In the refrigeration process, the fair design of the condenser
In the refrigeration process, the fair design of the condenser is an important part of improving the energy efficiency r...
Excellent functions:
• Equipped with oil separator, high and lower pressure controller, solenoid valve, filter drier, high and lower pressure gauge, big volume receiver and high efficient condensing units, it is good match unit.
Special design for the construction:
• Construction compact, equipped with protect cover,stability, service life long and good looking.
• Excellent design for the driving parts to rduced the vibration result.
• The reasonable suction device in order to compressor cylinder has completed cooling.
• According to different applications to equipment with high efficient Wpattern Rifle bored copper, it can be reduced overall dimension and add transfer-heating result.
• BFBV20 over 56H(Y) compressor unit adopted split wire motor, it can use small current to start running.
Reliability protectors:
• The motor uses electronic module protector or advanced heat protector to control the temperature.
• BFBV20 over 84.5H(Y)compress unit or adopted oil different pressure controller to ensure well lubrication system and equipped with auto-proctor of high pressure release valve.
• Crankcase heater fitted to prevent liquid migration.
UNIT MODEL INSTRUCTION
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | ||||
BFB-FJZ- 3HP |
27 |
Qo |
|
|
|
|
6880 |
5540 |
4450 |
4080 |
2680 |
|
Pe |
|
|
|
|
2.98 |
2.66 |
2.37 |
1.95 |
1.58 |
|||
32 |
Qo |
|
|
|
|
6380 |
5073 |
4040 |
3070 |
2460 |
||
Pe |
|
|
|
|
3.04 |
2.64 |
2.31 |
1.93 |
1.64 |
|||
43 |
Qo |
|
|
|
|
|
4600 |
3700 |
2740 |
2180 |
||
Pe |
|
|
|
|
|
3.21 |
2.53 |
2.12 |
1.75 |
|||
BFB-FJZ- 4HP |
27 |
Qo |
|
|
|
|
8280 |
6690 |
5420 |
4120 |
3220 |
|
Pe |
|
|
|
|
3.49 |
2.90 |
2.62 |
2.05 |
1.63 |
|||
32 |
Qo |
|
|
|
|
8000 |
6400 |
5130 |
3910 |
3120 |
||
Pe |
|
|
|
|
3.68 |
3.04 |
2.75 |
2.15 |
1.71 |
|||
43 |
Qo |
|
|
|
|
|
5540 |
4430 |
3260 |
2780 |
||
Pe |
|
|
|
|
|
3.23 |
2.86 |
2.31 |
2.03 |
|||
BFB-FJZ- 4HPH |
27 |
Qo |
13980 |
12910 |
11925 |
9950 |
8560 |
6830 |
5472 |
4165 |
3390 |
|
Pe |
4.09 |
3.72 |
3.47 |
3.24 |
3.23 |
2.79 |
2.54 |
2.01 |
1.61 |
|||
32 |
Qo |
13350 |
12330 |
11395 |
95250 |
8188 |
6450 |
5187 |
3950 |
3190 |
||
Pe |
4.24 |
3.85 |
3.62 |
3.40 |
3.26 |
2.93 |
2.64 |
2.03 |
1.63 |
|||
43 |
Qo |
|
|
12910 |
8900 |
7280 |
5790 |
4570 |
3360 |
2780 |
||
Pe |
|
|
4.30 |
3.79 |
3.54 |
3.11 |
2.80 |
2.24 |
1.99 |
|||
BFB-FJZ- 5HP |
27 |
Qo |
|
|
|
|
10580 |
8830 |
7240 |
6360 |
4540 |
|
Pe |
|
|
|
|
4.46 |
3.84 |
3.49 |
2.88 |
2.25 |
|||
32 |
Qo |
|
|
|
|
10220 |
8450 |
6860 |
5570 |
4270 |
||
Pe |
|
|
|
|
4.70 |
4.02 |
3.67 |
3.02 |
2.37 |
|||
43 |
Qo |
|
|
|
|
|
7530 |
6110 |
4780 |
3810 |
||
Pe |
|
|
|
|
|
4.39 |
3.94 |
3.38 |
2.78 |
|||
BFB-FJZ- 5HPH |
27 |
Qo |
18410 |
17010 |
15710 |
13600 |
11930 |
9020 |
7320 |
6430 |
4630 |
|
Pe |
5.17 |
5.02 |
4.73 |
4.43 |
4.09 |
3.69 |
3.39 |
2.82 |
2.33 |
|||
32 |
Qo |
17570 |
16240 |
15010 |
13010 |
10460 |
8640 |
6930 |
5630 |
4360 |
||
Pe |
5.35 |
5.19 |
4.95 |
4.64 |
4.33 |
3.87 |
3.53 |
2.85 |
2.25 |
|||
43 |
Qo |
|
|
14600 |
12350 |
9550 |
7870 |
6310 |
4930 |
3810 |
||
Pe |
|
24930 |
5.67 |
5.19 |
4.65 |
4.22 |
3.86 |
3.28 |
2.72 |
|||
BFB-FJZ- 8HPH |
27 |
Qo |
|
6.91 |
23020 |
19260 |
15780 |
12670 |
10080 |
8090 |
6350 |
|
Pe |
|
|
6.63 |
5.80 |
5.30 |
5.00 |
4.67 |
3.84 |
3.59 |
|||
32 |
Qo |
|
|
22000 |
18420 |
15100 |
12130 |
8560 |
7670 |
5980 |
||
Pe |
|
|
6.93 |
6.07 |
5.56 |
5.25 |
4.87 |
3.88 |
3.62 |
|||
43 |
Qo |
|
|
19670 |
16400 |
13480 |
11040 |
8710 |
6610 |
5220 |
||
Pe |
|
|
7.38 |
6.84 |
6.39 |
5.93 |
5.33 |
4.66 |
4.02 |
|||
BFB-FJZ- 10HP |
27 |
Qo |
|
|
|
|
21360 |
17870 |
14580 |
11740 |
9160 |
|
Pe |
|
|
|
|
8.69 |
7.70 |
6.85 |
5.76 |
4.94 |
|||
32 |
Qo |
|
|
|
|
20650 |
17090 |
13820 |
11130 |
8610 |
||
Pe |
|
|
|
|
9.16 |
8.07 |
7.19 |
6.05 |
5.19 |
|||
43 |
Qo |
|
|
|
|
|
15380 |
12550 |
10050 |
7680 |
||
Pe |
|
|
|
|
|
8.72 |
7.87 |
7.02 |
5.60 |
|||
BFB-FJZ- 10HPH |
27 |
Qo |
36020 |
33270 |
30730 |
26600 |
22070 |
18250 |
14740 |
11860 |
9340 |
|
Pe |
9.92 |
9.33 |
9.02 |
8.54 |
8.06 |
7.40 |
6.64 |
5.64 |
4.89 |
|||
32 |
Qo |
34380 |
31770 |
29360 |
25440 |
21120 |
17480 |
13970 |
11250 |
8790 |
||
Pe |
10.26 |
9.66 |
9.43 |
8.94 |
8.45 |
7.77 |
6.92 |
5.70 |
4.94 |
|||
43 |
Qo |
|
|
28260 |
23550 |
19360 |
16060 |
12950 |
10370 |
7680 |
||
Pe |
|
|
10.67 |
9.86 |
9.21 |
8.38 |
7.72 |
6.81 |
4.49 |
|||
BFB-FJZ- 15HP |
27 |
Qo |
|
|
|
|
31400 |
26000 |
21430 |
17350 |
13430 |
|
Pe |
|
|
|
|
12.98 |
10.92 |
9.29 |
8.47 |
7.15 |
|||
32 |
Qo |
|
|
|
|
30350 |
24870 |
20300 |
16460 |
12620 |
||
Pe |
|
|
|
|
13.69 |
11.45 |
9.75 |
8.89 |
7.52 |
|||
43 |
Qo |
|
|
|
|
|
22390 |
18370 |
14800 |
11260 |
||
Pe |
|
|
|
|
|
13.03 |
11.24 |
9.50 |
8.20 |
|||
BFB-FJZ- 15HPH |
27 |
Qo |
53090 |
49040 |
45290 |
39160 |
31800 |
25410 |
21660 |
17080 |
|
|
Pe |
14.73 |
14.13 |
13.42 |
12.60 |
11.88 |
10.35 |
8.92 |
8.22 |
|
|||
32 |
Qo |
50680 |
46840 |
43080 |
37450 |
30430 |
24330 |
20530 |
16210 |
|
||
Pe |
15.24 |
14.63 |
14.03 |
13.20 |
12.47 |
10.87 |
9.28 |
8.65 |
|
|||
43 |
Qo |
|
|
42530 |
35130 |
28460 |
22950 |
17620 |
14700 |
|
||
Pe |
|
|
15.9 |
14.31 |
13.49 |
12.32 |
11.04 |
9.36 |
|
Note: The refrigerating effect is got on the basis of the degree of superheating of inlet air 25℃ and liquid with over-cold suction temperature of medium-high temperature compressor.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-FJZ- V3HP |
27 |
Qo |
|
|
|
|
10460 |
8720 |
6840 |
5850 |
4750 |
3730 |
Pe |
|
|
|
|
4.11 |
3.66 |
3.27 |
3.01 |
2.63 |
2.29 |
||
32 |
Qo |
|
|
|
|
9790 |
8040 |
6350 |
5440 |
4350 |
3430 |
|
Pe |
|
|
|
|
4.31 |
3.82 |
3.38 |
3.13 |
2.72 |
2.38 |
||
43 |
Qo |
|
|
|
|
|
|
5420 |
4650 |
3570 |
2690 |
|
Pe |
|
|
|
|
|
|
3.67 |
3.49 |
3.01 |
2.59 |
||
BFB-FJZ- V5HPH |
27 |
Qo |
18610 |
17280 |
15960 |
13270 |
11020 |
9120 |
7190 |
6050 |
4810 |
5570 |
Pe |
4.68 |
4.46 |
4.36 |
4.05 |
3.81 |
3.43 |
3.09 |
2.91 |
2.72 |
2.53 |
||
32 |
Qo |
16640 |
15370 |
14100 |
11890 |
10330 |
8520 |
6680 |
5280 |
4520 |
3580 |
|
Pe |
4.97 |
4.86 |
4.77 |
4.57 |
3.99 |
3.62 |
3.24 |
3.03 |
2.82 |
2.61 |
||
43 |
Qo |
|
|
12560 |
10250 |
8790 |
7170 |
5610 |
4340 |
3070 |
|
|
Pe |
|
|
5.41 |
4.96 |
4.46 |
3.94 |
3.53 |
3.32 |
3.11 |
|
||
BFB-FJZ- V4HP |
27 |
Qo |
|
|
|
|
12150 |
10210 |
8160 |
7130 |
5760 |
4550 |
Pe |
|
|
|
|
5.15 |
4.63 |
4.13 |
3.77 |
3.37 |
2.96 |
||
32 |
Qo |
|
|
|
|
11450 |
9480 |
7540 |
6550 |
5270 |
4190 |
|
Pe |
|
|
|
|
5.37 |
4.75 |
4.27 |
3.92 |
3.47 |
3.06 |
||
43 |
Qo |
|
|
|
|
|
|
6410 |
5570 |
4290 |
3260 |
|
Pe |
|
|
|
|
|
|
4.76 |
4.32 |
3.78 |
3.16 |
||
BFB-FJZ- V6HPH |
27 |
Qo |
21640 |
20170 |
18710 |
15670 |
13110 |
10930 |
8680 |
7380 |
6080 |
4760 |
Pe |
6.45 |
6.16 |
5.88 |
5.31 |
4.81 |
4.34 |
3.91 |
3.62 |
3.33 |
3.02 |
||
32 |
Qo |
19310 |
17920 |
16490 |
14080 |
12250 |
9850 |
7870 |
6430 |
4980 |
3520 |
|
Pe |
6.87 |
6.64 |
6.23 |
5.69 |
5.06 |
4.52 |
4.03 |
3.84 |
3.62 |
3.41 |
||
43 |
Qo |
|
|
14570 |
11980 |
10350 |
8510 |
6610 |
5550 |
4490 |
|
|
Pe |
|
|
7.04 |
6.29 |
5061 |
4.96 |
4.44 |
4.17 |
3.89 |
|
||
BFB-FJZ- V5HP |
27 |
Qo |
|
|
|
|
15290 |
12790 |
10310 |
8610 |
7020 |
5540 |
Pe |
|
|
|
|
6.06 |
5.45 |
4.82 |
4.38 |
3.92 |
3.48 |
||
32 |
Qo |
|
|
|
|
14460 |
12060 |
9560 |
8010 |
6430 |
4940 |
|
Pe |
|
|
|
|
6.36 |
5.65 |
5.06 |
4.57 |
4.06 |
3.57 |
||
43 |
Qo |
|
|
|
|
|
|
8090 |
6750 |
5220 |
3960 |
|
Pe |
|
|
|
|
|
|
5.38 |
4.87 |
4.38 |
3.91 |
||
BFB-FJZ- V7HPH |
27 |
Qo |
26650 |
24840 |
23010 |
19240 |
16060 |
12940 |
10610 |
8910 |
6840 |
4760 |
Pe |
7.25 |
6.98 |
6.71 |
6.17 |
5.72 |
5.16 |
4.67 |
4.23 |
3.76 |
3.27 |
||
32 |
Qo |
23810 |
22740 |
21630 |
17870 |
15040 |
12210 |
9860 |
8130 |
6080 |
4130 |
|
Pe |
7.81 |
7.47 |
7.18 |
6.65 |
6.01 |
5.44 |
4.91 |
4.41 |
3.92 |
3.51 |
||
43 |
Qo |
|
|
18610 |
15320 |
12810 |
10290 |
8270 |
6780 |
5190 |
|
|
Pe |
|
|
8.25 |
7.48 |
6.75 |
6.05 |
5.38 |
4.66 |
4.05 |
|
||
BFB-FJZ- V6HP |
27 |
Qo |
|
|
|
|
17630 |
