18.33

16.34

14.4

 

 

 

 

BFBWS30

101.1Y

30

Qo

42970

37030

31430

26240

21480

17030

13550

10430

7840

5740

Pe

22.41

20.55

18.69

16.86

15.07

13.35

11.71

10.15

8.70

7.36

35

Qo

42080

36230

30740

25640

20990

16860

13290

10240

7700

5620

Pe

23.73

21.75

18.99

17.85

15.96

14.14

12.39

10.73

9.18

7.76

40

Qo

41090

35340

30000

25050

20490

16510

13040

10050

7510

 

Pe

25.07

22.98

20.90

18.87

16.87

14.93

13.07

11.31

9.67

 

45

Qo

40050

34450

29250

24450

20100

16200

12800

9820

 

 

Pe

26.46

24.45

22.05

19.88

17.77

15.75

13.76

11.90

 

 

50

Qo

39110

33660

28560

23860

19670

15900

12520

 

 

 

Pe

27.93

25.56

23.21

20.90

18.66

16.48

14.41

 

 

 

55

Qo

38410

32920

27920

23360

19300

15580

 

 

 

 

Pe

29.49

26.92

24.39

21.92

19.53

17.23

 

 

 

 

 

Base on suction temperature 20℃, fixed with inter cooler, rev. 1450 .

Test Data

 

TECHNICAL DATA

 

Compressors

model

Nominal power of motor (HP/KW)

Displacement

Cylinder numbers

Oil

quantity

Connecting

pipe

Power

supply

(V/Φ/Hz)

Electrical

parameters

Startrt

running

power(A)

Weight(kg)

Low pressure

(m³ /h)

High pressure

(m³ /h)

Exhaust pipe (mm) Suction pipe (mm) Max working current(A)  Max power consumption(KW) 

BFBWS20 73. 6 (Y)

20/15

73.6

36.9

6

4.75

35

42

 

380~420VYY /3/50Hz 440~480VYY /3/60Hz

 

37

21.5

97/158

222

BFBWS25 84. 5 (Y)

25/18.5

84.5

42.3

6

4.75

35

42

45

24.9

116/193

234

BFBWS30 101. 1 (Y)

30/22

101.1

50.5

6

4.75

35

42

53

30.1

135/220

235

 

Appliance Scope

 

Zhejiang Beifeng Refrigeration Equipment Co., Ltd is a famous China Semi-Hermetic Compressor(3HP-20HP) Factory and Semi-Hermetic Compressor(3HP-20HP) Company,and the products are exported to the Europe,South East Asia,Middle East,North America,Africa etc.

Get In Touch

If you have any questions or need help, please contact us directly, we will provide you with online help and services in time.

Since 1986

Professional refrigeration equipment manufacturer

Zhejiang Beifeng Refrigeration Equipment Co., Ltd. has 35 years history of manufacturing refrigeration equipment. Currently, it has two processing bases located in Shengzhou, Zhejiang, with a production building of 60,000 square meters. It has set up three sales companies in Shanghai, Beijing, and Guangzhou, with strong technical force, advanced equipment, complete varieties and stable quality. The company has a high-quality inspection center to detect the performance index of refrigeration products and imported vacuum-type helium leak detectors for condensers and evaporators. It has a great influence in the national refrigeration industry and occupies a large market, with distributors in all major cities; It enjoys a high reputation not only in the domestic market, but also in the overseas market, and the products are exported to Europe, Southeast Asia, the Middle East, North America, Africa, etc.

Zhejiang Beifeng Refrigeration Equipment Co., Ltd.

Follow Beifeng to get the latest enterprise and refrigeration equipment products news

What’s New