14840 |
12030 |
9780 |
7770 |
6010 |
Pe |
|
|
|
|
7.52 |
6.71 |
6.01 |
5.37 |
4.74 |
4.14 |
||
32 |
Qo |
|
|
|
|
16650 |
13820 |
11160 |
9010 |
7110 |
5410 |
|
Pe |
|
|
|
|
7.95 |
7.05 |
6.27 |
5.55 |
4.89 |
4.21 |
||
43 |
Qo |
|
|
|
|
|
|
9480 |
7290 |
5570 |
4330 |
|
Pe |
|
|
|
|
|
|
6.74 |
6.08 |
5.28 |
4.38 |
||
BFB-FJZ- V9HPH |
27 |
Qo |
31580 |
29460 |
27330 |
22910 |
19170 |
16010 |
12870 |
10400 |
7830 |
6310 |
Pe |
9.31 |
8.87 |
8.42 |
7.67 |
7.01 |
6.36 |
5.76 |
5.19 |
4.63 |
4.05 |
||
32 |
Qo |
29740 |
27710 |
25720 |
21310 |
17980 |
14950 |
11980 |
9420 |
7260 |
5350 |
|
Pe |
10.04 |
9.54 |
9.03 |
8.15 |
7.41 |
6.71 |
6.08 |
5.38 |
4.68 |
4.05 |
||
43 |
Qo |
|
|
|
|
15320 |
12620 |
9970 |
7840 |
5710 |
|
|
Pe |
|
|
|
|
8.47 |
7.58 |
6.67 |
5.82 |
4.96 |
|
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-FJZ- V8HP |
27 |
Qo |
|
|
|
|
23570 |
19850 |
16280 |
13390 |
10610 |
8410 |
Pe |
|
|
|
|
9.43 |
8.38 |
7.43 |
6.56 |
5.82 |
5.04 |
||
32 |
Qo |
|
|
|
|
22090 |
18570 |
15210 |
12460 |
10060 |
7710 |
|
Pe |
|
|
|
|
9.89 |
8.82 |
7.71 |
6.84 |
6.04 |
5.23 |
||
43 |
Qo |
|
|
|
|
|
|
12930 |
10640 |
8210 |
6240 |
|
Pe |
|
|
|
|
|
|
8.35 |
7.28 |
6.31 |
5.41 |
||
BFB-FJZ- V12HPH |
27 |
Qo |
43610 |
38480 |
33350 |
28320 |
24260 |
20280 |
16510 |
13460 |
11410 |
8470 |
Pe |
12.43 |
11.88 |
10.86 |
9.83 |
8.96 |
7.97 |
7.21 |
6.39 |
5.64 |
4.93 |
||
32 |
Qo |
39860 |
35650 |
31340 |
27130 |
22730 |
18970 |
15420 |
12560 |
10620 |
7680 |
|
Pe |
12.68 |
12.07 |
11.48 |
10.38 |
9.42 |
8.43 |
7.44 |
6.54 |
5.66 |
5.12 |
||
43 |
Qo |
|
|
26640 |
23610 |
20070 |
16490 |
13310 |
10740 |
8610 |
|
|
Pe |
|
|
13.06 |
11.64 |
10.46 |
9.25 |
8.11 |
7.09 |
6.59 |
|
||
BFB-FJZ- V10HP |
27 |
Qo |
|
|
|
|
27330 |
22980 |
18830 |
15490 |
12630 |
9730 |
Pe |
|
|
|
|
10.98 |
9.75 |
8.71 |
7.59 |
6.67 |
5.76 |
||
32 |
Qo |
|
|
|
|
25670 |
21530 |
17590 |
14420 |
11650 |
8940 |
|
Pe |
|
|
|
|
11.51 |
10.15 |
8.92 |
7.81 |
6.82 |
5.86 |
||
43 |
Qo |
|
|
|
|
|
|
14950 |
12650 |
9530 |
7240 |
|
Pe |
|
|
|
|
|
|
9.36 |
8.29 |
7.21 |
6.08 |
||
BFB-FJZ- V15HPH |
27 |
Qo |
51650 |
48230 |
44610 |
36940 |
30860 |
25170 |
20210 |
16270 |
12950 |
10010 |
Pe |
12.07 |
11.72 |
11.17 |
10.32 |
8.58 |
8.69 |
7.87 |
7.04 |
6.25 |
5.35 |
||
32 |
Qo |
48680 |
45350 |
42010 |
33680 |
28720 |
23910 |
18950 |
15390 |
12060 |
9160 |
|
Pe |
12.96 |
12.43 |
11.91 |
10.94 |
10.01 |
9.11 |
8.21 |
7.31 |
6.46 |
5.65 |
||
43 |
Qo |
|
|
36520 |
31110 |
25620 |
20790 |
16940 |
13680 |
10480 |
|
|
Pe |
|
|
13.46 |
12.28 |
11.15 |
10.13 |
8.95 |
7.96 |
6.89 |
|
||
BFB-FJZ- V12HP |
27 |
Qo |
|
|
|
|
33340 |
27680 |
22860 |
18770 |
14640 |
11740 |
Pe |
|
|
|
|
12.34 |
12.12 |
9.87 |
8.75 |
7.67 |
6.53 |
||
32 |
Qo |
|
|
|
|
31370 |
26550 |
21670 |
17720 |
14140 |
10850 |
|
Pe |
|
|
|
|
13.15 |
11.56 |
10.34 |
8.95 |
7.89 |
6.63 |
||
43 |
Qo |
|
|
|
|
|
|
18820 |
15090 |
11640 |
8810 |
|
Pe |
|
|
|
|
|
|
10.79 |
9.64 |
8.29 |
6.95 |
||
BFB-FJZ- V20HPH |
27 |
Qo |
57660 |
53390 |
49910 |
41890 |
35540 |
29480 |
25060 |
19070 |
15050 |
11580 |
Pe |
15.36 |
14.39 |
13.89 |
12.77 |
11.57 |
10.56 |
9.39 |
8.42 |
7.31 |
6.28 |
||
32 |
Qo |
54600 |
50620 |
46790 |
39720 |
33740 |
27980 |
23810 |
18520 |
14630 |
11260 |
|
Pe |
15.67 |
15.03 |
14.52 |
13.38 |
12.13 |
11.11 |
9.77 |
8.50 |
7.396.35 |
|
||
43 |
Qo |
|
|
44110 |
36880 |
31060 |
25010 |
20630 |
16350 |
12700 |
|
|
Pe |
|
|
15.05 |
14.47 |
13.01 |
12.13 |
10.38 |
8.94 |
6.35 |
|
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-FJZ- V15HP |
27 |
Qo |
|
|
|
|
42260 |
32940 |
29000 |
23330 |
18490 |
14360 |
Pe |
|
|
|
|
16.44 |
14.40 |
12.76 |
11.22 |
9.54 |
8.53 |
||
32 |
Qo |
|
|
|
|
40850 |
33510 |
26180 |
20270 |
17320 |
13280 |
|
Pe |
|
|
|
|
17.33 |
14.93 |
13.17 |
11.51 |
10.14 |
8.6 |
||
43 |
Qo |
|
|
|
|
|
30400 |
24960 |
19660 |
15330 |
11490 |
|
Pe |
|
|
|
|
|
16.77 |
14.45 |
12.63 |
10.88 |
9.14 |
||
BFB-FJZ- V25HPH |
27 |
Qo |
71850 |
67290 |
62150 |
52250 |
44370 |
36830 |
30480 |
24460 |
19380 |
15010 |
Pe |
19.33 |
18.32 |
17.46 |
15.85 |
14.49 |
13.85 |
11.87 |
10.66 |
9.26 |
7.86 |
||
32 |
Qo |
69440 |
64260 |
59250 |
50460 |
42890 |
35560 |
29390 |
23500 |
18500 |
|
|
Pe |
19.60 |
18.80 |
18.14 |
16.61 |
15.28 |
13.83 |
12.27 |
10.54 |
8.91 |
|
||
43 |
Qo |
|
|
56260 |
47091 |
39880 |
32930 |
27030 |
21490 |
16720 |
|
|
Pe |
|
|
20.15 |
18.33 |
16.63 |
15.02 |
13.48 |
11.74 |
10.15 |
|
||
BFB-FJZ- V20HP |
27 |
Qo |
|
|
|
|
48570 |
38460 |
33550 |
27010 |
21360 |
17100 |
Pe |
|
|
|
|
19.14 |
16.74 |
14.75 |
13.1 |
11.66 |
10.09 |
||
32 |
Qo |
|
|
|
|
47010 |
36840 |
31830 |
25600 |
20120 |
16300 |
|
Pe |
|
|
|
|
20.18 |
17.55 |
15.48 |
13.76 |
12.26 |
10.40 |
||
43 |
Qo |
|
|
|
|
|
33440 |
29040 |
22720 |
17780 |
13820 |
|
Pe |
|
|
|
|
|
19.32 |
16.93 |
15.05 |
13.10 |
11.09 |
||
BFB-FJZ- W25HP |
27 |
Qo |
|
|
|
|
61570 |
52120 |
43430 |
35530 |
28040 |
22190 |
Pe |
|
|
|
|
26.71 |
23.43 |
20.32 |
17.36 |
14.76 |
12.84 |
||
32 |
Qo |
|
|
|
|
56340 |
49260 |
40930 |
33360 |
26530 |
20440 |
|
Pe |
|
|
|
|
27.17 |
24.61 |
21.43 |
18.25 |
15.57 |
13.17 |
||
43 |
Qo |
|
|
|
|
|
45780 |
37460 |
29580 |
22470 |
16970 |
|
Pe |
|
|
|
|
|
25.35 |
22.71 |
19.97 |
17.13 |
14.25 |
||
BFB-FJZ- V30HPH |
27 |
Qo |
81830 |
76670 |
70900 |
59580 |
50660 |
40080 |
34910 |
28090 |
22450 |
17630 |
Pe |
22.80 |
21.58 |
20.57 |
18.69 |
17.14 |
15.60 |
14.01 |
12.64 |
10.96 |
9.41 |
||
32 |
Qo |
79100 |
73340 |
67850 |
57680 |
49100 |
38860 |
33890 |
27280 |
21820 |
17150 |
|
Pe |
23.28 |
22.35 |
21.51 |
19.58 |
17.98 |
16.38 |
14.59 |
12.77 |
11.07 |
9.51 |
||
43 |
Qo |
|
|
64170 |
53830 |
45640 |
35960 |
31160 |
24960 |
19660 |
|
|
Pe |
|
|
23.87 |
21.62 |
19.57 |
17.78 |
16.03 |
14.21 |
12.64 |
|
||
BFB-FJZ- W30HP |
27 |
Qo |
|
|
|
|
72860 |
60650 |
50330 |
40610 |
32140 |
24860 |
Pe |
|
|
|
|
28.40 |
24.81 |
22.00 |
19.41 |
17.31 |
15.05 |
||
32 |
Qo |
|
|
|
|
70310 |
57870 |
47490 |
38300 |
29950 |
23450 |
|
Pe |
|
|
|
|
30.46 |
26.27 |
23.36 |
20.75 |
18.16 |
15.48 |
||
43 |
Qo |
|
|
|
|
|
52770 |
43550 |
34170 |
26740 |
20130 |
|
Pe |
|
|
|
|
|
28.58 |
25.14 |
22.30 |
19.46 |
16.48 |
||
BFB-FJZ- W35HPH |
27 |
Qo |
103830 |
97250 |
89860 |
75570 |
64220 |
54310 |
45210 |
37120 |
29390 |
23590 |
Pe |
29.39 |
28.15 |
26.84 |
25.03 |
22.31 |
21.88 |
19.18 |
16.73 |
13.91 |
11.89 |
||
32 |
Qo |
94920 |
87820 |
81330 |
69220 |
58800 |
51970 |
43550 |
35410 |
28650 |
|
|
Pe |
31.64 |
30.29 |
28.98 |
26.19 |
23.91 |
22.92 |
19.91 |
16.82 |
14.61 |
|
||
43 |
Qo |
|
|
78420 |
62350 |
56110 |
49220 |
40190 |
32410 |
24870 |
|
|
Pe |
|
|
31.54 |
28.76 |
26.14 |
23.33 |
21.46 |
18.81 |
16.52 |
|
||
BFB-FJZ- W40HPH |
27 |
Qo |
122860 |
115080 |
106340 |
89420 |
75990 |
63200 |
52390 |
42430 |
33690 |
26430 |
Pe |
33.52 |
32.10 |
30.60 |
28.54 |
25.44 |
23.17 |
20.77 |
18.71 |
16.30 |
13.94 |
||
32 |
Qo |
118460 |
109660 |
101500 |
86390 |
73380 |
61050 |
50530 |
40650 |
32340 |
|
|
Pe |
35.48 |
33.96 |
32.50 |
29.38 |
26.81 |
24.47 |
21.69 |
19.12 |
17.04 |
|
||
43 |
Qo |
|
|
96380 |
80850 |
68490 |
56740 |
46720 |
37440 |
29600 |
|
|
Pe |
|
|
35.40 |
32.11 |
29.07 |
26.30 |
23.76 |
21.00 |
18.77 |
|
||
BFB-FJZ- W40HP |
27 |
Qo |
|
|
|
|
86160 |
71870 |
59840 |
48480 |
38460 |
29990 |
Pe |
|
|
|
|
34.85 |
30.47 |
27.10 |
24.06 |
20.86 |
18.06 |
||
32 |
Qo |
|
|
|
|
83380 |
68840 |
56790 |
46060 |
36220 |
28590 |
|
Pe |
|
|
|
|
36.75 |
31.94 |
28.44 |
25.26 |
21.93 |
18.61 |
||
43 |
Qo |
|
|
|
|
|
62770 |
52070 |
41070 |
32350 |
24520 |
|
Pe |
|
|
|
|
|
34.73 |
30.60 |
27.10 |
23.46 |
19.80 |
||
BFB-FJZ- W50HPH |
27 |
Qo |
144460 |
135400 |
125260 |
105490 |
89860 |
74890 |
62280 |
50420 |
40470 |
32020 |
Pe |
42.26 |
40.39 |
38.34 |
34.72 |
31.71 |
28.91 |
25.90 |
23.38 |
20.55 |
17.67 |
||
32 |
Qo |
139640 |
129510 |
119870 |
102120 |
87080 |
72620 |
60450 |
48960 |
39330 |
31160 |
|
Pe |
43.17 |
41.82 |
40.08 |
36.38 |
33.27 |
30.36 |
26.96 |
23.62 |
20.77 |
17.86 |
||
43 |
Qo |
|
|
113700 |
95580 |
81190 |
67490 |
55870 |
45060 |
35920 |
|
|
Pe |
|
|
43.67 |
39.77 |
36.10 |
32.70 |
29.50 |
25.90 |
22.80 |
|
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold..
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R134a Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-FJZ- 3HPY |
27 |
Qo |
8240 |
7406 |
6950 |
5980 |
5610 |
4580 |
3140 |
2130 |
1620 |
1090 |
Pe |
2.22 |
2.12 |
2.01 |
1.92 |
1.68 |
1.54 |
1.38 |
1.09 |
0.88 |
0.66 |
||
32 |
Qo |
7700 |
7160 |
6590 |
5730 |
4310 |
3540 |
2880 |
1910 |
1620 |
1100 |
|
Pe |
259 |
2.52 |
2.42 |
2.26 |
1.96 |
1.79 |
1.52 |
1.16 |
1.07 |
0.81 |
||
43 |
Qo |
7300 |
6360 |
5710 |
4820 |
3910 |
3120 |
2504 |
1590 |
|
|
|
Pe |
2.76 |
2.66 |
2.46 |
2.31 |
1.99 |
1.81 |
1.54 |
1.18 |
|
|
||
BFB-FJZ- 4HPY |
27 |
Qo |
9880 |
9060 |
8380 |
7030 |
6130 |
4830 |
3840 |
2670 |
1960 |
1370 |
Pe |
2.60 |
2.46 |
2.35 |
2.10 |
1.97 |
1.74 |
1.54 |
1.18 |
1.08 |
0.75 |
||
32 |
Qo |
9330 |
8660 |
8040 |
6820 |
5550 |
4450 |
3520 |
2330 |
1890 |
1330 |
|
Pe |
2.99 |
2.85 |
2.70 |
2.45 |
2.20 |
1.96 |
1.65 |
1.25 |
1.13 |
0.87 |
||
43 |
Qo |
8040 |
7540 |
6980 |
5970 |
4870 |
3830 |
3030 |
1960 |
|
|
|
Pe |
3.45 |
3.12 |
2.98 |
2.76 |
2.54 |
2.23 |
1.86 |
1.52 |
|
|
||
BFB-FJZ- 5HPY |
27 |
Qo |
13000 |
11900 |
11000 |
9600 |
7820 |
6440 |
5170 |
3800 |
3200 |
2310 |
Pe |
3.12 |
2.96 |
2.82 |
2.68 |
2.45 |
2.25 |
2.00 |
1.65 |
1.35 |
1.01 |
||
32 |
Qo |
11750 |
10840 |
9900 |
9100 |
7290 |
6050 |
4860 |
3700 |
2840 |
1900 |
|
Pe |
3.89 |
3.77 |
3.70 |
3.43 |
2.96 |
2.69 |
2.30 |
2.14 |
2.12 |
1.84 |
||
43 |
Qo |
11000 |
10300 |
9550 |
8280 |
6390 |
5200 |
4190 |
2860 |
|
|
|
Pe |
4.39 |
4.21 |
4.04 |
3.78 |
3.21 |
2.89 |
2.64 |
1.94 |
|
|
||
BFB-FJZ- 8HPHY |
27 |
Qo |
19020 |
14730 |
13360 |
12610 |
11080 |
9050 |
7110 |
5190 |
3890 |
|
Pe |
5.00 |
4.75 |
4.53 |
4.06 |
3.16 |
3.22 |
2.82 |
2.26 |
1.87 |
|
||
32 |
Qo |
17190 |
13960 |
12790 |
11870 |
10290 |
8480 |
6710 |
4590 |
3364 |
|
|
Pe |
5.25 |
5.10 |
5.00 |
4.56 |
4.19 |
3.77 |
3.21 |
2.44 |
2.10 |
|
||
43 |
Qo |
14770 |
12980 |
11960 |
10990 |
9080 |
7400 |
5770 |
3860 |
|
|
|
Pe |
6.17 |
6.00 |
5.88 |
5.40 |
4.92 |
4.43 |
3.77 |
2.87 |
|
|
||
BFB-FJZ- 10HPY |
27 |
Qo |
25460 |
23340 |
21610 |
18810 |
15800 |
13050 |
10420 |
7620 |
5740 |
|
Pe |
6.70 |
6.34 |
6.05 |
5.61 |
5.06 |
4.38 |
4.09 |
3.32 |
2.76 |
|
||
32 |
Qo |
24700 |
22300 |
21260 |
18050 |
14780 |
12350 |
9890 |
7200 |
5240 |
|
|
Pe |
7.55 |
7.33 |
7.18 |
6.55 |
5.70 |
5.45 |
4.64 |
3.76 |
3.10 |
|
||
43 |
Qo |
21260 |
19980 |
18460 |
15800 |
12970 |
10630 |
8610 |
6030 |
|
|
|
Pe |
8.49 |
8.16 |
7.82 |
7.21 |
6.66 |
5.95 |
5.1 |
3.96 |
|
|
||
BFB-FJZ- 15HPY |
27 |
Qo |
36700 |
33660 |
31000 |
27120 |
22710 |
18630 |
15030 |
11000 |
8270 |
5940 |
Pe |
9.88 |
9.36 |
8.92 |
8.26 |
7.42 |
6.77 |
5.05 |
4.89 |
4.05 |
3.27 |
||
32 |
Qo |
35050 |
32460 |
30050 |
26150 |
21160 |
17270 |
14300 |
10440 |
7550 |
5450 |
|
Pe |
11.36 |
11.02 |
10.82 |
9.77 |
8.86 |
7.75 |
6.91 |
5.70 |
4.53 |
3.62 |
||
43 |
Qo |
31100 |
28870 |
26970 |
22880 |
18560 |
14590 |
12190 |
8660 |
|
|
|
Pe |
12.68 |
12.14 |
11.65 |
10.64 |
9.41 |
8.24 |
7.43 |
5.78 |
|
|
Note: The refrigerating effect is got on the basis of the degree of superheating of inlet air 20℃and liquid with over-cold.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R134a Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-FJZ- V3HPY |
27 |
Qo |
12230 |
11280 |
10360 |
8460 |
6960 |
5620 |
4380 |
3410 |
2620 |
1890 |
Pe |
2.83 |
2.74 |
2.61 |
2.39 |
2.21 |
1.97 |
1.75 |
1.54 |
1.31 |
1.07 |
||
32 |
Qo |
11160 |
10320 |
9450 |
7970 |
6490 |
5250 |
4160 |
3210 |
2390 |
1780 |
|
Pe |
2.99 |
2.88 |
2.76 |
2.54 |
2.32 |
2.09 |
1.86 |
1.61 |
1.35 |
1.08 |
||
43 |
Qo |
9980 |
9210 |
8420 |
6880 |
5630 |
4480 |
3440 |
2610 |
1940 |
1330 |
|
Pe |
3.31 |
3.18 |
3.03 |
2.79 |
2.53 |
2.26 |
1.98 |
1.69 |
1.39 |
1.11 |
||
BFB-FJZ- V4HPY |
27 |
Qo |
14830 |
13740 |
12670 |
10680 |
8710 |
7050 |
5550 |
4470 |
3440 |
2580 |
Pe |
4.09 |
3.94 |
3.78 |
3.47 |
3.17 |
2.87 |
2.57 |
2.28 |
1.97 |
1.68 |
||
32 |
Qo |
13910 |
12870 |
11880 |
9810 |
8140 |
6570 |
5270 |
4130 |
3150 |
2330 |
|
Pe |
4.29 |
4.13 |
3.99 |
3.66 |
3.32 |
2.98 |
2.65 |
2.31 |
1.98 |
1.71 |
||
43 |
Qo |
11930 |
11010 |
10180 |
8380 |
6920 |
5550 |
4390 |
3380 |
2540 |
1830 |
|
Pe |
4.81 |
4.62 |
4.44 |
4.01 |
3.56 |
3.17 |
2.76 |
2.37 |
1.95 |
1.54 |
||
BFB-FJZ- V5HPY |
27 |
Qo |
18420 |
17060 |
15680 |
12920 |
10720 |
8670 |
6950 |
5450 |
4140 |
3050 |
Pe |
4.67 |
4.48 |
4.32 |
3.94 |
3.57 |
3.21 |
2.86 |
2.48 |
2.14 |
1.75 |
||
32 |
Qo |
17340 |
16030 |
14750 |
12130 |
10050 |
8100 |
6470 |
5040 |
3950 |
2770 |
|
Pe |
4.95 |
4.76 |
4.58 |
4.13 |
3.74 |
3.35 |
2.97 |
2.57 |
2.21 |
1.81 |
||
43 |
Qo |
15000 |
13860 |
12730 |
10340 |
8610 |
6890 |
5460 |
4200 |
3110 |
2190 |
|
Pe |
5.51 |
5.32 |
5.09 |
4.64 |
4.18 |
3.68 |
3.24 |
2.74 |
2.29 |
1.79 |
||
BFB-FJZ- V6HPY |
27 |
Qo |
21060 |
19580 |
18060 |
14980 |
12510 |
10160 |
8200 |
6480 |
5040 |
3750 |
Pe |
5.94 |
5.67 |
5.42 |
4.88 |
4.31 |
3.85 |
3.37 |
2.89 |
2.46 |
2.03 |
||
32 |
Qo |
19790 |
18380 |
16960 |
14050 |
11710 |
9050 |
7640 |
6010 |
4630 |
3410 |
|
Pe |
6.26 |
5.94 |
5.66 |
5.09 |
4.54 |
4.03 |
3.49 |
2.99 |
2.53 |
2.05 |
||
43 |
Qo |
17070 |
15850 |
14620 |
12080 |
10040 |
8100 |
6460 |
5050 |
3790 |
2710 |
|
Pe |
6.92 |
6.61 |
6.31 |
5.61 |
5.04 |
4.42 |
3.77 |
3.21 |
2.61 |
2.06 |
||
BFB-FJZ- V8HPY |
27 |
Qo |
27190 |
25260 |
23340 |
19360 |
16150 |
13120 |
10570 |
8320 |
6450 |
4770 |
Pe |
7.74 |
7.38 |
7.03 |
6.32 |
5.61 |
5.04 |
4.46 |
3.89 |
3.38 |
2.89 |
||
32 |
Qo |
25470 |
23680 |
21850 |
18110 |
15080 |
12220 |
9820 |
7680 |
5880 |
4280 |
|
Pe |
8.13 |
7.74 |
7.37 |
6.61 |
5.82 |
5.21 |
4.51 |
3.94 |
3.36 |
2.83 |
||
43 |
Qo |
21680 |
20130 |
18570 |
15350 |
12720 |
10230 |
8110 |
6240 |
4640 |
3220 |
|
Pe |
8.81 |
8.38 |
7.97 |
7.08 |
6.25 |
5.44 |
4.64 |
3.95 |
3.26 |
2.63 |
||
BFB-FJZ- V10HPY |
27 |
Qo |
31560 |
29360 |
27120 |
22480 |
18750 |
15220 |
12230 |
9610 |
7400 |
5420 |
Pe |
9.01 |
8.63 |
8.21 |
7.41 |
6.64 |
5.91 |
5.19 |
4.51 |
3.83 |
3.21 |
||
32 |
Qo |
29530 |
27460 |
25350 |
21010 |
17320 |
14160 |
11460 |
8840 |
6730 |
4840 |
|
Pe |
9.43 |
9.02 |
8.59 |
7.69 |
6.87 |
6.07 |
5.29 |
4.54 |
3.82 |
3.16 |
||
43 |
Qo |
25090 |
23280 |
21500 |
17760 |
14710 |
11830 |
9340 |
7150 |
5270 |
3580 |
|
Pe |
10.26 |
9.74 |
9.25 |
8.21 |
7.23 |
6.29 |
5.38 |
4.54 |
3.72 |
2.94 |
||
BFB-FJZ- V12HPY |
27 |
Qo |
38040 |
34670 |
32520 |
27440 |
22910 |
19190 |
14880 |
11330 |
8970 |
6630 |
Pe |
10.31 |
9.53 |
9.21 |
8.45 |
7.45 |
6.85 |
5.84 |
5.11 |
4.63 |
3.87 |
||
32 |
Qo |
35740 |
33430 |
30560 |
25760 |
21390 |
17380 |
13870 |
10750 |
8230 |
5940 |
|
Pe |
10.88 |
10.26 |
9.78 |
8.74 |
7.87 |
6.89 |
6.04 |
5.70 |
4.52 |
3.72 |
||
43 |
Qo |
30660 |
29740 |
26200 |
21890 |
18070 |
14730 |
11650 |
8930 |
6560 |
4530 |
|
Pe |
11.82 |
11.23 |
10.53 |
9.43 |
8.25 |
7.38 |
6.31 |
5.26 |
4.35 |
3.54 |
||
BFB-FJZ- V15HPY |
27 |
Qo |
49170 |
44980 |
41580 |
34810 |
29280 |
23780 |
18960 |
14750 |
11220 |
8040 |
Pe |
11.61 |
12.37 |
11.62 |
10.30 |
9.07 |
8.07 |
7.18 |
6.18 |
5.30 |
4.36 |
||
32 |
Qo |
46150 |
42640 |
39290 |
32690 |
25780 |
21410 |
16310 |
13350 |
9820 |
6870 |
|
Pe |
14.12 |
13.43 |
12.42 |
11.13 |
9.94 |
8.81 |
7.61 |
6.46 |
5.56 |
4.52 |
||
43 |
Qo |
43770 |
38330 |
34040 |
27500 |
23400 |
18850 |
14950 |
11080 |
|
|
|
Pe |
15.07 |
14.20 |
12.87 |
11.35 |
10.09 |
8.89 |
7.72 |
6.63 |
|
|
||
BFB-FJZ- V20HPY |
27 |
Qo |
60760 |
50700 |
46840 |
36900 |
33040 |
26850 |
21460 |
16720 |
12760 |
9200 |
Pe |
15.65 |
14.69 |
13.88 |
12.36 |
11.00 |
9.80 |
8.61 |
7.52 |
6.27 |
5.19 |
||
32 |
Qo |
51960 |
47990 |
44270 |
36900 |
30030 |
24500 |
19560 |
15220 |
11250 |
7940 |
|
Pe |
16.53 |
15.60 |
15.22 |
13.23 |
11.81 |
10.40 |
9.00 |
7.62 |
6.99 |
5.30 |
||
43 |
Qo |
49600 |
41200 |
38370 |
31060 |
26500 |
21400 |
17200 |
12260 |
|
|
|
Pe |
17.64 |
16.48 |
15.25 |
13.50 |
12.00 |
10.50 |
9.13 |
7.82 |
|
|
||
BFB-FJZ- W25HPY |
27 |
Qo |
71810 |
65880 |
60890 |
51560 |
42960 |
35170 |
28220 |
22110 |
16830 |
12330 |
Pe |
20.99 |
19.66 |
18.58 |
16.32 |
14.12 |
12.43 |
10.78 |
9.34 |
7.98 |
6.68 |
||
32 |
Qo |
66830 |
62350 |
57480 |
48620 |
40440 |
33020 |
26400 |
20600 |
15580 |
11310 |
|
Pe |
21.39 |
20.41 |
19.23 |
16.75 |
14.62 |
12.73 |
11.09 |
9.61 |
8.11 |
6.67 |
||
43 |
Qo |
56060 |
51980 |
50140 |
42320 |
35080 |
28490 |
22620 |
17460 |
|
|
|
Pe |
23.67 |
21.98 |
20.46 |
17.72 |
15.39 |
13.35 |
11.52 |
9.82 |
|
|
||
BFB-FJZ- W30HPY |
27 |
Qo |
82900 |
76050 |
70290 |
60310 |
49640 |
40320 |
32190 |
25010 |
19140 |
13790 |
Pe |
23.30 |
21.82 |
20.62 |
18.41 |
16.27 |
14.47 |
12.84 |
11.17 |
9.40 |
7.68 |
||
32 |
Qo |
77230 |
72050 |
66420 |
55310 |
45030 |
36750 |
29330 |
22240 |
16870 |
11900 |
|
Pe |
24.61 |
23.47 |
22.12 |
19.59 |
17.50 |
15.47 |
13.33 |
11.27 |
9.64 |
7.80 |
||
43 |
Qo |
68380 |
63400 |
61160 |
49460 |
40530 |
32410 |
25900 |
19920 |
|
|
|
Pe |
26.74 |
24.83 |
23.11 |
20.49 |
18.02 |
15.73 |
13.54 |
11.32 |
|
|
||
BFB-FJZ- W40HPY |
27 |
Qo |
97580 |
89470 |
82750 |
71080 |
58650 |
47770 |
38250 |
29900 |
23000 |
16730 |
Pe |
27.36 |
25.66 |
24.24 |
21.61 |
19.14 |
17.05 |
15.12 |
13.15 |
11.07 |
9.10 |
||
32 |
Qo |
91000 |
85000 |
78430 |
65500 |
53420 |
43880 |
35130 |
24470 |
20500 |
14660 |
|
Pe |
29.34 |
27.90 |
26.81 |
23.09 |
20.59 |
18.16 |
15.63 |
13.20 |
11.09 |
9.21 |
||
43 |
Qo |
81190 |
74980 |
68450 |
58650 |
48100 |
38780 |
31150 |
23980 |
|
|
|
Pe |
32.01 |
29.67 |
27.50 |
24.16 |
21.19 |
18.48 |
15.89 |
13.27 |
|
|
Note: The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-FJZ- 3HPY |
27 |
Qo |
|
|
|
5990 |
4890 |
3800 |
3060 |
2300 |
1760 |
1260 |
Pe |
|
|
|
3.22 |
2.95 |
2.34 |
1.84 |
1.51 |
1.31 |
1.08 |
||
32 |
Qo |
|
|
|
5863 |
4670 |
3560 |
2900 |
2230 |
1690 |
1170 |
|
Pe |
|
|
|
3.87 |
3.15 |
2.6 |
2.04 |
1.67 |
1.38 |
0.97 |
||
43 |
Qo |
|
|
|
|
|
|
2640 |
1980 |
1450 |
1070 |
|
Pe |
|
|
|
|
|
|
2.07 |
1.71 |
1.4 |
0.99 |
||
BFB-FJZ- 4HPY |
27 |
Qo |
|
|
|
7780 |
5950 |
4650 |
3830 |
2780 |
1900 |
1560 |
Pe |
|
|
|
3.77 |
3.35 |
2.58 |
2.05 |
1.74 |
1.42 |
1.09 |
||
32 |
Qo |
|
|
|
7440 |
5690 |
4460 |
3670 |
2560 |
1830 |
1500 |
|
Pe |
|
|
|
3.98 |
3.50 |
2.71 |
2.15 |
1.81 |
1.46 |
1.12 |
||
43 |
Qo |
|
|
|
|
|
|
3320 |
2390 |
1750 |
1200 |
|
Pe |
|
|
|
|
|
|
2.37 |
1.94 |
1.60 |
1.17 |
||
BFB-FJZ- 4HPHY |
27 |
Qo |
12720 |
10700 |
9270 |
7960 |
6080 |
4750 |
3950 |
2870 |
2090 |
1630 |
Pe |
4.34 |
4.06 |
3.86 |
3.50 |
3.22 |
2.51 |
2.01 |
1.71 |
1.41 |
1.09 |
||
32 |
Qo |
12150 |
10230 |
8970 |
7700 |
5820 |
4510 |
3680 |
2670 |
1980 |
1460 |
|
Pe |
4.49 |
4.24 |
4.05 |
3.67 |
3.38 |
2.61 |
2.05 |
1.74 |
1.44 |
1.10 |
||
43 |
Qo |
|
|
|
|
|
|
3460 |
2440 |
1800 |
1230 |
|
Pe |
|
|
|
|
|
|
2.32 |
1.92 |
1.48 |
1.06 |
||
BFB-FJZ- 5HPY |
27 |
Qo |
|
|
|
9660 |
7960 |
6620 |
5240 |
3900 |
3000 |
2160 |
Pe |
|
|
|
4.98 |
4.46 |
3.64 |
2.86 |
1.96 |
1.59 |
1.23 |
||
32 |
Qo |
|
|
|
9230 |
7610 |
6340 |
5030 |
3740 |
2880 |
2080 |
|
Pe |
|
|
|
5.25 |
4.68 |
3.82 |
2.99 |
2.04 |
1.64 |
1.25 |
||
43 |
Qo |
|
|
|
|
|
|
4550 |
3450 |
2540 |
1660 |
|
Pe |
|
|
|
|
|
|
3.24 |
2.65 |
2.07 |
1.45 |
||
BFB-FJZ- 5HPHY |
27 |
Qo |
16760 |
14620 |
11850 |
9870 |
8130 |
6760 |
5400 |
4050 |
3140 |
2250 |
Pe |
5.92 |
5.53 |
5.13 |
4.62 |
4.29 |
3.53 |
2.83 |
1.92 |
1.57 |
1.21 |
||
32 |
Qo |
15990 |
13970 |
11460 |
9550 |
7790 |
6410 |
5030 |
3710 |
2800 |
2020 |
|
Pe |
6.12 |
5.78 |
5.38 |
4.85 |
4.50 |
3.67 |
2.90 |
1.96 |
1.60 |
1.23 |
||
43 |
Qo |
|
|
|
|
|
|
4740 |
3620 |
2540 |
1680 |
|
Pe |
|
|
|
|
|
|
3.18 |
2.63 |
2.03 |
1.44 |
||
BFB-FJZ- 8HPHY |
27 |
Qo |
24560 |
20700 |
17110 |
13860 |
11200 |
9220 |
7410 |
5940 |
4590 |
3300 |
Pe |
8.31 |
7.25 |
6.59 |
6.05 |
5.59 |
4.80 |
4.49 |
3.81 |
3.14 |
2.43 |
||
32 |
Qo |
23440 |
19780 |
16540 |
13410 |
10730 |
8740 |
6900 |
5430 |
4100 |
2970 |
|
Pe |
8.60 |
7.76 |
6.91 |
6.35 |
5.87 |
5.00 |
4.58 |
3.89 |
3.21 |
2.46 |
||
43 |
Qo |
|
|
|
|
|
|
6490 |
4970 |
3480 |
2300 |
|
Pe |
|
|
|
|
|
|
4.68 |
4.01 |
3.32 |
2.55 |
||
BFB-FJZ- 10HPY |
27 |
Qo |
|
|
|
19540 |
16030 |
13230 |
10580 |
8400 |
6450 |
4630 |
Pe |
|
|
|
10.00 |
8.77 |
7.27 |
6.23 |
5.30 |
4.31 |
3.35 |
||
32 |
Qo |
|
|
|
18670 |
15330 |
12680 |
10150 |
8070 |
6210 |
4470 |
|
Pe |
|
|
|
10.54 |
9.19 |
7.63 |
6.54 |
5.51 |
4.44 |
3.42 |
||
43 |
Qo |
|
|
|
|
|
|
9170 |
7300 |
5120 |
3360 |
|
Pe |
|
|
|
|
|
|
6.83 |
5.60 |
4.55 |
3.61 |
||
BFB-FJZ- 10HPHY |
27 |
Qo |
32770 |
28590 |
23920 |
19970 |
16370 |
13420 |
10910 |
8640 |
6750 |
4850 |
Pe |
11.37 |
10.67 |
10.02 |
9.27 |
8.43 |
7.06 |
6.11 |
5.19 |
4.18 |
3.32 |
||
32 |
Qo |
31280 |
27320 |
23140 |
19320 |
15680 |
12720 |
10150 |
7900 |
6030 |
4360 |
|
Pe |
11.76 |
11.16 |
10.49 |
9.37 |
8.85 |
7.34 |
6.23 |
5.30 |
4.36 |
3.35 |
||
43 |
Qo |
|
|
|
|
|
|
9550 |
7590 |
5120 |
3390 |
|
Pe |
|
|
|
|
|
|
6.40 |
5.57 |
4.42 |
3.65 |
||
BFB-FJZ- 15HPY |
27 |
Qo |
|
|
|
28420 |
23550 |
19480 |
15510 |
12370 |
9500 |
6850 |
Pe |
|
|
|
14.18 |
11.90 |
10.70 |
9.03 |
7.68 |
5.95 |
4.80 |
||
32 |
Qo |
|
|
|
27160 |
22530 |
18660 |
14880 |
11880 |
9150 |
6610 |
|
Pe |
|
|
|
14.95 |
12.47 |
11.23 |
9.48 |
7.99 |
6.13 |
4.90 |
||
43 |
Qo |
|
|
|
|
|
|
13440 |
9050 |
6660 |
4370 |
|
Pe |
|
|
|
|
|
|
9.56 |
8.12 |
6.25 |
4.98 |
||
BFB-FJZ- 15HPHY |
27 |
Qo |
48300 |
42090 |
34470 |
28420 |
24060 |
19690 |
15840 |
12740 |
9840 |
7080 |
Pe |
16.80 |
15.71 |
14.77 |
12.96 |
11.46 |
10.33 |
8.82 |
7.33 |
5.82 |
4.56 |
||
32 |
Qo |
46110 |
40220 |
33330 |
26900 |
23040 |
18680 |
14740 |
11640 |
8790 |
6360 |
|
Pe |
17.38 |
16.42 |
15.48 |
13.60 |
12.03 |
10.76 |
9.00 |
7.48 |
5.94 |
4.60 |
||
43 |
Qo |
|
|
|
|
|
|
13870 |
9410 |
6590 |
4360 |
|
Pe |
|
|
|
|
|
|
9.26 |
7.62 |
6.04 |
4.66 |
Note: The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-FJZ- V3HPY |
27 |
Qo |
|
|
10570 |
8970 |
7580 |
6370 |
4980 |
4020 |
3080 |
2320 |
Pe |
4.78 |
4.27 |
3.86 |
3.43 |
3.07 |
2.68 |
2.26 |
1.92 |
||||
32 |
Qo |
9620 |
8240 |
6960 |
5770 |
4590 |
3650 |
2810 |
2080 |
|||
Pe |
|
|
4.95 |
4.44 |
3.97 |
3.52 |
3.13 |
2.71 |
2.29 |
1.89 |
||
43 |
Qo |
|
|
|
|
|
|
3730 |
2920 |
2190 |
1580 |
|
Pe |
|
|
|
|
|
|
3.21 |
2.73 |
2.28 |
1.83 |
||
BFB-FJZ- V5HPHY |
27 |
Qo |
15830 |
13450 |
11420 |
9690 |
8110 |
6690 |
5420 |
4310 |
3320 |
2470 |
Pe |
5.02 |
4.69 |
4.38 |
4.04 |
3.68 |
3.29 |
2.94 |
2.59 |
2.18 |
1.84 |
||
32 |
Qo |
14590 |
12400 |
10630 |
8920 |
7540 |
6130 |
4950 |
3940 |
2980 |
2190 |
|
Pe |
5.32 |
4.95 |
4.62 |
4.23 |
3.81 |
3.45 |
3.05 |
2.64 |
2.24 |
1.83 |
||
43 |
Qo |
|
|
|
|
|
4920 |
3920 |
3050 |
2270 |
1610 |
|
Pe |
|
|
|
|
|
3.63 |
3.15 |
2.69 |
2.22 |
1.75 |
||
BFB-FJZ- V4HPY |
27 |
Qo |
|
|
12270 |
10510 |
8960 |
7510 |
6040 |
4950 |
3860 |
2910 |
Pe |
|
|
5.86 |
5.28 |
4.73 |
4.21 |
3.68 |
3.18 |
2.71 |
2.24 |
||
32 |
Qo |
|
|
11110 |
9610 |
8180 |
6850 |
5610 |
4480 |
3460 |
2560 |
|
Pe |
|
|
6.08 |
5.47 |
4.87 |
4.31 |
3.75 |
3.22 |
2.71 |
2.21 |
||
43 |
Qo |
|
|
|
|
|
|
4420 |
3480 |
2660 |
1875 |
|
Pe |
|
|
|
|
|
|
3.86 |
3.26 |
2.66 |
2.11 |
||
BFB-FJZ- V6HPHY |
27 |
Qo |
18680 |
16010 |
13830 |
11680 |
9840 |
8150 |
6630 |
5270 |
4100 |
3040 |
Pe |
6.66 |
6.17 |
5.67 |
5.17 |
4.67 |
4.17 |
3.68 |
3.19 |
2.71 |
2.24 |
||
32 |
Qo |
17160 |
14710 |
12570 |
10720 |
9020 |
7440 |
6030 |
4760 |
3680 |
2690 |
|
Pe |
7.01 |
6.47 |
5.92 |
5.38 |
4.89 |
4.33 |
3.81 |
3.26 |
2.74 |
2.22 |
||
43 |
Qo |
|
|
|
|
|
5940 |
4750 |
3680 |
2770 |
1930 |
|
Pe |
|
|
|
|
|
4.49 |
3.87 |
3.25 |
2.67 |
2.09 |
||
BFB-FJZ- V5HPY |
27 |
Qo |
|
|
15710 |
13380 |
11340 |
9460 |
7750 |
6210 |
4880 |
3660 |
Pe |
|
|
6.89 |
6.28 |
5.67 |
5.06 |
4.45 |
3.85 |
3.27 |
2.69 |
||
32 |
Qo |
|
|
14400 |
12260 |
10390 |
8650 |
7060 |
5620 |
4390 |
3240 |
|
Pe |
|
|
7.21 |
6.53 |
5.92 |
5.25 |
4.59 |
3.94 |
3.31 |
2.67 |
||
43 |
Qo |
|
|
|
|
|
|
5610 |
4420 |
3360 |
2370 |
|
Pe |
|
|
|
|
|
|
4.74 |
4.11 |
3.31 |
2.61 |
||
BFB-FJZ- V7HPHY |
27 |
Qo |
22680 |
19360 |
16680 |
14050 |
11780 |
9730 |
7870 |
6230 |
4820 |
3550 |
Pe |
7.65 |
7.12 |
6.58 |
6.02 |
5.45 |
4.89 |
4.36 |
3.79 |
3.22 |
2.63 |
||
32 |
Qo |
20860 |
17810 |
15180 |
12920 |
10810 |
8890 |
7240 |
5630 |
4320 |
3130 |
|
Pe |
8.06 |
7.49 |
6.89 |
6.29 |
5.73 |
5.09 |
4.42 |
3.84 |
3.21 |
2.61 |
||
43 |
Qo |
|
|
|
|
|
7110 |
5670 |
4370 |
3260 |
2250 |
|
Pe |
|
|
|
|
|
5.33 |
4.59 |
3.85 |
3.15 |
2.43 |
||
BFB-FJZ- V6HPY |
27 |
Qo |
|
|
17800 |
15260 |
13040 |
10960 |
9040 |
7310 |
5810 |
4410 |
Pe |
|
|
8.68 |
7.83 |
7.01 |
6.22 |
5.44 |
4.71 |
3.98 |
3.29 |
||
32 |
Qo |
|
|
16320 |
13990 |
11940 |
10020 |
8250 |
6640 |
5240 |
3940 |
|
Pe |
|
|
9.08 |
8.18 |
7.36 |
6.49 |
5.59 |
4.79 |
4.05 |
3.31 |
||
43 |
Qo |
|
|
|
|
|
|
6560 |
5210 |
4030 |
3360 |
|
Pe |
|
|
|
|
|
|
5.94 |
4.99 |
4.12 |
3.24 |
||
BFB-FJZ- V9HPHY |
27 |
Qo |
26830 |
23010 |
19920 |
16850 |
14220 |
11820 |
9660 |
7730 |
6090 |
4610 |
Pe |
9.47 |
8.79 |
8.09 |
7.39 |
6.71 |
6.02 |
5.32 |
4.64 |
3.96 |
3.29 |
||
32 |
Qo |
24730 |
21230 |
18190 |
15550 |
13110 |
10870 |
8860 |
7050 |
5520 |
4110 |
|
Pe |
10.03 |
9.29 |
8.53 |
7.77 |
6.99 |
6.24 |
5.48 |
4.77 |
4.03 |
3.31 |
||
43 |
Qo |
|
|
|
|
|
8810 |
7110 |
5560 |
4230 |
3020 |
|
Pe |
|
|
|
|
|
6.82 |
5.89 |
4.99 |
4.06 |
3.25 |
Note: The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-FJZ- V8HPY |
27 |
Qo |
|
|
|
19720 |
16580 |
14130 |
11610 |
9310 |
7330 |
5490 |
Pe |
|
|
9.69 |
8.57 |
7.53 |
6.57 |
5.64 |
4.76 |
3.91 |
|||
32 |
Qo |
|
|
18140 |
15390 |
12890 |
10550 |
8420 |
6560 |
4840 |
||
Pe |
|
|
|
9.97 |
8.78 |
7.76 |
6.73 |
5.69 |
4.79 |
3.89 |
||
43 |
Qo |
|
|
|
|
|
|
8320 |
6540 |
4980 |
3530 |
|
Pe |
|
|
|
|
|
|
6.82 |
5.72 |
4.69 |
3.64 |
||
BFB-FJZ- V12HPHY |
27 |
Qo |
31830 |
27630 |
24120 |
20520 |
17370 |
14430 |
11740 |
9320 |
7230 |
5310 |
Pe |
12.43 |
11.32 |
10.25 |
9.21 |
8.22 |
7.27 |
6.36 |
5.46 |
4.59 |
3.75 |
||
32 |
Qo |
29100 |
25320 |
22110 |
18810 |
15920 |
13190 |
10680 |
8440 |
6480 |
3670 |
|
Pe |
12.97 |
11.73 |
10.59 |
9.58 |
8.44 |
7.42 |
6.51 |
5.57 |
4.65 |
3.76 |
||
43 |
Qo |
|
|
|
|
|
10510 |
8430 |
6550 |
4890 |
3370 |
|
Pe |
|
|
|
|
|
7.69 |
6.56 |
5.55 |
4.53 |
3.56 |
||
BFB-FJZ- V10HPY |
27 |
Qo |
|
|
|
22930 |
19550 |
16380 |
13440 |
10760 |
8440 |
6280 |
Pe |
|
|
|
11.24 |
9.92 |
8.69 |
7.53 |
6.45 |
5.44 |
4.47 |
||
32 |
Qo |
|
|
|
21020 |
17910 |
14970 |
12230 |
9740 |
7570 |
5550 |
|
Pe |
|
|
|
11.53 |
10.16 |
8.94 |
7.63 |
6.49 |
5.46 |
4.43 |
||
43 |
Qo |
|
|
|
|
|
|
9690 |
7610 |
5770 |
4060 |
|
Pe |
|
|
|
|
|
|
7.67 |
6.47 |
5.22 |
4.09 |
||
BFB-FJZ- V15HPHY |
27 |
Qo |
44710 |
38020 |
32590 |
27290 |
22740 |
18620 |
14930 |
11640 |
8890 |
6340 |
Pe |
13.21 |
12.11 |
11.07 |
10.09 |
9.11 |
8.16 |
7.19 |
6.22 |
5.25 |
4.31 |
||
32 |
Qo |
41140 |
35020 |
29710 |
25120 |
20910 |
17110 |
13660 |
10610 |
8020 |
5670 |
|
Pe |
13.89 |
12.64 |
11.51 |
10.42 |
9.37 |
8.34 |
7.38 |
6.34 |
5.31 |
4.29 |
||
43 |
Qo |
|
|
|
|
|
13600 |
10730 |
8190 |
6030 |
4080 |
|
Pe |
|
|
|
|
|
8.59 |
7.42 |
6.26 |
5.17 |
4.02 |
||
BFB-FJZ- V12HPY |
27 |
Qo |
|
|
|
28060 |
23850 |
19920 |
16290 |
12740 |
9780 |
7360 |
Pe |
|
|
|
13.01 |
11.52 |
10.09 |
8.85 |
7.55 |
6.37 |
5.29 |
||
32 |
Qo |
|
|
|
25730 |
21860 |
17850 |
14540 |
11570 |
8890 |
6530 |
|
Pe |
|
|
|
13.41 |
11.82 |
10.29 |
8.86 |
7.56 |
6.31 |
5.14 |
||
43 |
Qo |
|
|
|
|
|
|
11740 |
9190 |
6880 |
4840 |
|
Pe |
|
|
|
|
|
|
9.07 |
7.56 |
6.17 |
5.07 |
||
BFB-FJZ- V20HPHY |
27 |
Qo |
49770 |
43410 |
35810 |
28880 |
24460 |
20410 |
16550 |
13340 |
10210 |
7370 |
Pe |
16.12 |
14.79 |
13.47 |
12.19 |
10.92 |
9.69 |
8.48 |
7.31 |
6.19 |
5.11 |
||
32 |
Qo |
46610 |
40940 |
33600 |
27160 |
23880 |
18860 |
14990 |
11980 |
9280 |
6810 |
|
Pe |
16.79 |
15.36 |
13.92 |
12.53 |
11.16 |
8.84 |
8.56 |
7.32 |
6.19 |
5.05 |
||
43 |
Qo |
|
|
|
|
|
15440 |
12220 |
9350 |
6850 |
4680 |
|
Pe |
|
|
|
|
|
10.01 |
8.63 |
7.16 |
5.91 |
4.67 |
Note: The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
SEMI-HERMETIC COMPRESSOR & AIR-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | |||||||||
Evaporating temperature(℃) | ||||||||||||
5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-FJZ- V15HPY |
27 |
Qo |
|
|
|
36730 |
30960 |
26210 |
26860 |
16880 |
13500 |
10390 |
Pe |
|
|
|
18.54 |
16.00 |
13.99 |
12.29 |
10.57 |
8.99 |
7.34 |
||
32 |
Qo |
|
|
|
35560 |
29050 |
24060 |
18910 |
15440 |
12290 |
9330 |
|
Qo |
|
|
|
19.67 |
16.78 |
14.62 |
12.77 |
10.84 |
9.20 |
7.54 |
||
43 |
Pe |
|
|
|
|
|
|
16470 |
13130 |
10290 |
8520 |
|
Qo |
|
|
|
|
|
|
12.95 |
11.06 |
9.38 |
7.69 |
||
BFB-FJZ- V25HPHY |
27 |
Qo |
61980 |
52530 |
45040 |
38250 |
31690 |
25920 |
20990 |
16690 |
13170 |
9520 |
Pe |
21.98 |
20.27 |
18.24 |
16.48 |
14.80 |
13.22 |
11.70 |
10.03 |
8.45 |
6.88 |
||
32 |
Qo |
59050 |
49940 |
42950 |
36500 |
30340 |
24090 |
19270 |
15430 |
12300 |
9230 |
|
Qo |
23.14 |
21.29 |
19.00 |
17.23 |
16.19 |
13.51 |
11.64 |
9.89 |
8.24 |
6.67 |
||
43 |
Pe |
|
|
|
|
|
|
16660 |
13100 |
10150 |
8430 |
|
Qo |
|
|
|
|
|
|
12.13 |
10.31 |
8.51 |
6.81 |
||
BFB-FJZ- V20HPY |
27 |
Qo |
|
|
|
43540 |
36070 |
29700 |
24220 |
19710 |
15870 |
12300 |
Pe |
|
|
|
20.90 |
18.10 |
15.86 |
13.90 |
12.08 |
10.20 |
8.33 |
||
32 |
Qo |
|
|
|
41650 |
34170 |
27970 |
22770 |
18760 |
15150 |
11660 |
|
Pe |
|
|
|
22.04 |
18.97 |
16.64 |
14.60 |
12.57 |
10.61 |
8.59 |
||
43 |
Qo |
|
|
|
|
|
|
19840 |
15950 |
12630 |
10650 |
|
Pe |
|
|
|
|
|
|
14.80 |
12.80 |
10.82 |
8.77 |
||
BFB-FJZ- W25HPY |
27 |
Qo |
|
|
|
51690 |
44860 |
38170 |
31760 |
25740 |
20350 |
15500 |
Pe |
|
|
|
28.15 |
24.71 |
21.53 |
18.55 |
15.81 |
13.27 |
10.91 |
||
32 |
Qo |
|
|
|
49050 |
41100 |
35040 |
29180 |
23660 |
18580 |
14030 |
|
Pe |
|
|
|
29.57 |
25.43 |
22.15 |
19.03 |
16.13 |
13.43 |
10.97 |
||
43 |
Qo |
|
|
|
|
|
|
24720 |
19620 |
15080 |
11100 |
|
Pe |
|
|
|
|
|
|
19.31 |
16.46 |
13.51 |
11.04 |
||
BFB-FJZ- V30HPHY |
27 |
Qo |
70790 |
59870 |
51540 |
43890 |
36450 |
29470 |
24090 |
19420 |
15940 |
12400 |
Pe |
25.29 |
22.99 |
20.58 |
18.56 |
16.70 |
14.95 |
13.27 |
11.37 |
9.70 |
8.04 |
||
32 |
Qo |
67650 |
57240 |
49350 |
41980 |
34980 |
28300 |
23160 |
18700 |
15380 |
11760 |
|
Pe |
26.16 |
24.04 |
21.56 |
19.47 |
17.54 |
15.40 |
13.40 |
11.48 |
9.80 |
8.12 |
||
43 |
Qo |
|
|
|
|
|
|
19860 |
15880 |
12690 |
10700 |
|
Pe |
|
|
|
|
|
|
14.01 |
11.96 |
10.09 |
8.22 |
||
BFB-FJZ- W30HPY |
27 |
Qo |
|
|
|
63940 |
54080 |
45160 |
36770 |
29850 |
24080 |
18630 |
Pe |
|
|
|
31.04 |
26.77 |
23.50 |
20.69 |
17.89 |
15.21 |
12.33 |
||
32 |
Qo |
|
|
|
61260 |
51330 |
42410 |
34590 |
28400 |
21070 |
17740 |
|
Pe |
|
|
|
32.69 |
28.11 |
24.72 |
21.77 |
18.58 |
15.93 |
12.86 |
||
43 |
Qo |
|
|
|
|
|
|
29300 |
23550 |
18650 |
14040 |
|
Pe |
|
|
|
|
|
|
22.08 |
18.96 |
16.01 |
12.99 |
||
BFB-FJZ- W35HPHY |
27 |
Qo |
85830 |
72600 |
62290 |
52520 |
45210 |
38940 |
33340 |
26090 |
20580 |
15680 |
Pe |
34.14 |
30.87 |
27.81 |
25.07 |
22.84 |
20.29 |
17.66 |
14.94 |
12.57 |
10.57 |
||
32 |
Qo |
81140 |
68840 |
58540 |
49460 |
41990 |
35620 |
29780 |
24090 |
18740 |
14230 |
|
Pe |
35.38 |
32.49 |
29.19 |
26.53 |
23.81 |
20.81 |
18.07 |
15.81 |
12.87 |
10.77 |
||
43 |
Qo |
|
|
|
|
|
|
25180 |
19780 |
15270 |
11270 |
|
Pe |
|
|
|
|
|
|
18.36 |
16.16 |
13.17 |
10.82 |
||
BFB-FJZ- W40HPHY |
27 |
Qo |
106180 |
89810 |
77060 |
64970 |
54500 |
46070 |
38600 |
30260 |
24360 |
18850 |
Pe |
37.55 |
33.98 |
30.57 |
27.57 |
24.75 |
22.15 |
19.70 |
16.91 |
14.41 |
11.93 |
||
32 |
Qo |
101350 |
85990 |
73130 |
61780 |
52440 |
43110 |
35300 |
28920 |
22170 |
17990 |
|
Pe |
39.08 |
35.89 |
32.24 |
29.30 |
26.32 |
23.19 |
20.13 |
18.20 |
15.27 |
12.62 |
||
43 |
Qo |
|
|
|
|
|
|
29850 |
23740 |
18890 |
14250 |
|
Pe |
|
|
|
|
|
|
20.77 |
18.62 |
15.61 |
12.74 |
||
BFB-FJZ- W40HPY |
27 |
Qo |
|
|
|
76400 |
64570 |
53810 |
43680 |
35440 |
28400 |
21880 |
Pe |
|
|
|
37.25 |
32.13 |
28.10 |
24.65 |
21.17 |
17.96 |
14.50 |
||
32 |
Qo |
|
|
|
73080 |
61170 |
50520 |
41060 |
33740 |
27110 |
20750 |
|
Pe |
|
|
|
39.28 |
33.67 |
29.49 |
25.88 |
22.02 |
18.68 |
14.95 |
||
43 |
Qo |
|
|
|
|
|
|
34760 |
27810 |
21920 |
16360 |
|
Pe |
|
|
|
|
|
|
26.24 |
22.37 |
18.79 |
15.60 |
||
BFB-FJZ- W50HPHY |
27 |
Qo |
127010 |
107360 |
92040 |
77410 |
65010 |
54890 |
44690 |
35940 |
28840 |
22070 |
Pe |
47.01 |
42.40 |
38.08 |
34.43 |
30.99 |
27.77 |
24.70 |
21.28 |
18.02 |
14.72 |
||
32 |
Qo |
121360 |
102640 |
87200 |
74190 |
62390 |
51210 |
41880 |
34140 |
27360 |
20970 |
|
Pe |
48.64 |
44.33 |
39.90 |
36.11 |
32.54 |
28.61 |
24.94 |
21.49 |
18.21 |
14.82 |
||
43 |
Qo |
|
|
|
|
|
|
35460 |
28020 |
22210 |
16620 |
|
Pe |
|
|
|
|
|
|
25.71 |
21.97 |
18.36 |
15.13 |
Note: The refrigerating effect is got on the basis of suction temperature 20℃ and liquid with over-cold.
SEMI - HERMETIC COMPRESSOR & WATER-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | ||||||||||
Evaporating temperature(℃) | |||||||||||||
12.5 | 10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-WJZ- 3HP |
40 |
Qo |
|
|
|
|
|
7360 |
5800 |
4520 |
3360 |
2590 |
|
BFB-WJZ- 4HPH |
40 |
Qo |
|
|
|
|
|
9150 |
7230 |
5670 |
4230 |
3300 |
|
BFB-WJZ- 4HPH |
40 |
Qo |
|
|
14440 |
13180 |
10760 |
9150 |
7230 |
5670 |
4230 |
3300 |
|
BFB-WJZ- 5HP |
40 |
Qo |
|
|
|
|
|
11690 |
9550 |
7580 |
6020 |
3300 |
|
BFB-WJZ- 5HPH |
40 |
Qo |
22700 |
20810 |
19010 |
17360 |
14710 |
11690 |
9550 |
7580 |
6020 |
4520 |
|
BFB-WJZ- 8HPH |
40 |
Qo |
|
|
27870 |
25450 |
20820 |
16880 |
13410 |
10440 |
8210 |
4520 |
|
BFB-WJZ- 10HP |
40 |
Qo |
|
|
|
|
|
23610 |
19320 |
15270 |
12040 |
6200 |
|
BFB-WJZ- 10HPH |
40 |
Qo |
44390 |
40720 |
37190 |
33970 |
28760 |
23610 |
19320 |
15270 |
12040 |
9110 |
|
BFB-WJZ- 15HP |
40 |
Qo |
|
|
|
|
|
34710 |
28120 |
22440 |
17710 |
9110 |
|
BFB-WJZ- 15HPH |
40 |
Qo |
65440 |
61020 |
55680 |
49510 |
42340 |
35280 |
28450 |
22660 |
17670 |
13360 |
|
BFB-WJZ- V3HP |
40 |
Qo |
|
|
|
|
|
11000 |
8850 |
7010 |
5890 |
4560 |
3460 |
BFB-WJZ- V5HPH |
40 |
Qo |
21150 |
19360 |
17710 |
16150 |
13470 |
11010 |
8860 |
7010 |
5420 |
4050 |
2940 |
BFB-WJZ- V4HP |
40 |
Qo |
|
|
|
|
|
13560 |
10960 |
8700 |
7400 |
5740 |
4350 |
BFB-WJZ- V6HPH |
40 |
Qo |
26220 |
24100 |
21950 |
20040 |
16590 |
13570 |
10970 |
8710 |
6770 |
5110 |
3730 |
BFB-WJZ- V5HP |
40 |
Qo |
|
|
|
|
|
16330 |
13190 |
10480 |
8650 |
6740 |
5120 |
BFB-WJZ- V7HPH |
40 |
Qo |
31530 |
28860 |
26390 |
24110 |
20140 |
16330 |
13190 |
10480 |
8150 |
6210 |
4500 |
BFB-WJZ- V6HP |
40 |
Qo |
|
|
|
|
|
19650 |
16080 |
12820 |
10020 |
7620 |
5650 |
BFB-WJZ- V9HPH |
40 |
Qo |
37740 |
34580 |
31640 |
28960 |
23980 |
19650 |
16080 |
12830 |
10030 |
7630 |
5660 |
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and the degree of supercooling 5℃.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI-HERMETIC COMPRESSOR & WATER-COOLED CONDENSING UNIT CAPACITY
R22 Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | ||||||||||
Evaporating temperature(℃) | |||||||||||||
12.5 | 10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-WJZ- V8HP |
40 |
Qo |
|
|
|
|
|
26390 |
21490 |
17310 |
13870 |
10780 |
8040 |
BFB-WJZ- V12HPH |
40 |
Qo |
50120 |
45250 |
41470 |
37930 |
31580 |
26260 |
21190 |
17040 |
13570 |
10470 |
7820 |
BFB-WJZ- V10HP |
40 |
Qo |
|
|
|
|
|
30520 |
24940 |
20120 |
16060 |
12460 |
9310 |
BFB-WJZ- V15HPH |
40 |
Qo |
59690 |
54230 |
50180 |
45410 |
37680 |
30990 |
25220 |
20130 |
16030 |
12300 |
9130 |
BFB-WJZ- V12HP |
40 |
Qo |
|
|
|
|
|
35550 |
29060 |
23430 |
18600 |
14470 |
10710 |
BFB-WJZ- V20HPH |
40 |
Qo |
68480 |
62760 |
57520 |
52570 |
43650 |
35890 |
29150 |
24050 |
18340 |
14070 |
10430 |
BFB-WJZ- V15HP |
40 |
Qo |
|
|
|
|
|
45210 |
34500 |
29440 |
23210 |
17860 |
13350 |
BFB-WJZ- V25HPH |
40 |
Qo |
86570 |
79430 |
72770 |
66500 |
55300 |
45500 |
37010 |
29730 |
23400 |
18020 |
13450 |
BFB-WJZ- V20HP |
40 |
Qo |
|
|
|
|
|
51960 |
40280 |
34060 |
26770 |
20530 |
15700 |
BFB-WJZ- W25HP |
40 |
Qo |
|
|
|
|
|
68340 |
55770 |
44700 |
35240 |
26920 |
20030 |
BFB-WJZ- W30HP |
40 |
Qo |
|
|
|
|
|
77950 |
63520 |
51100 |
40410 |
31040 |
23110 |
BFB-WJZ- V30HPH |
40 |
Qo |
98580 |
90460 |
82920 |
75860 |
63060 |
52260 |
40480 |
34360 |
27170 |
20930 |
15900 |
BFB-WJZ- W35HPH |
40 |
Qo |
129490 |
118930 |
109020 |
99800 |
83080 |
68820 |
56050 |
45050 |
35580 |
27180 |
20150 |
BFB-WJZ- W40HPH |
40 |
Qo |
147960 |
135830 |
124460 |
113770 |
94650 |
77950 |
63520 |
51100 |
40410 |
31330 |
23690 |
BFB-WJZ- W40HP |
40 |
Qo |
|
|
|
|
|
92170 |
76260 |
60750 |
48230 |
37150 |
17890 |
BFB-WJZ- W50HPH |
40 |
Qo |
173900 |
159700 |
146430 |
134010 |
111660 |
92370 |
76460 |
60850 |
48430 |
37350 |
27990 |
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and the degree of supercooling 5℃
2. If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI-HERMETIC COMPRESSOR & WATER-COOLED CONDENSING UNIT CAPACITY
R134a Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | ||||||||||
Evaporating temperature(℃) | |||||||||||||
12.5 | 10 | 7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | |||
BFB-WJZ- 3HPY |
40 |
Qo |
9940 |
9000 |
8010 |
7350 |
6140 |
4810 |
3870 |
2900 |
1910 |
1400 |
930 |
BFB-WJZ- 4HPY |
40 |
Qo |
11080 |
10090 |
9160 |
8290 |
6670 |
5670 |
4320 |
3310 |
2240 |
1580 |
1080 |
BFB-WJZ- 5HPY |
40 |
Qo |
14590 |
13290 |
12060 |
10920 |
9120 |
7133 |
5710 |
4450 |
3190 |
2290 |
1510 |
BFB-WJZ- 8HPHY |
40 |
Qo |
21330 |
19440 |
16750 |
14000 |
12917 |
10300 |
8010 |
6130 |
4350 |
3150 |
|
BFB-WJZ- 10HPY |
40 |
Qo |
28550 |
26020 |
23590 |
21300 |
17850 |
14400 |
11560 |
8970 |
6380 |
4640 |
|
BFB-WJZ- 15HPY |
40 |
Qo |
42080 |
38350 |
24780 |
31430 |
26280 |
21120 |
16820 |
13180 |
9400 |
6800 |
4800 |
BFB-WJZ- V3HPY |
40 |
Qo |
13790 |
12530 |
11380 |
10300 |
8370 |
6720 |
5310 |
4110 |
3100 |
2240 |
1560 |
BFB-WJZ- V4HPY |
40 |
Qo |
17850 |
16220 |
14720 |
13330 |
10840 |
8720 |
6910 |
5380 |
4110 |
3040 |
2160 |
BFB-WJZ- V5HPY |
40 |
Qo |
21270 |
19360 |
17580 |
15950 |
13010 |
10480 |
8310 |
6480 |
4930 |
3640 |
2580 |
BFB-WJZ- V6HPY |
40 |
Qo |
25480 |
23180 |
21070 |
19100 |
15590 |
12570 |
10010 |
7820 |
5980 |
4430 |
3150 |
BFB-WJZ- V8HPY |
40 |
Qo |
33270 |
30280 |
27490 |
24890 |
20290 |
16340 |
12960 |
10080 |
7650 |
5620 |
3910 |
BFB-WJZ- V10HPY |
40 |
Qo |
38810 |
35280 |
32050 |
29060 |
23670 |
19020 |
15050 |
11680 |
8820 |
6410 |
4390 |
BFB-WJZ- V12HPY |
40 |
Qo |
44390 |
40380 |
36700 |
33270 |
26310 |
21850 |
17330 |
13480 |
10230 |
7500 |
5220 |
BFB-WJZ- V15HPY |
40 |
Qo |
59460 |
54030 |
48890 |
44230 |
35890 |
28710 |
22650 |
17560 |
13290 |
9760 |
6870 |
BFB-WJZ- V20HPY |
40 |
Qo |
66570 |
61430 |
54830 |
49580 |
40210 |
32230 |
25450 |
19770 |
14990 |
11040 |
7820 |
BFB-WJZ- W25HPY |
40 |
Qo |
88780 |
80680 |
73050 |
66100 |
53560 |
42900 |
33870 |
26200 |
19830 |
14570 |
10260 |
BFB-WJZ- W30HPY |
40 |
Qo |
99920 |
90740 |
82250 |
74410 |
60370 |
48430 |
38210 |
29660 |
22500 |
16590 |
11730 |
BFB-WJZ- W40HPY |
40 |
Qo |
117390 |
106690 |
96760 |
87590 |
71160 |
57210 |
45270 |
35240 |
26880 |
19920 |
14220 |
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and the degree of supercooling 5℃.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI·HERMETIC COMPRESSOR & WATER-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | ||||||||||
Evaporating temperature(℃) | |||||||||||||
7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-WJZ- 3HPHY |
40 |
Qo |
|
|
|
8160 |
6480 |
5120 |
3870 |
3040 |
2200 |
1590 |
1080 |
BFB-WJZ- 4HPHY |
40 |
Qo |
|
|
|
9470 |
8040 |
6010 |
4550 |
3630 |
2530 |
1650 |
1280 |
BFB-WJZ- 4HPHY |
40 |
Qo |
14680 |
13440 |
11050 |
9470 |
8040 |
6010 |
4550 |
3630 |
2530 |
1650 |
1280 |
BFB-WJZ- 5HPY |
40 |
Qo |
|
|
|
12100 |
9980 |
8000 |
6480 |
4970 |
3590 |
2600 |
1770 |
BFB-WJZ- 5HPHY |
40 |
Qo |
19330 |
17700 |
15100 |
12100 |
9980 |
8000 |
6480 |
4970 |
3590 |
2600 |
1770 |
BFB-WJZ- 8HPHY |
40 |
Qo |
|
25950 |
21390 |
17480 |
14000 |
11080 |
8830 |
6820 |
5260 |
3810 |
2600 |
BFB-WJZ- 10HPY |
40 |
Qo |
|
|
|
24640 |
20490 |
16300 |
12960 |
10240 |
7390 |
5700 |
3920 |
BFB-WJZ- 10HPHY |
40 |
Qo |
37810 |
34630 |
29540 |
24440 |
20190 |
16200 |
12860 |
10040 |
7730 |
5600 |
3820 |
BFB-WJZ- 15HPY |
40 |
Qo |
|
|
|
35420 |
28300 |
23000 |
18970 |
14680 |
11180 |
8080 |
5360 |
BFB-WJZ- 15HPHY |
40 |
Qo |
55740 |
51000 |
43490 |
35220 |
28100 |
22800 |
18870 |
14580 |
11080 |
8070 |
5280 |
BFB-WJZ- V3HPY |
40 |
Qo |
|
|
|
11500 |
9470 |
7700 |
6170 |
4860 |
3730 |
2770 |
1970 |
BFB-WJZ- V5HPHY |
40 |
Qo |
18150 |
16650 |
13950 |
11590 |
9530 |
7750 |
6210 |
4870 |
3740 |
2780 |
1960 |
BFB-WJZ- V4HPY |
40 |
Qo |
|
|
|
14370 |
11810 |
9600 |
7680 |
6040 |
4630 |
3430 |
2420 |
BFB-WJZ- V6HPHY |
40 |
Qo |
23030 |
21140 |
17690 |
14670 |
12060 |
9790 |
7820 |
6130 |
4670 |
3450 |
2410 |
BFB-WJZ- V5HPY |
40 |
Qo |
|
|
|
17560 |
14450 |
11750 |
9410 |
7400 |
5690 |
4230 |
3000 |
BFB-WJZ- V7HPHY |
40 |
Qo |
27360 |
25070 |
20990 |
17400 |
14280 |
11570 |
9220 |
7210 |
5480 |
4020 |
2790 |
BFB-WJZ- V6HPY |
40 |
Qo |
|
|
|
21000 |
17330 |
14130 |
11360 |
8980 |
6940 |
5210 |
3750 |
BFB-WJZ- V9HPHY |
40 |
Qo |
32690 |
30000 |
25170 |
20990 |
17320 |
14120 |
11370 |
8990 |
6960 |
5220 |
3750 |
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and the degree of supercooling 5℃.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
SEMI · HERMETIC COMPRESSOR & WATER-COOLED CONDENSING UNIT CAPACITY
R404A Watt(50Hz 380v)
Model |
Condensing temperature(℃) |
↓ |
Capacity Qo(kw) Power Consumption Pe(kw) | ||||||||||
Evaporating temperature(℃) | |||||||||||||
7.5 | 5 | 0 | -5 | -10 | -15 | -20 | -25 | -30 | -35 | -40 | |||
BFB-WJZ- V8HPY |
40 |
Qo |
|
|
|
27610 |
22680 |
18380 |
14690 |
11500 |
8780 |
6490 |
4560 |
BFB-WJZ- V12HPY |
40 |
Qo |
43280 |
39650 |
33130 |
27410 |
22490 |
18170 |
14460 |
11260 |
8550 |
6240 |
4300 |
BFB-WJZ- V10HPHY |
40 |
Qo |
|
|
|
32140 |
26370 |
21390 |
17040 |
13330 |
10170 |
7480 |
5210 |
BFB-WJZ- V15HPY |
40 |
Qo |
51940 |
47610 |
39750 |
32880 |
26910 |
21740 |
17270 |
13420 |
10140 |
7350 |
4990 |
BFB-WJZ- V12HPY |
40 |
Qo |
|
|
|
37280 |
30540 |
24550 |
19610 |
15360 |
11720 |
8650 |
6060 |
BFB-WJZ- V20HPHY |
40 |
Qo |
60200 |
55300 |
46100 |
38100 |
30310 |
24440 |
19580 |
15040 |
11330 |
8300 |
5570 |
BFB-WJZ- V15HPY |
40 |
Qo |
|
|
|
48110 |
39720 |
32430 |
26160 |
20760 |
16150 |
12220 |
8920 |
BFB-WJZ- V25HPHY |
40 |
Qo |
74700 |
68530 |
57430 |
47680 |
39230 |
30850 |
25530 |
20080 |
15370 |
11390 |
8030 |
BFB-WJZ- V20HPY |
40 |
Qo |
|
|
|
53170 |
47000 |
37780 |
30240 |
24000 |
18850 |
14350 |
10540 |
BFB-WJZ- W25HPY |
40 |
Qo |
|
|
|
72090 |
59450 |
48440 |
39190 |
30950 |
23960 |
18220 |
13300 |
BFB-WJZ- V30HPHY |
40 |
Qo |
85310 |
78260 |
65460 |
52550 |
44970 |
36630 |
29000 |
23000 |
17890 |
13790 |
7970 |
BFB-WJZ- W30HPY |
40 |
Qo |
|
|
|
83680 |
69150 |
56650 |
45850 |
36590 |
28560 |
21780 |
15980 |
BFB-WJZ- W35HPHY |
40 |
Qo |
112230 |
102870 |
86180 |
71500 |
59070 |
47960 |
38420 |
30180 |
23200 |
17320 |
12360 |
BFB-WJZ- W40HPHY |
40 |
Qo |
12800C |
117390 |
89240 |
81480 |
67420 |
54820 |
44080 |
34960 |
27120 |
20540 |
15000 |
BFB-WJZ- W40HPY |
40 |
Qo |
|
|
|
99910 |
82620 |
67630 |
54630 |
43460 |
33900 |
25690 |
18760 |
BFB-WJZ- W50HPHY |
40 |
Qo |
153120 |
140400 |
117390 |
100190 |
82820 |
67730 |
54830 |
43560 |
34100 |
25790 |
18860 |
Note:
1.The refrigerating effect is got on the basis of suction temperature 20℃ and the degree of supercooling 5℃.
2.If the service temperature is very low, a cooling spray system should be equiped. For the details please refer to the compressor instructions.
OVERALL DIMENSION OF AIR-COOLED CONDENSING UNIT
TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR AIR-COOLED CONDENSING UNIT
Unit model |
Dimension ( mm ) |
Outlet diameter(mm) |
Inlet diameter(mm) |
|||||
A |
B |
D |
E |
H |
L |
|||
BFB-FJZ-3HP(Y) |
720 |
520 |
133 |
480 |
739 |
780 |
12 |
19.5 |
BFB-FJZ-4HP(Y) |
885 |
520 |
159 |
487 |
810 |
780 |
12 |
25 |
BFB-FJZ-4HPH(Y) |
885 |
520 |
159 |
487 |
810 |
780 |
12 |
25 |
BFB-FJZ_5HP(Y) |
885 |
520 |
159 |
487 |
810 |
780 |
12 |
25 |
BFB-FJZ-5HPH(Y) |
885 |
520 |
159 |
487 |
810 |
780 |
12 |
25 |
BFB-FJZ-8HPH(Y) |
980 |
840 |
180 |
455 |
965 |
930 |
16 |
25 |
BFB-FJZ-IOHP(Y) |
1280 |
1120 |
159 |
455 |
965 |
930 |
16 |
31.75 |
BFB-FJZ-IOHPH(Y) |
1280 |
1120 |
159 |
455 |
965 |
930 |
16 |
31.75 |
BFB_FJZ_15HP(Y) |
1470 |
1100 |
180 |
455 |
965 |
950 |
16 |
31.75 |
BFB_FJZ_15HPH(Y) |
1470 |
1100 |
180 |
455 |
965 |
950 |
16 |
38 |
BFB-FJZ-V3HP(Y)~BFB-FJZ-V7HPH(Y),BFB-FJZ-V9HPH(Y)
BFB-FJZ-V8HP(Y),BFB-FJZ-V10HP(Y)〜BFB-FJZ-V15HPH(Y)
BFB-FJZ-V20HPH(Y)
NEW TYPE TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR AIR-COOLED CONDENSING UNIT
Unit model |
Dimension ( mm ) |
Mounting Dimension(mm) |
Outlet diameter(mm) |
Inlet diameter(mm) |
|||
A |
L |
H |
B |
E |
|||
BFB-FJZ-V3HP (Y) |
890 |
850 |
815 |
683 |
375 |
Φ12 |
Φ22 |
BFB-FJZ-V5HPH (Y) |
890 |
850 |
815 |
683 |
375 |
Φ12 |
Φ22 |
BFB-FJZ-V4HP (Y) |
890 |
850 |
815 |
683 |
375 |
Φ12 |
Φ28 |
BFB-FJZ-V6HPH (Y) |
910 |
1010 |
1065 |
683 |
375 |
Φ12 |
Φ28 |
BFB-FJZ-V5HP (Y) |
890 |
850 |
815 |
683 |
375 |
Φ12 |
Φ28 |
BFB-FJZ-V7HPH (Y) |
1000 |
1070 |
1065 |
1103 |
435 |
Φ16 |
Φ28 |
BFB-FJZ-V6HP (Y) |
930 |
1010 |
875 |
683 |
375 |
Φ16 |
Φ28 |
BFB-FJZ-V9HPH (Y) |
1000 |
1070 |
1035 |
1103 |
435 |
Φ16 |
Φ28 |
BFB-FJZ-V8HP (Y) |
1280 |
1070 |
980 |
1103 |
455 |
Φ16 |
Φ35 |
BFB-FJZ-V12HPH (Y) |
1280 |
1070 |
980 |
1103 |
455 |
Φ16 |
Φ35 |
BFB-FJZ-V10HP (Y) |
1280 |
1070 |
980 |
1103 |
455 |
Φ16 |
Φ35 |
BFB-FJZ-V15HPH (Y) |
1450 |
1000 |
1045 |
1103 |
455 |
Φ16 |
Φ42 |
BFB-FJZ-V12HP (Y) |
1450 |
1070 |
980 |
1103 |
455 |
Φ16 |
Φ35 |
BFB-FJZ-V20HPH (Y) |
1770 |
1180 |
1100 |
1594 |
1130 |
Φ22 |
Φ42 |
NEW TYPE TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR AIR-COOLED CONDENSING UNIT
Unit model |
Dimension(mm) |
Mounting Dimenson(mm) |
Outlet diameter(mm) |
Inlet diameter(mm) |
|||
A |
L |
H |
B |
E |
|||
B-FJZ-V15HP(Y) |
1450 |
1120 |
1050 |
1274 |
1070 |
0Φ22 |
Φ42 |
B-FJZ-V25HP(Y) |
1770 |
1180 |
1100 |
797×797 |
1130 |
Φ22 |
Φ42 |
B-FJZ-V20HP |
1640 |
1180 |
1000 |
1464 |
1130 |
Φ22 |
Φ42 |
B-FJZ-V30HPH |
1650 |
1270 |
1400 |
762×762 |
1220 |
Φ22 |
Φ42 |
B-FJZ-W25HP |
1770 |
1180 |
1100 |
797×797 |
1130 |
Φ22 |
Φ42 |
B-FJZ-W35HPH |
1650 |
1270 |
1600 |
762×762 |
1220 |
Φ28 |
Φ42 |
B-FJZ-W30HP |
1650 |
1270 |
1400 |
762×762 |
1220 |
Φ22 |
Φ42 |
B-FJZ-W40HPH |
1850 |
1180 |
1600 |
837×837 |
1130 |
Φ28 |
Φ54 |
B-FJZ-W40HP |
1650 |
1270 |
1500 |
762×762 |
1220 |
Φ28 |
Φ54 |
B-FJZ-W50HPH |
2130 |
1180 |
1800 |
977×977 |
1130 |
Φ28 |
Φ54 |
OVERALL DIMENSION OF WATER-COOLED CONDENSING UNIT
BFB-WJZ-3HP(Y)~BFB-WJZ-15HPH(Y)
TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR WATER-COOLED CONDENSING UNIT
Unit model |
Dimension ( mm ) |
Outlet diameter(mm) |
Inlet diameter(mm) |
||||||
A |
B |
C |
D |
H |
L |
E |
|||
BFB-WJZ-3HP(Y) |
906 |
550 |
450 |
168 |
585 |
370 |
330 |
12 |
19.5 |
BFB-WJZ-4HPH(Y) |
1030 |
690 |
480 |
219 |
720 |
370 |
330 |
12 |
25 |
BFB-WJZ-4HPH(Y) |
1030 |
690 |
480 |
219 |
720 |
370 |
330 |
12 |
25 |
BFB-WJZ-5HP(Y) |
1030 |
690 |
480 |
219 |
720 |
370 |
330 |
12 |
25 |
BFB-WJZ-5HPH(Y) |
1030 |
690 |
480 |
219 |
720 |
370 |
330 |
12 |
25 |
BFB-WJZ-8HPH(Y) |
1180 |
780 |
480 |
219 |
800 |
370 |
330 |
16 |
31.75 |
BFB-WJZ-IOHP(Y) |
1230 |
780 |
480 |
219 |
800 |
370 |
330 |
16 |
31.75 |
BFB-WJZ-IOHPH(Y) |
1230 |
780 |
480 |
219 |
800 |
370 |
330 |
16 |
31.75 |
BFB-WJZ-15HP(Y) |
1230 |
890 |
500 |
273 |
800 |
440 |
400 |
16 |
38 |
BFB-WJZ-15HPH(Y) |
1230 |
890 |
500 |
273 |
800 |
440 |
400 |
16 |
38 |
OVERALL DIMENSION OF WATER-COOLED CONDENSING UNIT
TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR WATER-COOLED CONDENSING UNIT
Unit model |
Dimension ( mm ) |
Outlet diameter(mm) |
Inlet diameter(mm) |
||||
A |
B |
E |
H |
L |
|||
BFB-WJZ-V3HP(Y) |
1056 |
690 |
330 |
738 |
480 |
Φ12 |
Φ22 |
BFB-WJZ-V5HPH(Y) |
1056 |
690 |
330 |
738 |
480 |
Φ12 |
Φ22 |
BFB-WJZ-V4HP(Y) |
1056 |
690 |
330 |
738 |
480 |
Φ12 |
Φ28 |
BFB-WJZ-V6HPH(Y) |
1206 |
780 |
330 |
738 |
480 |
Φ12 |
Φ28 |
BFB-WJZ-V5HP(Y) |
1056 |
690 |
330 |
738 |
480 |
Φ12 |
Φ28 |
BFB-WJZ-V7HPH(Y) |
1206 |
780 |
330 |
738 |
480 |
Φ16 |
Φ28 |
BFB-WJZ-V6HP(Y) |
1206 |
780 |
330 |
738 |
480 |
Φ16 |
Φ28 |
BFB-WJZ-V9HPH(Y) |
1206 |
780 |
330 |
738 |
480 |
Φ16 |
Φ28 |
BFB-WJZ-V8HP(Y) |
1206 |
780 |
330 |
740 |
650 |
Φ16 |
Φ35 |
BFB-WJZ-V12HPH(Y) |
1246 |
890 |
400 |
805 |
650 |
Φ16 |
Φ35 |
BFB-WJZ-VIOHP(Y) |
1246 |
890 |
400 |
805 |
650 |
Φ16 |
Φ35 |
BFB-WJZ-V15HPH(Y) |
1356 |
900 |
400 |
805 |
650 |
Φ16 |
Φ42 |
BFB-WJZ-V12HP(Y) |
1246 |
890 |
400 |
805 |
650 |
Φ16 |
Φ35 |
BFB-WJZ-V20HPH(Y) |
1356 |
900 |
400 |
805 |
650 |
Φ22 |
Φ42 |
BFB-WJZ-V15HP(Y)~BFB-WJZ-W50HPH(Y)
TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR WATER-COOLED CONDENSING UNIT
Unit model |
Dimension ( mm ) |
Outlet diameter(mm) |
Inlet diameter(mm) |
||||||
A |
B |
C |
D |
H |
L |
E |
|||
BFB-WJZ-V15HP(Y) |
1380 |
900 |
650 |
273 |
950 |
440 |
400 |
22 |
42 |
BFB-WJZ-V25HPH(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
22 |
42 |
BFB-WJZ-V20HP(Y) |
1380 |
900 |
650 |
273 |
950 |
440 |
400 |
22 |
42 |
BFB-WJZ-W25HP(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
22 |
42 |
BFB-WJZ-V30HPH(Y) |
1735 |
1200 |
650 |
273 |
950 |
440 |
400 |
22 |
42 |
BFB-WJZ-W30HP(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
22 |
42 |
BFB-WJZ-W35HPH(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
28 |
42 |
BFB-WJZ-W40HPH(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
28 |
54 |
BFB-WJZ-W40HP(Y) |
1735 |
1200 |
700 |
273 |
1000 |
440 |
400 |
28 |
54 |
BFB-WJZ-W50HPH(Y) |
2165 |
1430 |
700 |
273 |
1000 |
440 |
400 |
28 |
54 |
OVERALL DIMENSION OF PARALLEL WATER-COOLED CONDENSING UNIT
BFB-WJZ80HP(2)(Y)~BFB-WJZ200HPH(4)(Y) Parallel unit
TABLE OF UNIT OVERALL DIMENTION FOR SEMI-HERMETIC COMPRESSOR WATER-COOLED CONDENSING PARALLEL UNIT
Unit model |
Dimension ( mm ) |
Outlet diameter Φmm |
Inlet diameter Φmm |
||||||
A |
B |
C |
D |
H |
E |
L |
|||
BFB-WJZ-80HP(2)(Y) |
2000 |
1880 |
900 |
Φ325 |
1980 |
950 |
1000 |
Φ35 |
Φ76 |
BFB-WJZ_90HPH(3)(Y) |
2260 |
2160 |
850 |
Φ325 |
1700 |
900 |
950 |
Φ35 |
Φ89 |
BFB-WJZ-120HP(3)(Y) |
2712 |
2595 |
900 |
Φ325 |
1750 |
950 |
1000 |
Φ42 |
Φ108 |
BFB-WJZ-200HPH(4)(Y) |
3470 |
3307 |
1000 |
Φ426 |
2100 |
1050 |
1100 |
Φ54 |
Φ108 |
Note: other requirements for unit, is can as custormer application and we can do special order make. The unit refrigeration quantity is the corresponding single plane multiple.
SEMI · HERMETIC AIR-COOLED UNIT CONDENSER CONFIGURATION TABLE
Unit model |
Compressor |
air-cooled condenser |
receiver |
Inlet diameter Φ mm |
Outlet diameter Φmm |
||||
Model |
Power Source |
Power KW |
Model |
fan |
Volume L |
||||
Power Source |
Power KW |
||||||||
BFB-FJZ-3HP(Y) |
BFBZ3 12(Y) |
Power 380V/3~/50Hz Control220/1~50Hz (460/3~/60Hz) |
2.2 |
BF-FNK03S |
380V/3~/50Hz(460/3~/60Hz)
|
0.18 |
7 |
19.5 |
12 |
BFB-FJZ-4HP(Y) |
BFBZ4 15(Y) |
2.2 |
BF-FNK04S |
0.25 |
9.5 |
25 |
12 |
||
BFB-FJZ-4HPH(Y) |
BFBZ4 15H(Y) |
3 |
BF-FNK04SH |
0.25 |
9.5 |
25 |
12 |
||
BFB-FJZ-5HP(Y) |
BFBZ5 18(Y) |
3.7 |
BF-FNK05S |
0.25 |
9.5 |
25 |
12 |
||
BFB-FJZ-5HPH(Y) |
BFBZ5 18H(Y) |
5.1 |
BF-FNK05SH |
0.25 |
9.5 |
25 |
12 |
||
BFB-FJZ-8HPH(Y) |
BFBZ8 27H(Y) |
5.5 |
BF-FNK08S |
0.37 |
15 |
31.75 |
16 |
||
BFB-FJZ-10HP(Y) |
BFBZ10 36(Y) |
7.5 |
BF-FNK10S |
0.5 |
19.5 |
31.75 |
16 |
||
BFB-FJZ-10HPH(Y) |
BFBZ10 36H(Y) |
9.6 |
BF-FNK10SH |
0.5 |
19.5 |
31.75 |
16 |
||
BFB-FJZ-15HP(Y) |
BFBZ1554(Y) |
10.5 |
BF-FNK15S |
0.74 |
28 |
38 |
16 |
||
BFB-FJZ-15HPH(Y) |
BFBZ1554H(Y) |
12 |
BF-FNK15SH |
0.74 |
28 |
38 |
16 |
||
BFB-FJZ_V3HP(Y) |
BFBV318.1(Y) |
2.2 |
BF-FNK04S |
0.25 |
15 |
22 |
12 |
||
BFB-FJZ-V5HPH(Y) |
BFBV5 18.2H(Y) |
3 |
BF-FNK05S |
0.25 |
15 |
22 |
12 |
||
BFB-FJZ_V4HP(Y) |
BFBV4 22.7(Y) |
3 |
BF-FNK05S |
0.25 |
15 |
28 |
12 |
||
BFB-FJZ-V6HPH(Y) |
BFBV6 22.7H(Y) |
3.7 |
BF-FNK05S |
0.37 |
15 |
28 |
12 |
||
BFB-FJZ_V5HP(Y) |
BFBV5 26.8(Y) |
3.7 |
BF-FNK05S |
0.37 |
15 |
28 |
12 |
||
BFB-FJZ-V7HPH(Y) |
BFBV7 26.8H(Y) |
5.1 |
BF-FNK08SH |
0.37 |
19.5 |
28 |
16 |
||
BFB-FJZ_V6HP(Y) |
BFBV6 32.5(Y) |
4.5 |
BF-FNK05SH |
0.25 |
15 |
28 |
16 |
||
BFB-FJZ-V9HPH(Y) |
BFBV9 32.5H(Y) |
5.5 |
BF-FNK10S |
0.25 |
19.5 |
28 |
16 |
||
BFB-FJZ-V8HP(Y) |
BFBV8 41.3(Y) |
5.5 |
BF-FNK10S |
0.25 |
22 |
35 |
16 |
||
BFB-FJZ-V12HPH(Y) |
BFBV1241.3H(Y) |
8.8 |
BF-FNK10SH |
0.25 |
22 |
35 |
16 |
||
BFB-FJZ-VIOHP(Y) |
BFBV1048.5(Y) |
7.4 |
BF-FNK10S |
0.25 |
22 |
35 |
16 |
||
BFB-FJZ-V15HPH(Y) |
BFBV1548.5H(Y) |
11 |
BF-FNK18SH |
0.37 |
28 |
42 |
16 |
||
BFB-FJZ-V12HP(Y) |
BFBV1256(Y) |
9.1 |
BF-FNK15S |
0.37 |
22 |
35 |
16 |
||
BFB-FJZ-V20HPH(Y) |
BFBV2056H(Y) |
15 |
BF-FNK-20SH |
0.78 |
28 |
42 |
22 |
||
BFB-FJZ-V15HP(Y) |
BFBV1573.7(Y) |
11 |
BF-FNK-15SH |
0.6 |
38 |
42 |
22 |
||
BFB-FJZ-V25HPH(Y) |
BFBV2573.7H(Y) |
18 |
BF-FNK-15ST |
0.8 |
38 |
42 |
22 |
||
BFB-FJZ-V20HP(Y) |
BFBV20 84.5(Y) |
15 |
BF-FNK-20S |
0.78 |
38 |
42 |
22 |
||
BFB-FJZ-V30HPH(Y) |
BFBV30 84.5H(Y) |
22 |
BF-FNK-30S |
0.45 |
38 |
42 |
22 |
||
BFB-FJZ-W25HP(Y) |
BFBW25110_5(Y) |
18 |
BF-FNK-25S |
0.8 |
38 |
42 |
22 |
||
BFB-FJZ-W35HPH(Y) |
BFBW35110.5H(Y) |
27 |
BF-FNK-30SH |
0.6 |
38 |
42 |
28 |
||
BFB_FJZ-W30HP(Y) |
BFBW30 126_8(Y) |
22 |
BF-FNK-30S |
0.45 |
38 |
42 |
22 |
||
BFB-FJZ-W40HPH(Y) |
BFBW40 126.8H(Y) |
30 |
BF-FNK-40S |
0.6 |
75 |
54 |
28 |
||
BFB_FJZ-W40HP(Y) |
BFBW40151.6(Y) |
30 |
BF-FNK-35S |
0.45 |
75 |
54 |
28 |
||
BFB-FJZ-W50HPH(Y) |
BFBW50151.6H(Y) |
37 |
BF-FNK-50S |
0.78 |
75 |
54 |
28 |
SEMI · HERMETIC WATER-COOLED UNIT CONDENSER CONFIGURATION TABLE
Unit model |
Compressor |
water-cooled condenser |
Inlet diameter Φ mm |
Outlet diameter Φ mm |
|||
Model |
Power Source |
Power KW |
Model |
Water pipe in |
|||
BFB-WJZ-3HP(Y) |
BFBZ3 12(Y) |
Power 38V/3~/50Hz Control220/1~50Hz (460/3~/60Hz) |
2.2 |
BF-WN-3HP |
1 |
19.5 |
12 |
BFB-WJZ-4HP(Y) |
BFBZ4 15(Y) |
2.2 |
BF-WN-4HP |
1 |
25 |
12 |
|
BFB-WJZ-4HPH(Y) |
BFBZ4 15H(Y) |
3 |
BF-WN-4HPA① |
1-1/4 |
25 |
12 |
|
BFB-WJZ-5HP(Y) |
BFBZ5 18(Y) |
3.7 |
BF-WN-5HP |
1-1/2 |
25 |
12 |
|
BFB-WJZ-5HPH(Y) |
BFBZ5 18H(Y) |
5.1 |
BF-WN-5HP A① |
1-1/2 |
258 |
12 |
|
BFB-WJZ_8HPH(Y) |
BFBZ8 27(Y) |
5.5 |
BF-WN-8HP |
1-1/2 |
31.75 |
16 |
|
BFB-WJZ-IOHP(Y) |
BFBZ10 36(Y) |
7.5 |
BF-WN-10HP |
1-1/2 |
31.75 |
16 |
|
BFB-WJZ-IOHPH(Y) |
BFBZ10 36H(Y) |
9.6 |
BF-WN-10HP A① |
1-1/2 |
31.75 |
16 |
|
BFB-WJZ-15HP(Y) |
BFBZ15 54(Y) |
10.5 |
BF-WN-15HP |
1-1/2 |
38 |
16 |
|
BFB-WJZ-15HPH(Y) |
BFBZ15 54H(Y) |
12 |
BF-WN-15HP A① |
1-1/2 |
38 |
16 |
|
BFB-WJZ-V3HP(Y) |
BFBV3 18.1(Y) |
2.2 |
BF-WN-4HP High |
1-1/2 |
22 |
12 |
|
BFB-WJZ-V5HPH(Y) |
BFBV518.1H(Y) |
3 |
BF-WN-5HP High |
1-1/2 |
22 |
12 |
|
BFB-WJZ-V4HP(Y) |
BFBV4 22.7(Y) |
3 |
BF-WN-5HP Medium |
1-1/2 |
28 |
12 |
|
BFB-WJZ-V6HPH(Y) |
BFBV6 22.7H(Y) |
3.7 |
BF-WN-8HP Medium |
1-1/2 |
28 |
12 |
|
BFB-WJZ-V5HP(Y) |
BFBV5 26.8(Y) |
3.7 |
BF-WN-5HP Medium |
1-1/2 |
28 |
12 |
|
BFB-WJZ-V7HP(Y) |
BFBV7 26.8H(Y) |
5.1 |
BF-WN-8HP High |
1-1/2 |
28 |
16 |
|
BFB-WJZ-V6HP(Y) |
BFBV6 32.5(Y) |
4.5 |
BF-WN-8HP Medium |
1-1/2 |
28 |
16 |
|
BFB-WJZ-V9HPH(Y) |
BFBV9 32.5H(Y) |
5.5 |
BF-WN-10HP High |
1-1/2 |
28 |
16 |
|
BFB-WJZ-V8HP(Y) |
BFBV8 41.3(Y) |
5.5 |
BF-WN-10HP High |
1-1/2 |
35 |
16 |
|
BFB-WJZ-V12HPH(Y) |
BFBV12 41.3H(Y) |
8.8 |
BF-WN-15HP High |
1-1/2 |
35 |
16 |
|
BFB-WJZ-VIOHP(Y) |
BFBV10 48.5(Y) |
7.4 |
BF-WN-15HP Medium |
1-1/2 |
35 |
16 |
|
BFB-WJZ-V15HPH(Y) |
BFBV15 48.5H(Y) |
11 |
BF-WN-20HP Medium |
2-1/2 |
42 |
16 |
|
BFB-WJZ-V12HP(Y) |
BFBV12 56(Y) |
9.1 |
BF-WN-15HP High |
1-1/2 |
35 |
16 |
|
BFB-WJZ-V20HPH(Y) |
BFBV20 56(Y) |
15 |
BF-WN-20HP High |
2-1/2 |
42 |
22 |
|
BFB-WJZ-V15HP(Y) |
BFBV15 73.7(Y) |
11 |
BF-WN-20HP High |
2-1/2 |
42 |
22 |
|
BFB-WJZ-V25HPH(Y) |
BFBV25 73.7H(Y) |
18 |
BF-WN-30HP High |
2-1/2 |
42 |
22 |
|
BFB-WFJZ-V20HP(Y) |
BFBV20 84.5(Y) |
15 |
BF-WN-20HP |
2-1/2 |
42 |
12 |
|
BFB-WFJZ-W25HP(Y) |
BFBW25110.5(Y) |
18 |
BF-WN-25HP |
2-1/2 |
54 |
22 |
|
BFB-WFJZ-V30HPH(Y) |
BFBV30 84.5H(Y) |
22 |
BF-WN-30HP |
2-1/2 |
54 |
22 |
|
BFB-WFJZ-W30HP(Y) |
BFBW30126.8(Y) |
22 |
BF-WN-30HP |
2-1/2 |
54 |
22 |
|
BFB-WFJZ-W35HPH(Y) |
BFBW35110.5H(Y) |
27 |
BF-WN-35HP |
2-1/2 |
54 |
28 |
|
BFB-WFJZ-W40HPH(Y) |
BFBW40126.8H(Y) |
30 |
BF-WN-40HP |
2-1/2 |
54 |
28 |
|
BFB-WFJZ-W40HP(Y) |
BFBW40151.6(Y) |
30 |
BF-WN-40HP |
2-1/2 |
54 |
28 |
|
BFB-WFJZ-W50HPH(Y) |
BFBW50151.6H(Y) |
37 |
BF-WN-50HP |
2-1/2 |
54 |
28 |
|
BFB-WFJZ-W80HPH(Y) |
BFBW40151.6x2 |
30x2 |
BF-WN-75HP |
3" |
76 |
35 |
|
BFB-WFJZ-W90HPH(Y) |
BFBV30 84.5Hx3 |
22x3 |
90 RT |
4" |
89 |
35 |
|
BFB-WFJZ-W120HPH(Y) |
BFBW40151.6x3 |
30x3 |
110RT |
4" |
108 |
42 |
|
BFB-WFJZ-W200HPH(Y) |
BFBW50151.6Hx4 |
37x4 |
170RT |
Dn150 |
108 |
54 |
Notes:
1) With A means it is the new model of expand heat exchage area.
2) In advance fill polyester oil and then charing R134 aor R404A,The fither screen use XH-10 or XH11,after recharing refrigreant that
should be same type.
3) The peformance data of paralley unit,which is same as two times single compressor.if you need the deatil information,please contact us,
4) If you need refrigeration capacity is not in the table and power 460/3-60Hz,you can contact us.
If you have any questions or need help, please contact us directly, we will provide you with online help and services in time.
Professional refrigeration equipment manufacturer
Zhejiang Beifeng Refrigeration Equipment Co., Ltd. has 35 years history of manufacturing refrigeration equipment. Currently, it has two processing bases located in Shengzhou, Zhejiang, with a production building of 60,000 square meters. It has set up three sales companies in Shanghai, Beijing, and Guangzhou, with strong technical force, advanced equipment, complete varieties and stable quality. The company has a high-quality inspection center to detect the performance index of refrigeration products and imported vacuum-type helium leak detectors for condensers and evaporators. It has a great influence in the national refrigeration industry and occupies a large market, with distributors in all major cities; It enjoys a high reputation not only in the domestic market, but also in the overseas market, and the products are exported to Europe, Southeast Asia, the Middle East, North America, Africa, etc.
In the refrigeration process, the fair design of the condenser is an important part of improving the energy efficiency r...
In industrial air conditioning refrigeration systems, evaporators, condensers, compressors and throttle valves are four ...
Different condensers according to steam condensation can be divided into surface type (also called partition type) and m...
Air coolers can be used for cooling or condensation, and are widely used in: refining, condensation of petrochemical ove...
In summer, the compressor's exhaust temperature is relatively high and the hand cannot touch it. According to national s...
An air cooler is a heat exchanger that uses air as a cooling medium to cool a warm stream to a desired temperature. Refe...